FIR19-00743
| INSP-Sprinkler Rough-in | 5/27/2020 | 5/28/2020 | 5/28/2020 4:24:39 PM | P | PART |
|
|
Rough in inspection for gymnasium area is complete. Rough to cover inspection for overhead fire sprinkler piping above hardlid type ceiling in center entry is complete, approved for cover.
Contact Tanner Loomis ###-#### 30 min prior to RTC Insp start please. Area to inspect is the high area in the middle of the building and the gym. Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR20-00148
| INSP-Sprinkler Rough-in | 5/27/2020 | 5/28/2020 | 5/28/2020 2:06:12 PM | P | PASS |
|
|
Rough to cover inspection for undergorund supply complete, approved for cover.
Approval to cover on underground. Contact: Mike Martin Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
BLD20-01058
| FIRE-Final Inspection | 5/28/2020 | 5/28/2020 | 5/28/2020 2:05:42 PM | P | PASS |
|
|
No fire sprinkler modifications, fire alarm modifications were completed under FIR20-00343, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work is complete, signatures provided on permit sign off card.
call to meet there // Jeremy Phone #: ###-####
|
BLD19-01893
| FIRE-Final Inspection | 5/28/2020 | 5/28/2020 | 5/28/2020 12:07:55 PM | P | FAIL |
|
|
Fire sprinkler head in restroom is stilled masked off from painting. Escutcheons for fire sprinkler heads are still missing as noted in last fire inspection. Project has 2 FIR permits attached, one for fire sprinkler and one for fire alarm that must be inspected and completed before life fire safety inspection can be completed.
Access key pad 1208 Phone #: ###-#### Inspection requested via web by Josh Strasser
|
BLD19-02606
| FIRE-Final Inspection | 5/28/2020 | 5/28/2020 | 5/28/2020 12:05:51 PM | P | FAIL |
|
|
Ceiling tile is mising thoughout tenant space, tiles must be installed for fire sprinkler heat collection.
Key pad is on 7052 address door Code 1208 Phone #: ###-#### Inspection requested via web by Josh Strasser
|
FIR20-00185
| INSP-Alarm Testing | 5/27/2020 | 5/28/2020 | 5/28/2020 9:07:44 AM | A | PART |
|
|
Final fire alarm testing for in ducts located in east office in scope of work is complete.
This inspection is for the additional 4 in-duct smoke detectors controlling 4 dampers in one office. Call first please. Phone #: ###-#### Inspection requested via web by Jim Shilton
|