FIR20-00122
| INSP-Sprinkler Rough-in | 4/6/2020 | 4/7/2020 | 4/7/2020 1:31:43 PM | A | PASS |
|
|
Tenting has been corrected, all tenting in place at time of inspection, cover is approved. Cover sticker has been placed.
tenting re-inspection Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00108
| INSP-Sprinkler Rough-in | 4/6/2020 | 4/7/2020 | 4/7/2020 1:31:24 PM | A | PASS |
|
|
Tenting has been corrected, all tenting in place at time of inspection, cover is approved. Cover sticker has been placed.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
BLD20-01038
| FIRE-Final Inspection | 4/7/2020 | 4/7/2020 | 4/7/2020 1:14:39 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is placed and will be inspected as dicussed. Final life fire safety inspection is complete, signature card not available at time of inspection.
screened please call to meet // Delia Phone #: ###-####
|
FIR20-00186
| INSP-Sprinkler Rough-in | 4/7/2020 | 4/7/2020 | 4/7/2020 12:24:34 PM | P | PASS |
|
|
Previously noted item has been corrected, rough to cover inspection for overhead fire sprinkler piping in scope of work is complete, scope of work approved for cover.
Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR20-00127
| INSP-Sprinkler Rough-in | 4/6/2020 | 4/7/2020 | 4/7/2020 10:12:00 AM | A | PART |
|
|
Previously noted item has been corrected, rough in inspection is complete. Tenting not installed at time of inspection, cover is not approved.
piping correction made Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
BLD20-00021
| FIRE-Final Inspection | 4/6/2020 | 4/7/2020 | 4/7/2020 9:25:53 AM | A | PASS |
|
|
No fire sprinklers, smoke detectors/heat detectors are stand alone, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work is complete, signature provided on permit sign off card.
Please contact Sid ###-#### Phone #: ###-#### Inspection requested via web by Carissa Mattison
|
BLD19-00248
| FIRE-Final Inspection | 4/7/2020 | 4/7/2020 | 4/7/2020 8:38:37 AM | A | PART |
|
|
Fire sprinkler riser monitoring has been tested and complete, storage of furntiure in building is authorized. After this entry fire sprinklers are to remain active and monitored (Allowed to be put on test during normal working hours, fire sprinkler monitoring must be taken off of test at the end of the business day, if monitoring is not active then furntiure storage will be revoked).
|
FIR20-00236
| INSP-Final Inspection | 4/6/2020 | 4/7/2020 | 4/7/2020 8:34:46 AM | A | PASS |
|
|
Final inspection for AES communicator is complete.
We would like this inspection at 8:00 am if possible. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00489
| INSP-Final Inspection | 4/6/2020 | 4/7/2020 | 4/7/2020 8:33:30 AM | A | PART |
|
|
Partial final inspection is complete, fire sprinkler riser monitoring is complete, intial walkthrough is complete, permit will remian in issued status until BLD permit gets close to final life fire safety inspection. Sprinkler riser monitoring is to remain active. Furniture storage inside the building is authorized provided sprinklers remain active and monitored.
Todd Ketterling is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00139
| INSP-Alarm Testing | 4/6/2020 | 4/7/2020 | 4/7/2020 8:31:10 AM | A | PART |
|
|
Fire alarm testing is complete, fire sprinkler riser monitoring is tested/active.
clear // buck tom Phone #: ###-####
|