FIR18-00235
| INSP-Final Inspection | 4/2/2019 | 4/3/2019 | 4/3/2019 2:51:05 PM | P | PASS |
|
|
Final AES inspection complete.
as late in pm as possible - can't have alarms go off during school // Will Phone #: ###-####
|
FIR18-00319
| INSP-Final Inspection | 4/2/2019 | 4/3/2019 | 4/3/2019 1:29:23 PM | P | PASS |
|
|
Previously noted items have been corrected, final fire sprinkler inspection complete.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-01629
| FIRE-Final Inspection | 4/2/2019 | 4/3/2019 | 4/3/2019 11:15:03 AM | A | FAIL |
|
|
Access control for north gym door did not release on general fire alarm.
Lauren Phone #: ###-####
|
BLD18-02596
| FIRE-Final Inspection | 4/1/2019 | 4/3/2019 | 4/3/2019 10:41:36 AM | A | FAIL |
|
|
Fire alarm inspection did not pass, need access control release on mag locks per IFC Chapter 10 during general fire alarm. Main double doors to space are rated doors with mag drop release, doors do shut correctly due to contact with carpet, doors will need to shut all the way and latch to be code compliant.
Doug Phone #: ###-####
|
FIR18-00928
| INSP-Final Inspection | 4/3/2019 | 4/3/2019 | 4/3/2019 10:36:26 AM | A | FAIL |
|
|
Provide relay for access control door release, all other items have been inspected.
|
FIR18-00928
| INSP-Conference | 4/3/2019 | 4/3/2019 | 4/3/2019 10:35:28 AM | A | CANC |
|
|
|
BLD18-04110
| FIRE-Final Inspection | 4/2/2019 | 4/3/2019 | 4/3/2019 9:28:32 AM | A | CANC |
|
|
Cancelled per conversation with point of contact, do not have FIR permit in system for fire alarm work/demo as of this note entry.
call to meet // Tyler Phone #: ###-####
|
BLD19-00128
| FIRE-Final Inspection | 4/2/2019 | 4/3/2019 | 4/3/2019 7:52:32 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Tom Phone #: ###-####
|
FIR19-00044
| INSP-Final Inspection | 4/1/2019 | 4/3/2019 | 4/3/2019 7:51:41 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00100
| INSP-Final Inspection | 4/1/2019 | 4/3/2019 | 4/3/2019 7:51:02 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
We would like to set the alarm off at 7:00 am. Phone #: ###-#### Inspection requested via web by Sam Ball
|