NAF18-00081 INSP-Final4/17/20194/17/20194/17/2019 3:01:37 PMPDONE
Final life fire safety inspection for area of work complete.

Call for access Phone #: 2082873693 >> Inspection requested via mobile web by Chadwick
NAF19-00030 INSP-Sprinkler Rough-in/Hydro4/17/20194/17/20194/17/2019 2:42:40 PMPDONE
Inspection request was for a final life fire safety inspection, not fire sprinkler. City approved documents were provided, inspection was performed with no noted defecincies, proper inspection needs to be called in to final permit.

Call for access Phone #: 2084128338 >> Inspection requested via mobile web by Ken
NAF18-00124 INSP-Sprinkler Rough-in4/17/20194/17/20194/17/2019 2:40:18 PMPPART
Rough to cover inspection for overhead fire sprinkler piping above lowered ceilings complete, notated packet in job shack with red ink areas approved for cover, inspected rooms 201, 203, 204, 205, 206, 207 and 208.

Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
BLD19-00504 FIRE-Final Inspection4/17/20194/17/20194/17/2019 1:55:00 PMPPASS
Previously noted items have been repaired, final life fire safety inspection complete.

Please call 30 minutes ahead of time so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
FIR18-00714 INSP-Final Inspection4/16/20194/17/20194/17/2019 1:32:08 PMPPASS
As-builts have been confirmed, fire alarm inspeciton complete.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD19-00158 FIRE-Final Inspection4/17/20194/17/20194/17/2019 1:13:57 PMPCANC
Informed point of contact that the FIR permit for fire sprinkler is still in issued status, need FIR permit to be finaled before life fire safety inspection, this request is cancelled per telephone conversation with POC.

Phone #: ###-#### Inspection requested via web by Tyson Jardine
BLD17-01303 FIRE-Final Inspection4/17/20194/17/20194/17/2019 1:09:07 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher will be placed in discussed location. Final life fire safety inspection complete.

Call for access- Mike Phone #: ###-####
FIR18-00830 INSP-Sprinkler Rough-in/Hydro4/16/20194/17/20194/17/2019 12:09:43 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Jon Beazor is the contact. He wants this to be a hydro only. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
NAF19-00037 INSP-Final4/16/20194/17/20194/17/2019 11:42:27 AMAPART
Fianl inspection for hood suppression system complete. As-builts will show removal of one appliance so protection was deleted.

Call prior to going Phone #: 2086317804 >> Inspection requested via mobile web by Nate
FIR19-00210 INSP-Sprinkler Rough-in4/17/20194/17/20194/17/2019 9:56:50 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, approved for cover.
FIR19-00210 INSP-Sprinkler Rough-in/Hydro4/17/20194/17/20194/17/2019 9:54:29 AMPDONE
Hydrostatic test for overhead fire sprinkler piping associated with this system witnessed, no pressure loss observed.

Please Cordinate inspection with Troy Nelson
Thanks Phone #: ###-#### Inspection requested via web by Christophe Wilson
FIR19-00074 INSP-Final Inspection4/16/20194/17/20194/17/2019 9:53:10 AMAFAIL
Per alarm matrix on city approved drawings, paint booth is to be disabled during a general fire alarm, panit booth did not disable, panit prep room did. Provide knox box per note 12 of review comments. Fire sprinkler associated components have been tested and passed.



Confirm inspection 208.466.0613 Phone #: ###-#### Inspection requested via web by Cheyenne Zumstein
FIR18-00640 INSP-Final Inspection4/16/20194/17/20194/17/2019 9:52:55 AMAPART
Fire sprinkler inspection substantially complete, fire alarm components have been tested and verified with central station , remaining items for fire sprinkler completion is providing fire sprinkler in area where old paint booth is going to be removed. Permit will remain in issued status until all sprinkler work is completed.

Austin Farnworth is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR12-00323 FIR-Aging Inspection4/17/20194/17/20194/17/2019 6:29:53 AM CANC