BLD19-00677
| FIRE-Final Inspection | 5/17/2019 | 5/17/2019 | 5/17/2019 2:36:37 PM | P | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Door handle between break room area to corridor to be changed before final BLD inspection, lock in the path of travel to be removed/changed. Final life fire safety inspection complete.
Call ahead // Jon Phone #: ###-####
|
FIR19-00159
| INSP-Final Inspection | 5/17/2019 | 5/17/2019 | 5/17/2019 2:33:15 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Please call Troy with frame.
Thank you and have a great day. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00210
| INSP-Final Inspection | 5/17/2019 | 5/17/2019 | 5/17/2019 2:32:06 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Call Troy with time frame.
Thank you and a have a great day. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
BLD19-00515
| FIRE-Final Inspection | 5/17/2019 | 5/17/2019 | 5/17/2019 2:31:41 PM | P | PASS |
|
|
Final life fire safety inspection complete.
Please call 30 mins ahead of time so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
|
FIR18-00267
| INSP-Final Inspection | 5/16/2019 | 5/17/2019 | 5/17/2019 1:17:12 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Justin Phone #: ###-####
|
FIR18-00435
| INSP-Sprinkler Rough-in/Hydro | 5/16/2019 | 5/17/2019 | 5/17/2019 12:19:30 PM | P | PASS |
|
|
Rough to cover inspection for remaining overhead fire sprinkler piping complete, all areas approved for cover. Hydrostatic test to be completed at a later date.
James Wells is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00508
| FIRE-Final Inspection | 5/16/2019 | 5/17/2019 | 5/17/2019 11:39:40 AM | A | FAIL |
|
|
Associated FIR permits for fire sprinklers needs to be finaled before life fire safety inspection can be completed, this request will need to be rescheduled.
Clint Phone #: ###-####
|
FIR19-00348
| INSP-Sprinkler Rough-in | 5/17/2019 | 5/17/2019 | 5/17/2019 11:13:13 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Lonnie Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR19-00207
| INSP-Sprinkler Rough-in | 5/17/2019 | 5/17/2019 | 5/17/2019 10:51:02 AM | A | PART |
|
|
Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, areas requiring tenting will be inspected at a later date, piping requiring tenting is not approved for cover.
|
FIR19-00207
| INSP-Sprinkler Rough-in/Hydro | 5/16/2019 | 5/17/2019 | 5/17/2019 10:49:17 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Call James before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00166
| INSP-Final Inspection | 5/17/2019 | 5/17/2019 | 5/17/2019 10:48:38 AM | A | FAIL |
|
|
Exterior access control for staiwell doors did not release on general alarm, per IFC access control doors in egress paths need to disable and unlock on general fire alarm.
|
FIR18-00166
| INSP-Final Inspection | 5/14/2019 | 5/17/2019 | 5/17/2019 10:47:03 AM | A | PART |
|
|
Final inspection for all initiating devices complete.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR19-00274
| INSP-Supply line flush | 5/17/2019 | 5/17/2019 | 5/17/2019 10:24:10 AM | P | CANC |
|
|
Contact Heath Day at ###-#### Phone #: ###-#### >> Inspection requested via web by Matt Barnard Inspection cancelled from web by: Matt Barnard
|
FIR19-00348
| INSP-Final Inspection | 5/17/2019 | 5/17/2019 | 5/17/2019 8:02:33 AM | A | CANC |
|
|
Lonnie Phone #: ###-#### >> Inspection requested via web by Nathan Stenquist Inspection cancelled from web by: Nathan Stenquist
|
FIR19-00198
| INSP-Final Inspection | 5/13/2019 | 5/17/2019 | 5/16/2019 3:45:06 PM | P | CANC |
|
|
Please call with inspection time Phone #: ###-#### >> Inspection requested via web by Heather Stier Inspection cancelled from web by: Heather Stier
|