FIR18-00804
| INSP-Sprinkler Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 4:57:47 PM | P | PASS |
|
|
Rough to cover inspection for wing C complete. All rough in inspection for this project complete.
|
FIR18-00804
| INSP-Final Inspection | 3/29/2019 | 4/1/2019 | 4/1/2019 4:55:41 PM | P | PART |
|
|
Final trip test for wing C complete at 50 seconds. Final inspection for wing C complete, auto purge devices need to be relocated out of the attic space, temperature for auto purges per installation requirements specifies that purge unit needs to be in temperature controlled environment between -4 degrees farenheit to 122 degrees farenheit, the attic space has the ability to exceed these limits. FIR permit for fire sprinkler will not be finaled until address related fire alarm and AES permits are inspected and finaled.
Richard Clark is the contact. This final inspection is for wing C. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00848
| FIRE-Final Inspection | 3/29/2019 | 4/1/2019 | 4/1/2019 2:33:48 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher has a current inspection tag and will be placed in discussed location. Final life fire safety inspection for area of work comlpete.
Ron Phone #: ###-####
|
BLD18-02909
| FIRE-Final Inspection | 4/1/2019 | 4/1/2019 | 4/1/2019 2:03:16 PM | P | PASS |
|
|
Previously noted items have been corrected, no fire sprinkler modifications, fire alarm inspection is complete, fire extinguisher is placed and will be tagged with a current inspection tag. Final life fire safety inspection for area of work complete.
Jane Phone #: ###-####
|
FIR18-00804
| INSP-Sprinkler Rough-in/Hydro | 4/1/2019 | 4/1/2019 | 4/1/2019 1:53:25 PM | P | DONE |
|
|
24 hour air test complete per conversation with Troy Cobbley.
|
FIR18-00640
| INSP-Sprinkler Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 1:41:22 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping in paint-booth itself is complete, overhead filters can be placed, no use of the paint booth is authorized until final inspections are complete.
Jeff Chaney is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00510
| INSP-Sprinkler Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 11:25:38 AM | P | FAIL |
|
|
Tenting not installed correctly, tenting needs to be over the entire piping to include areas where trusses are crossed. Piping in attic space must be clear between sheetrock and piping, no insulation between sheetrock and piping, areas throughout floor have spots where insulation is installed between piping and sheetrock. No combustible pockets in attic space per NFPA 13, all areas in attic space to be filled with non-combustible insulation as discussed, cover is not approved for remaining units, contact on-site foreman for added detail on proper tenting installation.
still have gaps
Fifth floor tenting inspection. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00177
| INSP-Final Inspection | 3/29/2019 | 4/1/2019 | 4/1/2019 11:23:39 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Cole Phone #: ###-####
|
FIR18-00565
| INSP-Sprinkler Rough-in/Hydro | 3/29/2019 | 4/1/2019 | 4/1/2019 11:22:27 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed, hydrostatic testing for this building is complete.
overhead // Jonathan Phone #: ###-####
|
FIR18-00527
| INSP-Sprinkler Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 10:38:50 AM | A | PASS |
|
|
Insulation inspection for fire sprinkler piping heat trace complete, approved for cover.
|
FIR18-00528
| INSP-Sprinkler Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 10:38:09 AM | A | PASS |
|
|
Insulation inspection for fire sprinkler piping heat trace complete, approved for cover.
|
FIR18-00529
| INSP-Sprinkler Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 10:37:25 AM | A | PASS |
|
|
Insulation inspection for fire sprinkler piping heat trace complete, approved for cover.
|
FIR18-00527
| INSP-Conference | 4/1/2019 | 4/1/2019 | 4/1/2019 10:35:48 AM | P | CANC |
|
|
Inspection is for a rough in for heat trace insulation cover, not a conference, this request is cancelled.
Phone #: 2085733237 >> Inspection requested via mobile web by Scott Wilson
|
FIR18-00528
| INSP-Conference | 4/1/2019 | 4/1/2019 | 4/1/2019 10:35:16 AM | P | CANC |
|
|
Inspection is for a rough in for heat trace insulation cover, not a conference, this request is cancelled.
Phone #: 2085733237 >> Inspection requested via mobile web by Scott Wilson
|
FIR18-00529
| INSP-Conference | 4/1/2019 | 4/1/2019 | 4/1/2019 10:34:45 AM | P | CANC |
|
|
Inspection is for a rough in for heat trace insulation cover, not a conference, this request is cancelled.
Phone #: 2085733237 >> Inspection requested via mobile web by Scott wilson
|
BLD19-00582
| FIRE-Final Inspection | 3/29/2019 | 4/1/2019 | 4/1/2019 8:38:32 AM | A | PASS |
|
|
Fire sprinkler modifications completye (FIR19-00177), no fire alarm modifications, fire extinguishers are placed with current inspection tags, emergency lighting has been repaired since previous comments. Final life fire safety inspection complete.
830 // tina Phone #: ###-####
|
BLD17-04626
| FIRE-Final Inspection | 3/29/2019 | 4/1/2019 | 4/1/2019 7:47:56 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire al;arm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, fire alarms must be monitored after occupancy.
fire, Life ; Safety Phone #: ###-#### Inspection requested via web by J.C. Murray
|
FIR18-00636
| INSP-Final Inspection | 3/29/2019 | 4/1/2019 | 4/1/2019 7:46:26 AM | A | PEND |
|
|
Previousl;y noted items have been corrected, final fire sprinkler inspection complete.
Gerardo Arce is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|