Inspections for the day of: Friday, April 12, 2019.
Number of inspections: 36
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00942 INSP-Final Inspection4/11/20194/12/20194/12/2019 3:23:29 PMPCANC
Cancelled per conversation with point of contact, flow switch bell not hooked up, will be rescheduled for a later date.

Call James before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00862 INSP-Final Inspection4/12/20194/12/20194/12/2019 3:22:23 PMPPASS
Previously noted items have been corrected, final fire sprinkler inspection complete.

Please call Tanner 30 minutes prior at ###-#### Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00300 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:18:01 PMPFAIL
Last inspection performed was on 1NOV2018 which resulted in a fail, no follow inspection has been requested for defecincies noted.

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR18-00302 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:15:49 PMPCANC
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Clarence Phone #: ###-####
FIR18-00301 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:15:28 PMPFAIL
Last inspection performed was on 1NOV2018 which resulted in a fail, no follow inspection has been requested for defecincies noted.

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR18-00180 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:13:12 PMPCANC
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR18-00001 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:12:51 PMPCANC
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Clarence Phone #: ###-####
FIR16-00807 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:12:26 PMPCANC
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Clarence Phone #: ###-####
FIR16-00808 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:12:02 PMPCANC
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Clarence Phone #: ###-####
FIR16-00804 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:11:39 PMPCANC
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Clarence Phone #: ###-####
FIR16-00703 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:11:06 PMPCANC
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Clarence Phone #: ###-####
FIR16-00553 INSP-Final Inspection4/12/20194/12/20194/12/2019 2:10:43 PMPCANC
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Clarence Phone #: ###-####
FIR18-00640 INSP-Sprinkler Rough-in4/12/20194/12/20194/12/2019 2:07:58 PMPPART
Previously noted items have been corrected, rough in inspection for scope of work sudstantially complete, a follow up inspection will be required when existing paint booth is removed and fire sprinklers are provided.
FIR18-00640 INSP-Sprinkler Rough-in/Hydro4/11/20194/12/20194/12/2019 2:06:04 PMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Jim Baker is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00510 INSP-Sprinkler Rough-in4/12/20194/12/20194/12/2019 1:33:58 PMPPART
Insualtion that was removed in suites 507 and 509 has been replaced, overhead fire sprinkler piping in rooms suites 507 and 509 approved for cover.

5th floor tenting inspection. Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-00907 FIRE-Final Inspection4/12/20194/12/20194/12/2019 1:24:27 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Steve-please call to meet Phone #: ###-####
BLD19-01103 FIRE-Final Inspection4/11/20194/12/20194/12/2019 1:23:14 PMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Steve-please call to meet Phone #: ###-####
BLD15-04071 FIRE-Final Inspection4/11/20194/12/20194/12/2019 1:20:45 PMACANC
Final inspection for life fire safety associated with this permit completed on 7JAN2016, this request is cancelled.

Steve--call to meet Phone #: ###-####
FIR18-00632 INSP-Final Inspection4/11/20194/12/20194/12/2019 12:40:06 PMAFAIL
Hydrostatic test for overhead fire sprinkler needs to be completed per section 11.2 of NFPA 13D 2016 edition, no hydro request has been made as of these notes.

Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00844 INSP-Sprinkler Rough-in/Hydro4/11/20194/12/20194/12/2019 11:03:53 AMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Gerardo Arce is the contact. He wants a hydro only inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00812 INSP-Sprinkler Rough-in/Hydro4/11/20194/12/20194/12/2019 11:02:23 AMADONE
Hydrostatic test for underground supply witnessed, no pressure loss observed.

Gerardo Arce is the contact. He wants this to be a hydro only inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00601 INSP-Sprinkler Rough-in/Hydro4/11/20194/12/20194/12/2019 11:01:43 AMADONE
Hydrostatic test for underground supply witnessed, no pressure loss observed.

Gerardo Arce is the contact. He wants this to be a hydro only inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00703 INSP-Final Inspection4/11/20194/12/20194/12/2019 11:00:38 AMAPASS
Final fire sprinkler inspection complete, overhead system is on dedicated fire line, no irrigation shut down on flow switch activation required.

Jeremy Phone #: ###-####
FIR18-00357 INSP-Final Inspection4/11/20194/12/20194/12/2019 10:59:48 AMAPASS
Final inspection for underground supply complete.

JEremy Phone #: ###-####
FIR18-00703 INSP-Sprinkler Rough-in/Hydro4/12/20194/12/20194/12/2019 10:58:51 AMADONE
Hydrostatic test for undergorund supply witnessed, no pressure loss observed.
FIR18-00357 INSP-Sprinkler Rough-in/Hydro4/12/20194/12/20194/12/2019 10:57:43 AMADONE
Hydrostatic test for undergorund supply witnessed, no pressure loss observed.
FIR18-00357 INSP-Supply line flush4/11/20194/12/20194/12/2019 10:56:15 AMADONE
Underground main line flush complete.

JEremy Phone #: ###-####
FIR17-00502 INSP-Final Inspection4/12/20194/12/20194/12/2019 9:39:13 AMPPASS
Underground supply permit finaled.

Clarence Phone #: ###-####
FIR19-00197 INSP-Conference4/11/20194/12/20194/12/2019 8:17:59 AMADONE
Fire conference complete, heat trace is installed with pipe insulation, cover is approved.

Phone #: 2085733237 >> Inspection requested via mobile web by Scott
FIR19-00196 INSP-Conference4/11/20194/12/20194/12/2019 8:17:38 AMADONE
Fire conference complete, heat trace is installed with pipe insulation, cover is approved.

Phone #: 2085733237 >> Inspection requested via mobile web by Scott
FIR19-00195 INSP-Conference4/11/20194/12/20194/12/2019 8:17:16 AMADONE
Fire conference complete, heat trace is installed with pipe insulation, cover is approved.

Phone #: 2085733237 >> Inspection requested via mobile web by Scott
FIR19-00194 INSP-Conference4/11/20194/12/20194/12/2019 8:16:47 AMADONE
Fire conference complete, heat trace is installed with pipe insulation, cover is approved.

Phone #: 2085733237 >> Inspection requested via mobile web by Scott
FIR19-00193 INSP-Conference4/11/20194/12/20194/12/2019 8:15:47 AMADONE
Fire conference complete, heat trace is installed with pipe insulation, cover is approved.

Phone #: 2085733237 >> Inspection requested via mobile web by Scott Wilson
FIR19-00238 INSP-Final Inspection4/12/20194/12/20194/12/2019 12:00:00 AMPCANC
Rand Phone #: ###-####
FIR18-00640 INSP-Sprinkler Rough-in4/11/20194/12/20194/11/2019 4:23:58 PMACANC
Jim Baker is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR18-00942 INSP-Final Inspection4/11/20194/12/20194/11/2019 2:09:12 PMACANC
Call James when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello