Inspections for the day of: Friday, March 29, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00565 INSP-Sprinkler Rough-in3/26/20193/29/20193/29/2019 3:19:31 PMPPASS
Tenting/insulation inspection for fire sprinklers in remaining units complete, approved for cover. Rough to ocver ispection complete for all units in this building.



insulation inspection for units 128, 130, and 132 // Jonathan Phone #: ###-####
BLD17-04623 FIRE-Conference3/29/20193/29/20193/29/2019 3:06:56 PMPDONE
Each building that is requiring heat trace on the fire sprinkler lines has a FIR permit associated with the heat trace install. Inspection for heat trace needs to be scheduled with the associated permit for proper inspection procedure.

Breezeway sprinkler pipe heat tape insulation inspection
for Buildings A B C E. Phone #: ###-#### Inspection requested via web by J.C. Murray
BLD17-04626 FIRE-Final Inspection3/28/20193/29/20193/29/2019 3:04:58 PMACANC
Fire sprinkler ispection is scheduled for 01APR2019, this inspection will be rescheduled to coincide with fire sprinkler final, this request is cancelled per conversation with poiunt of contact.

Fire, life ; Safety Phone #: ###-#### Inspection requested via web by J.C. Murray
BLD19-00582 FIRE-Final Inspection3/29/20193/29/20193/29/2019 2:51:22 PMPCANC
Spoke with point of contact, life fire safety inspection will be rescheduled to coincide with fire sprinkler inspection. This request is cancelled.

Tina-(works with Nick) Phone #: ###-####
FIR18-00644 INSP-Final Inspection3/29/20193/29/20193/29/2019 2:33:08 PMPPASS
Previously noted items have been corrected, final fire alarm inspection complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00311 INSP-Final Inspection3/28/20193/29/20193/29/2019 1:39:33 PMAFAIL
Escutcheon is stairway is painted. Install escutcheon in HVAC closet. Provide conditioned in garage to maintain 40 degrees or above to be code compliant.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00319 INSP-Final Inspection3/28/20193/29/20193/29/2019 1:29:21 PMAFAIL
4 heads to close to heat registers, a minimum of 24 inches is allowed per NFPA 13D. Head in master bathroom needs to be relocated to spray in shower area, walls of shower do not go all the way to the ceiling so shower is not a seperate compartment. Garage needs to be a conditioned spaces due to fire sprinkler install.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00673 INSP-Sprinkler Rough-in3/28/20193/29/20193/29/2019 12:31:38 PMAPASS
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover. All rough in inspections for project complete.

Todd Phone #: ###-####
BLD18-04110 FIRE-Conference3/28/20193/29/20193/29/2019 11:31:39 AMAFAIL
Fire conference complete. Provide addressing for each suite. Provide sticker on each suite main entry reading "Door to remian unlocked while building is occupied. Fire alarm system that is in place is not code compliant and appears to never have been permitted, fire alarm system needs to be code compliant or verify if fire alarm system can be removed (a permit will be required for fire alarm removal if authorized for demo). Slide bolt locks need to be removed on east exit doors. Provide code compliant locking hardware on suite main entry doors. Provide annual inspection for all fire extinguishers. Gate on east side of building is in the path of egress, gate needs to have code compliant door hardware for egress purposes.

please Tyler for access Phone #: ###-####
FIR19-00050 INSP-Sprinkler Rough-in3/28/20193/29/20193/29/2019 10:38:07 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Tom Phone #: ###-####
BLD19-00423 FIRE-Final Inspection3/28/20193/29/20193/29/2019 10:22:52 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher will be placed in discussed location with a current inspection tag. Final life fire safety inspection for area of work complete. Southeast ecterior temp door to be replaced with new door/code compliant hardware when received.

Charlie Phone #: ###-####
BLD19-00462 FIRE-Final Inspection3/28/20193/29/20193/29/2019 10:20:51 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher will be placed in discussed location with a current inspection tag. Final life fire safety inspection for area of work complete.

Charlie Phone #: ###-####
FIR17-00612 INSP-Final Inspection3/28/20193/29/20193/29/2019 9:28:11 AMAFAIL
Alarm pressure switch on both east and west dry systems not hooked up to FDC bell, valve labeling on alarm side does match valve configuration.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00098 INSP-Final Inspection3/28/20193/29/20193/29/2019 9:26:12 AMAFAIL
West side dry system tamper is labeled west anti-freeze, west anti-freeze tamper is not reporting to panel. FDC bell is not hooked up to alarm pressure switch on east and west dry systems.

alarm not sprinklers // Barnie Phone #: ###-####