Inspections for the day of: Thursday, May 28, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00743 INSP-Sprinkler Rough-in5/27/20205/28/20205/28/2020 4:24:39 PMPPART
Rough in inspection for gymnasium area is complete. Rough to cover inspection for overhead fire sprinkler piping above hardlid type ceiling in center entry is complete, approved for cover.

Contact Tanner Loomis ###-#### 30 min prior to RTC Insp start please. Area to inspect is the high area in the middle of the building and the gym. Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR20-00148 INSP-Sprinkler Rough-in5/27/20205/28/20205/28/2020 2:06:12 PMPPASS
Rough to cover inspection for undergorund supply complete, approved for cover.

Approval to cover on underground.
Contact: Mike Martin Phone #: ###-#### Inspection requested via web by Hunter Fillmore
BLD20-01058 FIRE-Final Inspection5/28/20205/28/20205/28/2020 2:05:42 PMPPASS
No fire sprinkler modifications, fire alarm modifications were completed under FIR20-00343, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work is complete, signatures provided on permit sign off card.

call to meet there // Jeremy Phone #: ###-####
BLD19-01893 FIRE-Final Inspection5/28/20205/28/20205/28/2020 12:07:55 PMPFAIL
Fire sprinkler head in restroom is stilled masked off from painting. Escutcheons for fire sprinkler heads are still missing as noted in last fire inspection. Project has 2 FIR permits attached, one for fire sprinkler and one for fire alarm that must be inspected and completed before life fire safety inspection can be completed.

Access key pad 1208 Phone #: ###-#### Inspection requested via web by Josh Strasser
BLD19-02606 FIRE-Final Inspection5/28/20205/28/20205/28/2020 12:05:51 PMPFAIL
Ceiling tile is mising thoughout tenant space, tiles must be installed for fire sprinkler heat collection.

Key pad is on 7052 address door Code 1208 Phone #: ###-#### Inspection requested via web by Josh Strasser
FIR20-00185 INSP-Alarm Testing5/27/20205/28/20205/28/2020 9:07:44 AMAPART
Final fire alarm testing for in ducts located in east office in scope of work is complete.

This inspection is for the additional 4 in-duct smoke detectors controlling 4 dampers in one office.
Call first please. Phone #: ###-#### Inspection requested via web by Jim Shilton