BLD18-04471
| FIRE-Final Inspection | 3/4/2019 | 3/4/2019 | 3/4/2019 3:48:59 PM | P | FAIL |
|
|
Could not locate city approved draiwngs for work that was completed.
Dave Phone #: ###-####
|
BLD18-04159
| FIRE-Final Inspection | 3/4/2019 | 3/4/2019 | 3/4/2019 3:36:06 PM | P | FAIL |
|
|
Emergency lighting does not match the city approved draiwngs. Provide emergency lighitng for exterior discharge per 2015 IFC section 1008. Provide fire extinguisher on level 2 as discussed.
gREG Phone #: ###-####
|
FIR18-00640
| INSP-Sprinkler Rough-in | 2/28/2019 | 3/4/2019 | 3/4/2019 2:44:16 PM | P | FAIL |
|
|
Office fire sprinkler piping does not match city approved drawings. 2 inch teardrop hangers on 4 inch main trapeze needs to be changed to the correct heavy duty type hangers. Hanger attachment in pit under paint booth does not match any of the submitted attachment methods. Provide fire sprinklers under overhead doors by paint booth. Verify added 90's on 6 inch will work with calcs. Add fire sprinklers btween paint booth and main building, no sprinklers in mentioned area at time of inspection and buildings are connected. Provide and submit heat calculations to verify upright heads will not freeze in attic space and area between main building and paint booth.
Austin Farnsworth is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-04531
| FIRE-Final Inspection | 3/4/2019 | 3/4/2019 | 3/4/2019 1:19:28 PM | P | CANC |
|
|
Per conversation with fire alarm contractor, fire alarm system is not ready for inspection. FIR permit for fire alarms needs to be finaled before life fire safety inspection can be completed, this request is cancelled.
Tom Phone #: ###-####
|
BLD18-02551
| FIRE-Final Inspection | 3/4/2019 | 3/4/2019 | 3/4/2019 1:19:07 PM | P | CANC |
|
|
Per conversation with fire alarm contractor, fire alarm system is not ready for inspection. FIR permit for fire alarms needs to be finaled before life fire safety inspection can be completed, this request is cancelled.
jr Phone #: ###-####
|
FIR19-00087
| INSP-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 1:16:53 PM | A | PASS |
|
|
Final fire alarm ispection for scope of work complete.
Inspection has to be between 10am and 2pm please call1/2 hour ahead Phone #: ###-#### Inspection requested via web by Rafe Barrett
|
FIR19-00078
| INSP-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 12:32:00 PM | A | CANC |
|
|
Fire alarm system not ready for inspection per conversation with point of contact. Inspection request will be re-scheduled for a later date.
Please call 1/2 hour ahead Phone #: ###-#### Inspection requested via web by Rafe Barrett
|
BLD19-00544
| FIRE-Final Inspection | 2/28/2019 | 3/4/2019 | 3/4/2019 12:31:07 PM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Mike Phone #: ###-####
|
FIR19-00114
| INSP-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 12:20:47 PM | A | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Please call 1/2 hour ahead Phone #: ###-#### Inspection requested via web by Rafe Barrett
|
FIR19-00054
| INSP-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 10:59:13 AM | A | CANC |
|
|
Cancelled per conversarion with point of contact.
Jason Phone #: ###-####
|
FIR19-00048
| INSP-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 10:58:56 AM | A | CANC |
|
|
Cancelled per conversarion with point of contact.
Jason Phone #: ###-####
|
FIR19-00040
| INSP-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 10:58:23 AM | A | FAIL |
|
|
Communicator battery trouble did not report to cenral station.
Jason Phone #: ###-####
|
FIR19-00039
| INSP-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 10:57:51 AM | A | FAIL |
|
|
Communicator battery trouble did not report to cenral station.
Jason Phone #: ###-####
|
FIR19-00041
| INSP-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 10:28:43 AM | A | FAIL |
|
|
Tested initiating device on zone 1, did not annunciate at fire panel or local notification, alarm event did report to monitoring.
Jason Phone #: ###-####
|
BLD17-04425
| FIRE-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 9:00:02 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Permit numbers at bottom of page are different due to all pages being issued at the same time. Phone #: ###-#### Inspection requested via web by Brandon Reynolds
|
BLD17-04413
| FIRE-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 8:59:27 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Permit numbers at the bottom of the page dont match because all drawings were submitted in a set. Phone #: ###-#### Inspection requested via web by Brandon Reynolds
|
BLD18-00945
| FIRE-Final Inspection | 3/1/2019 | 3/4/2019 | 3/4/2019 8:28:12 AM | A | FAIL |
|
|
As stated before, no fire alarm inspection has been requested nor finaled for area of work, fire life safety inspection will not be performed or completed until fire alarms are inspected and passed, during hood inspection is was noticed that the fire alarm system has 3 different tones in the gym area when fire alarm is activated, this is not code compliant.
Ronald-partial life safety kitchen only Phone #: ###-####
|
FIR18-00640
| INSP-Sprinkler Rough-in | 2/28/2019 | 3/4/2019 | 2/28/2019 2:50:52 PM | A | CANC |
|
|
Austin Farnsworth is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|