Inspections for the day of: Thursday, May 14, 2020.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00091 INSP-Sprinkler Rough-in5/14/20205/14/20205/14/2020 4:57:34 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.

Contact Ken Orahood ###-#### 30 min prior to UG RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR20-00174 INSP-Sprinkler Rough-in5/14/20205/14/20205/14/2020 1:40:00 PMPPASS
Rough to cover inspection for area of work is complete, approved for cover.

FIR20-00174 INSP-Final Inspection5/13/20205/14/20205/14/2020 1:39:33 PMPCANC
Project not ready for final inspection, request changed to a rough in inspection, this request is cancelled.

Please call Chris Ford Phone #: ###-#### Inspection requested via web by Jessia McLain
FIR20-00322 INSP-Final Inspection5/14/20205/14/20205/14/2020 1:38:28 PMPPASS
Final fire sprinkler inspection for area of work is complete.

screened // Adam Phone #: ###-####
FIR20-00322 INSP-Sprinkler Rough-in5/14/20205/14/20205/14/2020 1:33:57 PMPPASS
Rough to cover inspection for area of work is complete, approved for cover.

screened // Adam Phone #: ###-####
FIR20-00318 INSP-Sprinkler Rough-in5/13/20205/14/20205/14/2020 1:33:30 PMAPART
Partial rough to cover inspection for underground supply from road box to change of direction complete, area inspected approved for cover, remaining underground to be inspected at a later date.

partial rough in on underground to cover.
Please call Chris Ford Phone #: ###-#### Inspection requested via web by Jessia McLain
FIR20-00248 INSP-Sprinkler Rough-in5/14/20205/14/20205/14/2020 10:57:00 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area A complete, area A approved for cover.
FIR20-00248 INSP-Sprinkler Rough-in/Hydro5/11/20205/14/20205/14/2020 10:56:26 AMADONE
Hydrostatic test for overhead fire sprinkler piping in area A witnessed, no pressure loss observed at riser provided gauge.

Call Steve Johnson cell 208.598.5155 for escort, meet in B26 Lobby. Phone #: ###-#### Inspection requested via web by Steve Johnson
BLD20-01387 FIRE-Final Inspection5/13/20205/14/20205/14/2020 8:34:40 AMAPASS
No fire sprinkler, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work is complete, signature provided on permit sign off card.

Curt Phone #: ###-####
FIR19-00261 INSP-Final Inspection5/14/20205/14/20205/14/2020 8:25:49 AMPPASS
Final fire sprinkler inspection is complete.

Screened- Ron Phone #: ###-####
FIR19-00261 INSP-Sprinkler Rough-in/Hydro5/14/20205/14/20205/14/2020 8:25:26 AMADONE
Hydrostatic test has been witnessed at city pressure, no pressure loss observed at riser provided gauge.
FIR19-00261 INSP-Sprinkler Rough-in/Hydro5/14/20205/14/20205/14/2020 8:24:37 AMAPASS
Freeze protection has been corrected by adding a pass through vent, all piping has been approved for cover.
BLD20-00253 FIRE-Final Inspection5/13/20205/14/20205/14/2020 8:21:53 AMACANC
Called point of contact listed on 13MAY2020 to inform that this project does not require a life fire safety signature as listed in permit details. No return call was received as of this entry, this request is cancelled.

Insulation Inspection on Pool House Phone #: ###-#### Inspection requested via web by Tammy Schacher
BLD19-03779 FIRE-Final Inspection5/13/20205/14/20205/14/2020 8:19:30 AMAPASS
Previously noted items have been corrected, curtian that was causing fire sprinkler blockage has been removed, no fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection is complete, signatures provided on permit sign off card.

Paul *screened* Phone #: ###-####