Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00204 INSP-Final Inspection3/5/20193/5/20193/5/2019 3:14:06 PMPCANC
Cancelled per conversation with point of contact, will be rescheduled for a later date.

Bill Phone #: ###-####
FIR18-00930 INSP-Final Inspection3/4/20193/5/20193/5/2019 2:43:32 PMAPART
Trip test was completed with Lee Meridith, could not perform walkthrough due to time constraints. Final walk through of project will need to be completed.

Zack Grasmick is the contact. Needing a final and a trial test. Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00078 INSP-Final Inspection3/5/20193/5/20193/5/2019 2:40:36 PMPCANC
Fire alarm system not ready for inspection per conversation with point of contact. Inspection request will be re-scheduled for a later date.

Please make last inspection for the day. Call 1/2 hour ahead Phone #: ###-#### Inspection requested via web by Rafe Barrett
BLD18-02551 FIRE-Final Inspection3/5/20193/5/20193/5/2019 2:26:04 PMPCANC
Call 30 minutes prior to late afternoon preferred Phone #: ###-#### >> Inspection requested via web by Johnathon McGee Inspection cancelled from web by: Johnathon McGee
BLD18-04159 FIRE-Final Inspection3/5/20193/5/20193/5/2019 2:00:54 PMPPASS
Previously noted items have been corrected, final life fire safety inspection for area of work complete.

Greg Phone #: ###-####
FIR18-00267 INSP-Sprinkler Rough-in3/4/20193/5/20193/5/2019 1:37:24 PMPPART
Fire pump commissioning complete.

fire pump test // justin Phone #: ###-####
FIR18-00964 INSP-Sprinkler Rough-in3/4/20193/5/20193/5/2019 12:28:38 PMAPART
Rough to cover inspection for overhead fire sprinkler piping on system 1 complete, notated city approved drawings where system 1 is approved for cover.

Cordinate inpsection with Lonnie Greenfield Phone #: ###-#### Inspection requested via web by Christophe Wilson
FIR18-00828 INSP-Sprinkler Rough-in3/5/20193/5/20193/5/2019 11:15:21 AMAFAIL
Level 3 is not approved for cover, tenting has been removed in numerous areas, needs to be corrected before cover is approved.
FIR18-00828 INSP-Sprinkler Rough-in3/5/20193/5/20193/5/2019 11:14:01 AMAPART
Rough to cover inspection for overhead fire sprinkler piping on levels 1 and 2 complete, levels 1 and 2 approved for cover.
FIR18-00828 INSP-Sprinkler Rough-in/Hydro3/4/20193/5/20193/5/2019 11:12:38 AMAPART
Hydrostatic test for level 1 and 2 witnessed, no pressure loss observed.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00563 INSP-Supply line flush3/4/20193/5/20193/5/2019 11:12:03 AMADONE
Underground main line flush complete.

Gabe Garduno is the contact. This is inspection is for an flush and hydro. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00004 INSP-Sprinkler Rough-in3/5/20193/5/20193/5/2019 9:52:59 AMAPART
Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, tenting not installed at time of inspection, piping in attic spaces requiring tenting not approved for cover.
FIR19-00004 INSP-Sprinkler Rough-in/Hydro3/4/20193/5/20193/5/2019 9:51:53 AMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Please call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD18-04471 FIRE-Final Inspection3/5/20193/5/20193/5/2019 9:28:40 AMAPASS
Final life fire safety inspection for area of work complete.

BLD18-02512 FIRE-Final Inspection3/5/20193/5/20193/5/2019 9:22:39 AMPPASS
Final life fire safety inspection for area of work complete.

Pete Phone #: ###-####
BLD17-03191 FIRE-Final Inspection3/5/20193/5/20193/5/2019 9:22:04 AMPPASS
Final life fire safety inspection for area of work complete.

Pete Phone #: ###-####
BLD17-02577 FIRE-Final Inspection3/5/20193/5/20193/5/2019 9:21:44 AMPPASS
Final life fire safety inspection for area of work complete.

Pete Phone #: ###-####
FIR18-00825 INSP-Final Inspection3/4/20193/5/20193/5/2019 9:20:12 AMAPASS
Final fire alarm inspection for area of work complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00214 INSP-Final Inspection3/4/20193/5/20193/5/2019 9:19:27 AMAPASS
Final fire alarm inspection for area of work complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00213 INSP-Final Inspection3/4/20193/5/20193/5/2019 9:18:48 AMAPASS
Final fire alarm inspection for area of work complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00740 INSP-Final Inspection3/4/20193/5/20193/5/2019 12:00:00 AMAFAIL
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah.

Numerous strobes at wrong height.One Visible coverage is inadequate at speaker SP1:30 in Kitchen. 15cd strobe PS:11:4:5 at vending brown bag needs to be removed. Adjust 11:4:1 to compensate. Its blocked by Refers. Strobes too low and/or blocked by shelves are 10:2:1, 10:2:210:1:4 and 20:2:4. All other equipment tested ok. Audible and visible needs to be retested.
FIR19-00160 INSP-Final Inspection3/4/20193/5/20193/5/2019 12:00:00 AMAPASS
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah