FIR18-00510
| INSP-Sprinkler Rough-in | 4/15/2019 | 4/15/2019 | 4/15/2019 4:23:54 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above soffits/lowered ceilings on level 4 suites off of west corridor complete, suites inspected approved for cover.
4th floor 1st 5 units. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00180
| INSP-Sprinkler Rough-in | 4/12/2019 | 4/15/2019 | 4/15/2019 3:28:10 PM | P | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, piping in attic spaces to have tenting inspection completed at a later date.
Dillon Phone #: ###-####
|
FIR17-00612
| INSP-Conference | 4/15/2019 | 4/15/2019 | 4/15/2019 3:26:56 PM | P | DONE |
|
|
Fire conference complete, FDC bells will need to be installed in discussed locations. FDC by Goodwill appears to supply only the wet system, FDC will need to be configured to supply both wet and dry systems without using the wet system as the FDC feed to the dry system.
Jon Beazor is the contact. This is to be a consultation about fire alarms and alarm bells. The contact requests that you give him an approximate time that you''ll be able to meet for the consultation so he can have the general contractor meet there as well. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00238
| INSP-Final Inspection | 4/12/2019 | 4/15/2019 | 4/15/2019 3:24:42 PM | P | PASS |
|
|
Final inspection for demo scope of work complete.
Rand Phone #: ###-####
|
FIR19-00212
| INSP-Sprinkler Rough-in | 4/12/2019 | 4/15/2019 | 4/15/2019 10:50:56 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids in area of work complete, notated city approved drawings areas approved for cover.
John Phone #: ###-####
|
FIR18-00942
| INSP-Final Inspection | 4/15/2019 | 4/15/2019 | 4/15/2019 10:18:35 AM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00019
| INSP-Sprinkler Rough-in | 4/14/2019 | 4/15/2019 | 4/15/2019 10:18:08 AM | P | PASS |
|
|
All tenting in place at time of inspection, overhead fire sprinkler piping approved for cover.
Remaining tenting, call James when heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD17-01583
| FIRE-Final Inspection | 4/15/2019 | 4/15/2019 | 4/15/2019 9:45:59 AM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
Andy Phone #: ###-####
|
FIR19-00214
| INSP-Sprinkler Rough-in | 4/15/2019 | 4/15/2019 | 4/15/2019 9:44:41 AM | P | PART |
|
|
Rough to cover inspection for drops supplying flex heads complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00632
| INSP-Final Inspection | 4/12/2019 | 4/15/2019 | 4/15/2019 9:15:38 AM | A | PASS |
|
|
Final fire sprinkler inspection complete, irrigation system not installed at time of this inspection but wire for solenoid disconnect on water flow has been installed from flow switch to sprinkler timer.
Colton Cox is the contact for this Hydro and he wants a Final Inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00632
| INSP-Sprinkler Rough-in/Hydro | 4/12/2019 | 4/15/2019 | 4/15/2019 9:14:01 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed at city static pressure, no pressure loss observed.
Colton Cox is the contact for this Hydro and he want a Final Inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00066
| FIRE-Final Inspection | 4/12/2019 | 4/15/2019 | 4/15/2019 8:23:14 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
Dustin Phone #: ###-####
|
FIR18-00555
| INSP-Final Inspection | 4/12/2019 | 4/15/2019 | 4/12/2019 3:29:21 PM | A | CANC |
|
|
Jim Baker is the contact for this inspection. We are trying to coordinate with Crane Alarm. We are hoping for a 12:30 time slot? Thank you for your help. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR18-00670
| INSP-Sprinkler Rough-in | 4/12/2019 | 4/15/2019 | 4/12/2019 3:17:16 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|
FIR18-00654
| INSP-Supply line flush | 4/12/2019 | 4/15/2019 | 4/12/2019 3:13:43 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|
FIR18-00670
| INSP-Sprinkler Rough-in/Hydro | 4/12/2019 | 4/15/2019 | 4/12/2019 2:44:02 PM | P | CANC |
|
|
Please call Chris Ford Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|