Inspections for the day of: Friday, April 17, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00516 INSP-Sprinkler Rough-in/Hydro4/17/20204/17/20204/17/2020 1:12:25 PMPPART
Rough to cover inspection for level 1 lobby restrooms, level 2 and level 3 room lowered ceilings is complete, areas inspected approved for cover.

Jon Beazer is the contact. 1st floor bathroom, 2nd and 3rd floor soffits Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-02921 FIRE-Final Inspection4/16/20204/17/20204/17/2020 1:11:21 PMPPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work is complete.

Please contact Jim 30 minutes prior to arrival Phone #: ###-#### Inspection requested via web by James Hibbard
BLD19-02706 FIRE-Final Inspection4/16/20204/17/20204/17/2020 10:25:21 AMAPASS
Previously noted item for fire alarm finalization has been completed, final life fire safety inspection for area of work is complete.

Bill ** cleared ** Phone #: ###-####
FIR19-00948 INSP-Final Inspection4/16/20204/17/20204/17/2020 10:24:30 AMPPASS
As-builts have been updated and now reflect what is installed. Final fire alarm inspection is complete.

Phone #: ###-#### Inspection requested via web by Neal Timmerman
MIS20-00116 FIR-Final4/16/20204/17/20204/17/2020 10:23:45 AMADONE
MIS inspeciton is complete. I was contacted by Brian Barber with Boise Fire in regards to a possible fire sprinkler impairment due too demolition. Building does not have fire sprinklers so there is no impairment in regards to active fire sprinklers. A stub is was provided at an earlier point but only the stub in was provided. Fire alarm modificaitons will be required for new tenant, fire alarm appliances are not to be removed unless an FIR permit is issued for fire alarm demo.

per Jim Page - possible work without permits. Active Fire Sprinkler Building Phone #: ###-####
BLD20-01053 FIRE-Final Inspection4/16/20204/17/20204/17/2020 10:20:22 AMAFAIL
Cooking appliances have been changed, added and moved under the Type 1 hood, a seperate FIR permit is required for hood fire suppression system modifications. Mount fire extinguisher as discussed and have annual inspection performed on the ABC and Class K extinguishers as discussed. Provide annual inspection on hood fire suppression system. Exit sign located in the east side of tenant space is mounted too low, exit sign must comply with 1010.1.1.1 of the 2015 IFC.

screened // ryeongmin Phone #: ###-####
FIR20-00140 INSP-Final Inspection4/16/20204/17/20204/17/2020 9:19:02 AMAFAIL
Make-up air did not function creating too much negative pressure for proper egress on exit door, required more force to open than IFC allows.

Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
BLD19-03480 FIRE-Final Inspection4/17/20204/17/20204/17/2020 9:16:25 AMACANC
Phone #: ###-#### >> Inspection requested via web by kevin debelloy Inspection cancelled from web by: kevin debelloy