FIR18-00204
| INSP-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 3:14:06 PM | P | CANC |
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Bill Phone #: ###-####
|
FIR18-00930
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 2:43:32 PM | A | PART |
|
|
Trip test was completed with Lee Meridith, could not perform walkthrough due to time constraints. Final walk through of project will need to be completed.
Zack Grasmick is the contact. Needing a final and a trial test. Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00078
| INSP-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 2:40:36 PM | P | CANC |
|
|
Fire alarm system not ready for inspection per conversation with point of contact. Inspection request will be re-scheduled for a later date.
Please make last inspection for the day. Call 1/2 hour ahead Phone #: ###-#### Inspection requested via web by Rafe Barrett
|
BLD18-02551
| FIRE-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 2:26:04 PM | P | CANC |
|
|
Call 30 minutes prior to late afternoon preferred Phone #: ###-#### >> Inspection requested via web by Johnathon McGee Inspection cancelled from web by: Johnathon McGee
|
BLD18-04159
| FIRE-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 2:00:54 PM | P | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection for area of work complete.
Greg Phone #: ###-####
|
FIR18-00267
| INSP-Sprinkler Rough-in | 3/4/2019 | 3/5/2019 | 3/5/2019 1:37:24 PM | P | PART |
|
|
Fire pump commissioning complete.
fire pump test // justin Phone #: ###-####
|
FIR18-00964
| INSP-Sprinkler Rough-in | 3/4/2019 | 3/5/2019 | 3/5/2019 12:28:38 PM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping on system 1 complete, notated city approved drawings where system 1 is approved for cover.
Cordinate inpsection with Lonnie Greenfield Phone #: ###-#### Inspection requested via web by Christophe Wilson
|
FIR18-00828
| INSP-Sprinkler Rough-in | 3/5/2019 | 3/5/2019 | 3/5/2019 11:15:21 AM | A | FAIL |
|
|
Level 3 is not approved for cover, tenting has been removed in numerous areas, needs to be corrected before cover is approved.
|
FIR18-00828
| INSP-Sprinkler Rough-in | 3/5/2019 | 3/5/2019 | 3/5/2019 11:14:01 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping on levels 1 and 2 complete, levels 1 and 2 approved for cover.
|
FIR18-00828
| INSP-Sprinkler Rough-in/Hydro | 3/4/2019 | 3/5/2019 | 3/5/2019 11:12:38 AM | A | PART |
|
|
Hydrostatic test for level 1 and 2 witnessed, no pressure loss observed.
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00563
| INSP-Supply line flush | 3/4/2019 | 3/5/2019 | 3/5/2019 11:12:03 AM | A | DONE |
|
|
Underground main line flush complete.
Gabe Garduno is the contact. This is inspection is for an flush and hydro. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00004
| INSP-Sprinkler Rough-in | 3/5/2019 | 3/5/2019 | 3/5/2019 9:52:59 AM | A | PART |
|
|
Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, tenting not installed at time of inspection, piping in attic spaces requiring tenting not approved for cover.
|
FIR19-00004
| INSP-Sprinkler Rough-in/Hydro | 3/4/2019 | 3/5/2019 | 3/5/2019 9:51:53 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Please call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-04471
| FIRE-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 9:28:40 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
|
BLD18-02512
| FIRE-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 9:22:39 AM | P | PASS |
|
|
Final life fire safety inspection for area of work complete.
Pete Phone #: ###-####
|
BLD17-03191
| FIRE-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 9:22:04 AM | P | PASS |
|
|
Final life fire safety inspection for area of work complete.
Pete Phone #: ###-####
|
BLD17-02577
| FIRE-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 9:21:44 AM | P | PASS |
|
|
Final life fire safety inspection for area of work complete.
Pete Phone #: ###-####
|
FIR18-00825
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 9:20:12 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00214
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 9:19:27 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00213
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 9:18:48 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00740
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 12:00:00 AM | A | FAIL |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah.
Numerous strobes at wrong height.One Visible coverage is inadequate at speaker SP1:30 in Kitchen. 15cd strobe PS:11:4:5 at vending brown bag needs to be removed. Adjust 11:4:1 to compensate. Its blocked by Refers. Strobes too low and/or blocked by shelves are 10:2:1, 10:2:210:1:4 and 20:2:4. All other equipment tested ok. Audible and visible needs to be retested.
|
FIR19-00160
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 12:00:00 AM | A | PASS |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|