Inspections for the day of: Wednesday, May 22, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-03875 FIRE-Final Inspection5/22/20195/22/20195/22/2019 3:25:46 PMPFAIL
Fire alarm work was completed without an issued permit, fire alarm modifications will need to be permitted, inspected and finaled before life fire safety inspection can be completed.

Marty Phone #: ###-####
FIR19-00287 INSP-Final Inspection5/22/20195/22/20195/22/2019 3:24:05 PMPPASS
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.

Adam Phone #: ###-####
FIR19-00274 INSP-Sprinkler Rough-in/Hydro5/22/20195/22/20195/22/2019 1:49:29 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed with static city pressure per NFPA 13D, no pressure loss observed and no visible leakage from fire sprinkler piping.
FIR19-00274 INSP-Sprinkler Rough-in5/22/20195/22/20195/22/2019 1:45:47 PMPPASS
Pastic sheeting used for tenting, all tenting in place at time of inspection, cover is approved for overhead fire sprinkler piping, cover approval sticker placed on riser.

Contact Heath Day at ###-#### Phone #: ###-#### Inspection requested via web by Matt Barnard
FIR19-00252 INSP-Sprinkler Rough-in5/22/20195/22/20195/22/2019 1:09:03 PMPFAIL
Rough to cover inspection for overhead fire sprinkler piping in attic space where piping was removed and installed due to roof collapse complete. Insulation is shown to be installed on the bottom cords of the trusses, piping will not be protected from freezing with this application. Freeze protection will need to be provided for fire sprinkler piping in attic space or submit heat calculations from a professional engineer showing that the attic space will be maintained at a minimum of 40 degrees fahrenheit to be compliant with 2016 NFPA 13, section 8.16.4.

###-#### clarence
FIR19-00237 INSP-Sprinkler Rough-in5/21/20195/22/20195/22/2019 12:22:43 PMAPART
Rough in inspection for overhead fire sprinkler piping complete, a follow up inspection will be required after flex heads are installed the grid before all cover can be approved. Hardlids in throughout level 1 approved for cover.

Contact Tyler Loomis ###-#### 30 Min prior to RTC Insp start please, he''s requesting an mid morning /10AM inspection time if possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00237 INSP-Sprinkler Rough-in/Hydro5/21/20195/22/20195/22/2019 12:20:45 PMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Tyler Loomis ###-#### 30min prior to RTC /Hydro Insp start please. He''s requesting a 10 AM insp time if at all possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00220 INSP-Final Inspection5/20/20195/22/20195/22/2019 10:52:46 AMAPASS
Final fire sprinkler inspection for area of work complete.

Please schedule with alarm final between 8-10 AM. Adam Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR19-00245 INSP-Final Inspection5/20/20195/22/20195/22/2019 10:52:19 AMAPASS
Final fire alarm inspection for area of work complete., record of completion was a digital form, document will be emailed to Lee Meridith per conversation with on-site technician.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
BLD19-00756 FIRE-Final Inspection5/20/20195/22/20195/22/2019 10:49:51 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.

Tom Phone #: ###-####
FIR19-00282 INSP-Final Inspection5/20/20195/22/20195/22/2019 10:48:56 AMAPASS
Final fire alarm inspection for area of work complete.

Final at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-00730 FIRE-Final Inspection5/22/20195/22/20195/22/2019 10:48:26 AMAPASS
No fire sprinkler modifications, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
FIR19-00240 INSP-Final Inspection5/20/20195/22/20195/22/2019 10:46:15 AMAPASS
Final fire sprinkler inspection complete.

Final at 7:00 am Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00343 INSP-Final Inspection5/21/20195/22/20195/22/2019 10:34:34 AMAPASS
Final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Rick Groom
FIR19-00245 INSP-Sprinkler Rough-in/Hydro5/20/20195/22/20195/20/2019 2:38:08 PMACANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Monday, May 20, 2019.