Inspections for the day of: Friday, May 11, 2018.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02377 FIRE-Conference5/10/20185/11/20185/11/2018 2:00:33 PMPDONE
Fire conference about required signage complete.

Todd Phone #: ###-####
FIR18-00362 INSP-Final Inspection5/10/20185/11/20185/11/2018 12:46:35 PMPPASS
Final fire sprinkler inspection for area of work complete.
BLD17-00091 FIRE-Final Inspection5/9/20185/11/20185/11/2018 12:11:29 PMAFAIL
Level 1 doors on both stairwells need to have grouting installed for stairwell rating. South emergency exit for parking garage is interfaced with the access control, door cannot be access controled due to the door being the second emergency exit for the parking garage. Emergency exit signs need to be installed in discussed locations. Provide building fire and evacuation plans in each apartment unit per note number 11 of building permit fire code review noted.



Coordinated with Jim for 10am // Evan Phone #: ###-####
FIR18-00256 INSP-Final Inspection5/9/20185/11/20185/11/2018 11:04:39 AMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR17-00585 INSP-Alarm Testing5/11/20185/11/20185/11/2018 10:29:46 AMADONE
Fire alarm testing for elevator recall and shunt complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00187 INSP-Sprinkler Rough-in5/9/20185/11/20185/11/2018 8:43:00 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover.

Rough in on hard lids Phone #: ###-#### Inspection requested via web by Matthew Lewis