FIR20-00091
| INSP-Sprinkler Rough-in | 5/14/2020 | 5/14/2020 | 5/14/2020 4:57:34 PM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
Contact Ken Orahood ###-#### 30 min prior to UG RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR20-00174
| INSP-Sprinkler Rough-in | 5/14/2020 | 5/14/2020 | 5/14/2020 1:40:00 PM | P | PASS |
|
|
Rough to cover inspection for area of work is complete, approved for cover.
|
FIR20-00174
| INSP-Final Inspection | 5/13/2020 | 5/14/2020 | 5/14/2020 1:39:33 PM | P | CANC |
|
|
Project not ready for final inspection, request changed to a rough in inspection, this request is cancelled.
Please call Chris Ford Phone #: ###-#### Inspection requested via web by Jessia McLain
|
FIR20-00322
| INSP-Final Inspection | 5/14/2020 | 5/14/2020 | 5/14/2020 1:38:28 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work is complete.
screened // Adam Phone #: ###-####
|
FIR20-00322
| INSP-Sprinkler Rough-in | 5/14/2020 | 5/14/2020 | 5/14/2020 1:33:57 PM | P | PASS |
|
|
Rough to cover inspection for area of work is complete, approved for cover.
screened // Adam Phone #: ###-####
|
FIR20-00318
| INSP-Sprinkler Rough-in | 5/13/2020 | 5/14/2020 | 5/14/2020 1:33:30 PM | A | PART |
|
|
Partial rough to cover inspection for underground supply from road box to change of direction complete, area inspected approved for cover, remaining underground to be inspected at a later date.
partial rough in on underground to cover. Please call Chris Ford Phone #: ###-#### Inspection requested via web by Jessia McLain
|
FIR20-00248
| INSP-Sprinkler Rough-in | 5/14/2020 | 5/14/2020 | 5/14/2020 10:57:00 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area A complete, area A approved for cover.
|
FIR20-00248
| INSP-Sprinkler Rough-in/Hydro | 5/11/2020 | 5/14/2020 | 5/14/2020 10:56:26 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping in area A witnessed, no pressure loss observed at riser provided gauge.
Call Steve Johnson cell 208.598.5155 for escort, meet in B26 Lobby. Phone #: ###-#### Inspection requested via web by Steve Johnson
|
BLD20-01387
| FIRE-Final Inspection | 5/13/2020 | 5/14/2020 | 5/14/2020 8:34:40 AM | A | PASS |
|
|
No fire sprinkler, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work is complete, signature provided on permit sign off card.
Curt Phone #: ###-####
|
FIR19-00261
| INSP-Final Inspection | 5/14/2020 | 5/14/2020 | 5/14/2020 8:25:49 AM | P | PASS |
|
|
Final fire sprinkler inspection is complete.
Screened- Ron Phone #: ###-####
|
FIR19-00261
| INSP-Sprinkler Rough-in/Hydro | 5/14/2020 | 5/14/2020 | 5/14/2020 8:25:26 AM | A | DONE |
|
|
Hydrostatic test has been witnessed at city pressure, no pressure loss observed at riser provided gauge.
|
FIR19-00261
| INSP-Sprinkler Rough-in/Hydro | 5/14/2020 | 5/14/2020 | 5/14/2020 8:24:37 AM | A | PASS |
|
|
Freeze protection has been corrected by adding a pass through vent, all piping has been approved for cover.
|
BLD20-00253
| FIRE-Final Inspection | 5/13/2020 | 5/14/2020 | 5/14/2020 8:21:53 AM | A | CANC |
|
|
Called point of contact listed on 13MAY2020 to inform that this project does not require a life fire safety signature as listed in permit details. No return call was received as of this entry, this request is cancelled.
Insulation Inspection on Pool House Phone #: ###-#### Inspection requested via web by Tammy Schacher
|
BLD19-03779
| FIRE-Final Inspection | 5/13/2020 | 5/14/2020 | 5/14/2020 8:19:30 AM | A | PASS |
|
|
Previously noted items have been corrected, curtian that was causing fire sprinkler blockage has been removed, no fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection is complete, signatures provided on permit sign off card.
Paul *screened* Phone #: ###-####
|