Inspections for the day of: Tuesday, May 21, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00510 INSP-Sprinkler Rough-in5/21/20195/21/20195/21/2019 4:36:11 PMPPART
2nd floor apartments approved for cover, level 5 corridor drop down ceilings, north of the fire doors approved for cover

2nd floor apartments and 4th floor corridor Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-00281 FIRE-Final Inspection5/21/20195/21/20195/21/2019 2:35:48 PMPPART
Fire sprinkler inspection complete for scope of work, fire alarm inspection has been completed but plan is back into reviewed status due to plan mod, fire extinguishers are placed with current inspection tags. 30 day TCO authorized for life fire safety contingent on fire alarm plans being approved and finaled.

Phone #: 2083188954 >> Inspection requested via mobile web by Jim Douglas
FIR19-00181 INSP-Final Inspection5/20/20195/21/20195/21/2019 2:33:57 PMAPART
Fina fire alarm inspection for scope of work complete, awaiting plan mod approval for final sign off.

(plan mod in process)

Ron ###-####
BLD18-04006 FIRE-Final Inspection5/21/20195/21/20195/21/2019 1:26:03 PMPPASS
Previously noted items have been corrected, fire exitnguisher was mounted in discussed location at time of inspection. Slide bolts were removed at time of inspection, final life fire safety inspection for area of work complete.

Alician Phone #: ###-####
BLD18-04174 FIRE-Final Inspection5/21/20195/21/20195/21/2019 1:14:06 PMPCANC
No fire life safety signature required for permit according to permit details, this request is cancelled.

Toby Phone #: ###-####
BLD18-04173 FIRE-Final Inspection5/21/20195/21/20195/21/2019 1:13:46 PMPCANC
No fire life safety signature required for permit according to permit details, this request is cancelled.

Toby Phone #: ###-####
BLD17-04465 FIRE-Final Inspection5/20/20195/21/20195/21/2019 1:10:17 PMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire exitnguishers are placed with current inspection tags, knox box is located by fire sprinkler riser room. Final life fire safety inspection complete.

Wes Phone #: ###-####
FIR19-00091 INSP-Supply line flush5/21/20195/21/20195/21/2019 12:49:34 PMADONE
Underground main line flush complete.

Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
BLD18-03875 FIRE-Final Inspection5/20/20195/21/20195/21/2019 12:19:37 PMAFAIL
Fire sprinkler inspection failed due to a painted head and texture mud all the way up to the base of the sprinkler head. An FIR permit is required for fire alarm work, currently there is a wall mounted device mounted on the ceiling, was informed by the GC that the devices were lowered from their original location, any modifications to the fire alarm system requires a permit, including lowering devices from the original location.

Marty Phone #: ###-####
FIR19-00287 INSP-Final Inspection5/20/20195/21/20195/21/2019 12:17:33 PMAFAIL
Fire sprinkler head in changing room has paint on the seat, head will need to be replaced. Texture mud needs to be cut around the other 2 heads in changing room, heads to not have escutcheons installed due to drywall mud issue.

Adam Chitwood
To coinside with the fire life safety final. Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD18-04124 FIRE-Final Inspection5/20/20195/21/20195/21/2019 11:38:50 AMAFAIL
FIR permit for fire alarms still in issued status, reference FIR19-00089 for fire alarm notes. FIR permit for fire alarm system needs to be finaled before life fire safety can be completed.

Antonio Phone #: ###-####
FIR19-00111 INSP-Sprinkler Rough-in/Hydro5/20/20195/21/20195/21/2019 11:21:17 AMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Leroy Anderson ###-#### 30 Min Prior to Hydro Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00795 INSP-Final Inspection5/20/20195/21/20195/21/2019 8:36:59 AMAPASS
Final fire alarm inspection for scope of work complete.

Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR19-00287 INSP-Final Inspection5/20/20195/21/20195/20/2019 8:52:01 AMPCANC
Adam Chitwood
To coinside with the fire life safety final Phone #: ###-#### >> Inspection requested via web by Brodie Stenquist Inspection cancelled from web by: Brodie Stenquist