Inspections for the day of: Thursday, April 4, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00139 INSP-Final Inspection4/4/20194/4/20194/4/2019 4:13:21 PMPPASS
Final fire sprinkler inspection for area of work complete.

Kyle Koepnick is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00146 INSP-Final Inspection4/4/20194/4/20194/4/2019 4:07:29 PMPPART
Final fire alarm inspection for levels 4, 5 and 6 complete. Remaining work to be completed at a later date.
FIR19-00146 INSP-Alarm Testing4/2/20194/4/20194/4/2019 4:06:45 PMPDONE
Fire alarm testing complete.

Josh-partial on floors 4, 5 & 6 Phone #: ###-####
BLD18-04110 FIRE-Final Inspection4/4/20194/4/20194/4/2019 2:16:10 PMPPART
Previously noted items have been corrected. FIR permit has been received for fire alarm demo, TCO is authorized for 30 days for life safety contingent on the work on the FIR permit for the fire alarm is completed, inspected and finaled.

Call ahead // Clint Phone #: ###-####
FIR18-00862 INSP-Sprinkler Rough-in4/1/20194/4/20194/4/2019 1:41:31 PMPFAIL
Both dry system and small wet system lost pressure, 6 PSI on dry, 15 PSI on small wet system. Larger wet system had no pressure loss observed.

Contact Tanner Loomis - ###-#### 30 Min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00692 INSP-Sprinkler Rough-in4/1/20194/4/20194/4/2019 1:40:29 PMPDONE
Request was for undergorund hydro, underground hydro witnessed, no pressure loss observed.

Contact Tanner Loomis 3###-#### 30 Min Prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD17-01829 FIRE-Final Inspection4/4/20194/4/20194/4/2019 1:21:37 PMPFAIL
fire extinguisher needs annual inspection performed. Service exit/emergency light on level 2 landing.

Jay Phone #: ###-####
FIR19-00085 INSP-Sprinkler Rough-in4/3/20194/4/20194/4/2019 1:07:05 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Contact ken Orahood ###-#### 30 Min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00633 INSP-Sprinkler Rough-in/Hydro4/3/20194/4/20194/4/2019 9:54:22 AMACANC
Inspection request cancelled per conversarion with point of contact, baffles to prevent cold soldering on sidewalls protecting exterior projections.

Kenny Caldwell is the contact. He requests this to be a partial rough/hydro for the 4th floor. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00510 INSP-Sprinkler Rough-in4/4/20194/4/20194/4/2019 8:50:19 AMAPART
Overhead fire sprinkler piping inspection above hardlids/soffits in all rooms to include north side of fire door on level 2 complete, hardlids/soffits in rooms on level 3 complete, areas inspected approved for cover.
FIR18-00510 INSP-Sprinkler Rough-in4/3/20194/4/20194/4/2019 8:45:56 AMAFAIL
Numerous pockets throughout level 5 corridor and remaining rooms that do not meet the requirements of filling attic space with non-combustible insulation.

5th floor tenting ;2nd floor rough in. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00123 INSP-Final Inspection4/3/20194/4/20194/4/2019 6:34:12 AMAPASS
Final inspection for hood suppression system inspection.

6am after hours inspection