Inspections for the day of: Monday, May 13, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00270 INSP-Sprinkler Rough-in5/10/20195/13/20195/13/2019 3:49:15 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, approved for cover.

Tom Phone #: ###-####
FIR18-00610 INSP-Sprinkler Rough-in5/13/20195/13/20195/13/2019 3:34:10 PMPPART
Rough to cover inspection for overhead fire sprinkler piping in common corridors and elevator lobby on levels 3 and 4 complete, approved for cover.

Mike Phone #: ###-####
BLD19-00961 FIRE-Final Inspection5/13/20195/13/20195/13/2019 3:09:17 PMPPASS
Final life fire safety inspection for area of work complete.

Mark Phone #: ###-####
BLD18-00944 FIRE-Final Inspection5/10/20195/13/20195/13/2019 2:45:39 PMPCANC
GC noticed that the FIR permit for sprinklers was still in issued status, GC will coordinate with the sprinkler contractor to get both inspections completed, this request is cancelled per conversation with point of contact.

Kirt Phone #: ###-####
FIR19-00111 INSP-Sprinkler Rough-in5/9/20195/13/20195/13/2019 2:40:10 PMPPART
Rough to cover inspection for levels 1 and 2 complete, levels 1 and 2 approved for cover. Level 3 rough in inspection complete, tenting/insulation to be installed at a later date, an inspection for tenting is required before cover can be approved, level 3 cover is not approved as of this inspection.

Contact Noemi Carrero ###-#### 30 Min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00323 INSP-Final Inspection5/13/20195/13/20195/13/2019 1:50:31 PMPPASS
Final fire alarm inspection complete.

Phone #: ###-#### Inspection requested via web by Matt Casey
FIR18-00565 INSP-Final Inspection5/10/20195/13/20195/13/2019 1:49:54 PMPPASS
Final fire sprinkler inspection complete.

Johnathon Phone #: ###-####
BLD17-03885 FIRE-Conference5/13/20195/13/20195/13/2019 11:52:14 AMPDONE
Wall mounted post indicator is to high above finish grade, maximum allowable elevation above finish floor needs to be 48 inches or less per conversation with Ron Johnson with Boise Fire. Manhole cover will be placed over sewer clean-out pit prior to final occupancy.

FIR18-00501 INSP-Final Inspection5/10/20195/13/20195/13/2019 11:50:07 AMPFAIL
Provide dry sidewall under combustible over-hang above west exit. Replace upright fire sprinkler head that was painted in the south room behind habitat exhibit. Replace exposed CPVC to steel pipe. Change upright head in restroom to the required pendant head. Replace pendant head that is in FACP room with an upright head as discussed.

George Jess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD17-03885 FIRE-Final Inspection5/13/20195/13/20195/13/2019 11:46:57 AMPCANC
Request was for a conference, this request is cancelled.

Please coordinate with fire suppression and alarm. building D7 Phone #: ###-#### Inspection requested via web by Brandon Reynolds
FIR19-00257 INSP-Final Inspection5/8/20195/13/20195/13/2019 11:45:43 AMPPASS
Final fire alarm inspection complete.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD19-01357 FIRE-Final Inspection5/10/20195/13/20195/13/2019 9:47:30 AMAPASS
Final life fire safety inspection for permit area complete.

Sharm Phone #: ###-####-call 30 minutes prior
BLD18-04526 FIRE-Final Inspection5/10/20195/13/20195/13/2019 9:23:43 AMAFAIL
Provide emergency lighting for exit discharge above northeast exterior exit. Install single action door hardware on restroom that has round type door hardware. Provide maximum occupancy placard.

Rick Phone #: ###-####
FIR19-00077 INSP-Sprinkler Rough-in5/10/20195/13/20195/13/2019 9:03:29 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with red ink areas approved for cover.

Tom Phone #: ###-####
FIR19-00263 INSP-Sprinkler Rough-in5/10/20195/13/20195/13/2019 12:00:00 AMPPASS
OK to cover area "A" only, notes made to plan mod #1 plan on site.***MAS**
Colton Cox is the contact. This rough-in is for section A of the building. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus