Inspections for the day of: Monday, April 15, 2019.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00510 INSP-Sprinkler Rough-in4/15/20194/15/20194/15/2019 4:23:54 PMPPART
Rough to cover inspection for overhead fire sprinkler piping above soffits/lowered ceilings on level 4 suites off of west corridor complete, suites inspected approved for cover.

4th floor 1st 5 units. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00180 INSP-Sprinkler Rough-in4/12/20194/15/20194/15/2019 3:28:10 PMPPART
Partial rough to cover inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, piping in attic spaces to have tenting inspection completed at a later date.

Dillon Phone #: ###-####
FIR17-00612 INSP-Conference4/15/20194/15/20194/15/2019 3:26:56 PMPDONE
Fire conference complete, FDC bells will need to be installed in discussed locations. FDC by Goodwill appears to supply only the wet system, FDC will need to be configured to supply both wet and dry systems without using the wet system as the FDC feed to the dry system.

Jon Beazor is the contact. This is to be a consultation about fire alarms and alarm bells. The contact requests that you give him an approximate time that you''ll be able to meet for the consultation so he can have the general contractor meet there as well. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00238 INSP-Final Inspection4/12/20194/15/20194/15/2019 3:24:42 PMPPASS
Final inspection for demo scope of work complete.

Rand Phone #: ###-####
FIR19-00212 INSP-Sprinkler Rough-in4/12/20194/15/20194/15/2019 10:50:56 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above hardlids in area of work complete, notated city approved drawings areas approved for cover.

John Phone #: ###-####
FIR18-00942 INSP-Final Inspection4/15/20194/15/20194/15/2019 10:18:35 AMPPASS
Final fire sprinkler inspection complete.

Call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00019 INSP-Sprinkler Rough-in4/14/20194/15/20194/15/2019 10:18:08 AMPPASS
All tenting in place at time of inspection, overhead fire sprinkler piping approved for cover.

Remaining tenting, call James when heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD17-01583 FIRE-Final Inspection4/15/20194/15/20194/15/2019 9:45:59 AMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.

Andy Phone #: ###-####
FIR19-00214 INSP-Sprinkler Rough-in4/15/20194/15/20194/15/2019 9:44:41 AMPPART
Rough to cover inspection for drops supplying flex heads complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00632 INSP-Final Inspection4/12/20194/15/20194/15/2019 9:15:38 AMAPASS
Final fire sprinkler inspection complete, irrigation system not installed at time of this inspection but wire for solenoid disconnect on water flow has been installed from flow switch to sprinkler timer.

Colton Cox is the contact for this Hydro and he wants a Final Inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00632 INSP-Sprinkler Rough-in/Hydro4/12/20194/15/20194/15/2019 9:14:01 AMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed at city static pressure, no pressure loss observed.

Colton Cox is the contact for this Hydro and he want a Final Inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-00066 FIRE-Final Inspection4/12/20194/15/20194/15/2019 8:23:14 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.

Dustin Phone #: ###-####
FIR18-00555 INSP-Final Inspection4/12/20194/15/20194/12/2019 3:29:21 PMACANC
Jim Baker is the contact for this inspection. We are trying to coordinate with Crane Alarm. We are hoping for a 12:30 time slot? Thank you for your help. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR18-00670 INSP-Sprinkler Rough-in4/12/20194/15/20194/12/2019 3:17:16 PMACANC
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
FIR18-00654 INSP-Supply line flush4/12/20194/15/20194/12/2019 3:13:43 PMACANC
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
FIR18-00670 INSP-Sprinkler Rough-in/Hydro4/12/20194/15/20194/12/2019 2:44:02 PMPCANC
Please call Chris Ford Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell