BLD19-00122
| FIRE-Final Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 2:34:34 PM | P | CANC |
|
|
Project related FIR permit for fire sprinklers needs to be finaled before life fire safety inspection can be completed, informed point of contact to coordinate life fire safety inspection with fire sprinkler final, this request is cancelled per conversation with point of contact.
Robert Phone #: ###-####
|
FIR19-00173
| INSP-Final Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 1:55:15 PM | P | PASS |
|
|
Previously noted items have been corrected, final fire alarm inspection complete.
John Howard, Tech Phone #: ###-#### Inspection requested via web by John Siewert
|
FIR18-00644
| INSP-Final Inspection | 3/27/2019 | 3/28/2019 | 3/28/2019 12:42:13 PM | A | FAIL |
|
|
Fire panel that was installed does not match what was submitted. Communicator showing trouble at time of inspection. In-duct detectors report to panel as a trouble with no RTU shutdown on both HVAC units. Provide a different type of notification appliance in horn location, horns do not sync with speaker strobes as well as overpowering the sound of the surrounding speaker strobes. Signals were not verified at time of inspection.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00501
| INSP-Sprinkler Rough-in | 3/27/2019 | 3/28/2019 | 3/28/2019 11:17:10 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler pipingt in otter and monkey exhibit complete, monkey and otter exhibit approved for cover.
George Jess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD17-04626
| FIRE-Final Inspection | 3/27/2019 | 3/28/2019 | 3/28/2019 10:49:51 AM | A | CANC |
|
|
Fire sprinkler did not pass inspection, this request cancelled per conversation with point of contact.
fire , Life ; Safety. fire sprinkler is scheduled for tomorrow am. Phone #: ###-#### Inspection requested via web by J.C. Murray
|
FIR18-00636
| INSP-Final Inspection | 3/27/2019 | 3/28/2019 | 3/28/2019 10:49:16 AM | A | FAIL |
|
|
Numerous overspaced issues throughout building next to kitchen, relocate hedas as discussed. Numerous heads to close to registers in restrooms, relocate head or provide intermediate temperature head in discussed locations. Provide heaqd box with required amount and style of heads.
Gerardo Arce is the contact. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00530
| INSP-Final Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 10:47:13 AM | A | PASS |
|
|
Final fire alarm inspection complete, signals verified.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
FIR18-00544
| INSP-Final Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 8:50:07 AM | P | PASS |
|
|
Final inspection for underground supply complete.
Gerardo Arce is the contact. This inspection has already been done, reach out to the contact for more information. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00545
| INSP-Final Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 8:49:49 AM | P | PASS |
|
|
Final inspection for underground supply complete.
Gerardo Arce is the contact. This inspection has already been done, reach out to the contact for more information. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00563
| INSP-Final Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 8:49:32 AM | P | PASS |
|
|
Final inspection for underground supply complete.
Gerardo Arce is the contact. This inspection has already been done, reach out to the contact for more information. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00519
| INSP-Final Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 8:49:15 AM | P | PASS |
|
|
Final inspection for underground supply complete.
Gerardo Arce is the contact. This inspection has already been done, reach out to the contact for more information. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00562
| INSP-Final Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 8:48:59 AM | P | PASS |
|
|
Final inspection for underground supply complete.
Gerardo Arce is the contact. This inspection has already been done, reach out to the contact for more information. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00938
| INSP-Final Inspection | 3/27/2019 | 3/28/2019 | 3/28/2019 7:00:05 AM | A | CANC |
|
|
Dave Phone #: ###-#### Inspection cancelled from web by: david davis
|