Inspections for the day of: Monday, March 4, 2019.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-04471 FIRE-Final Inspection3/4/20193/4/20193/4/2019 3:48:59 PMPFAIL
Could not locate city approved draiwngs for work that was completed.

Dave Phone #: ###-####
BLD18-04159 FIRE-Final Inspection3/4/20193/4/20193/4/2019 3:36:06 PMPFAIL
Emergency lighting does not match the city approved draiwngs. Provide emergency lighitng for exterior discharge per 2015 IFC section 1008. Provide fire extinguisher on level 2 as discussed.

gREG Phone #: ###-####
FIR18-00640 INSP-Sprinkler Rough-in2/28/20193/4/20193/4/2019 2:44:16 PMPFAIL
Office fire sprinkler piping does not match city approved drawings. 2 inch teardrop hangers on 4 inch main trapeze needs to be changed to the correct heavy duty type hangers. Hanger attachment in pit under paint booth does not match any of the submitted attachment methods. Provide fire sprinklers under overhead doors by paint booth. Verify added 90's on 6 inch will work with calcs. Add fire sprinklers btween paint booth and main building, no sprinklers in mentioned area at time of inspection and buildings are connected. Provide and submit heat calculations to verify upright heads will not freeze in attic space and area between main building and paint booth.


Austin Farnsworth is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-04531 FIRE-Final Inspection3/4/20193/4/20193/4/2019 1:19:28 PMPCANC
Per conversation with fire alarm contractor, fire alarm system is not ready for inspection. FIR permit for fire alarms needs to be finaled before life fire safety inspection can be completed, this request is cancelled.

Tom Phone #: ###-####
BLD18-02551 FIRE-Final Inspection3/4/20193/4/20193/4/2019 1:19:07 PMPCANC
Per conversation with fire alarm contractor, fire alarm system is not ready for inspection. FIR permit for fire alarms needs to be finaled before life fire safety inspection can be completed, this request is cancelled.

jr Phone #: ###-####
FIR19-00087 INSP-Final Inspection3/1/20193/4/20193/4/2019 1:16:53 PMAPASS
Final fire alarm ispection for scope of work complete.

Inspection has to be between 10am and 2pm please call1/2 hour ahead Phone #: ###-#### Inspection requested via web by Rafe Barrett
FIR19-00078 INSP-Final Inspection3/1/20193/4/20193/4/2019 12:32:00 PMACANC
Fire alarm system not ready for inspection per conversation with point of contact. Inspection request will be re-scheduled for a later date.

Please call 1/2 hour ahead Phone #: ###-#### Inspection requested via web by Rafe Barrett
BLD19-00544 FIRE-Final Inspection2/28/20193/4/20193/4/2019 12:31:07 PMAPASS
Final life fire safety inspection for area of work complete.

Mike Phone #: ###-####
FIR19-00114 INSP-Final Inspection3/1/20193/4/20193/4/2019 12:20:47 PMAPASS
Final fire alarm inspection for scope of work complete.

Please call 1/2 hour ahead Phone #: ###-#### Inspection requested via web by Rafe Barrett
FIR19-00054 INSP-Final Inspection3/1/20193/4/20193/4/2019 10:59:13 AMACANC
Cancelled per conversarion with point of contact.

Jason Phone #: ###-####
FIR19-00048 INSP-Final Inspection3/1/20193/4/20193/4/2019 10:58:56 AMACANC
Cancelled per conversarion with point of contact.

Jason Phone #: ###-####
FIR19-00040 INSP-Final Inspection3/1/20193/4/20193/4/2019 10:58:23 AMAFAIL
Communicator battery trouble did not report to cenral station.

Jason Phone #: ###-####
FIR19-00039 INSP-Final Inspection3/1/20193/4/20193/4/2019 10:57:51 AMAFAIL
Communicator battery trouble did not report to cenral station.

Jason Phone #: ###-####
FIR19-00041 INSP-Final Inspection3/1/20193/4/20193/4/2019 10:28:43 AMAFAIL
Tested initiating device on zone 1, did not annunciate at fire panel or local notification, alarm event did report to monitoring.

Jason Phone #: ###-####
BLD17-04425 FIRE-Final Inspection3/1/20193/4/20193/4/2019 9:00:02 AMAPASS
Final life fire safety inspection for area of work complete.

Permit numbers at bottom of page are different due to all pages being issued at the same time. Phone #: ###-#### Inspection requested via web by Brandon Reynolds
BLD17-04413 FIRE-Final Inspection3/1/20193/4/20193/4/2019 8:59:27 AMAPASS
Final life fire safety inspection for area of work complete.

Permit numbers at the bottom of the page dont match because all drawings were submitted in a set. Phone #: ###-#### Inspection requested via web by Brandon Reynolds
BLD18-00945 FIRE-Final Inspection3/1/20193/4/20193/4/2019 8:28:12 AMAFAIL
As stated before, no fire alarm inspection has been requested nor finaled for area of work, fire life safety inspection will not be performed or completed until fire alarms are inspected and passed, during hood inspection is was noticed that the fire alarm system has 3 different tones in the gym area when fire alarm is activated, this is not code compliant.

Ronald-partial life safety kitchen only Phone #: ###-####
FIR18-00640 INSP-Sprinkler Rough-in2/28/20193/4/20192/28/2019 2:50:52 PMACANC
Austin Farnsworth is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus