FIR12-00309
| FIR-Aging Inspection | 6/12/2019 | 6/12/2019 | 6/20/2019 9:11:29 AM | | FAIL |
|
|
Plans do not reflect circuit layout on the line drawings.
|
BLD19-00242
| FIRE-Final Inspection | 6/12/2019 | 6/12/2019 | 6/12/2019 4:20:00 PM | P | PART |
|
|
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers will be placed in discussed location. TCO is authorized contingent on the racking permit (BLD19-02023) getting inspected and passed. After racking permit is finaled then a final life fire safety inspection will be required to finalize inspection process for life safety.
David Phone #: ###-####
|
NAF19-00023
| INSP-Final | 6/12/2019 | 6/12/2019 | 6/12/2019 3:48:03 PM | P | FAIL |
|
|
Insulation is resting/covering numerous upright sprinkler heads in warehouse, insulation cannot be resting/covering sprinkler heads, insulation will need to be raised.
Call prior to going Phone #: 2089473955 >> Inspection requested via mobile web by David
|
NAF18-00124
| INSP-Sprinkler Rough-in | 6/11/2019 | 6/12/2019 | 6/12/2019 3:22:03 PM | P | PART |
|
|
Inspection for overhead fire sprinkler piping above hardlids on level 1 breezeway and level 1 parking on the northwest complete, areas inspected approved for cover.
side of Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
|
FIR19-00208
| INSP-Final Inspection | 6/11/2019 | 6/12/2019 | 6/12/2019 3:05:48 PM | P | PASS |
|
|
Final hood suppression system inspection compete.
Please call 1 hour prior to arrival to allow us time to get there and set up. We typically work nights so we are not early risers... Phone #: ###-#### Inspection requested via web by JJ Wallace
|
FIR19-00330
| INSP-Final Inspection | 6/12/2019 | 6/12/2019 | 6/12/2019 2:48:01 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work complete.
|
FIR15-00088
| INSP-Final Inspection | 6/10/2019 | 6/12/2019 | 6/12/2019 2:46:15 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
John Phone #: ###-####
|
FIR19-00258
| INSP-Sprinkler Rough-in | 6/12/2019 | 6/12/2019 | 6/12/2019 2:45:53 PM | P | PART |
|
|
Rough to cover inspection for underground stub in complete, approved for cover.
UG rough in. Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
|
FIR18-00698
| INSP-Sprinkler Rough-in/Hydro | 6/12/2019 | 6/12/2019 | 6/12/2019 2:19:14 PM | P | DONE |
|
|
Hydrostatic test for underground supply witnessed, no pressure loss observed.
|
FIR19-00215
| INSP-Sprinkler Rough-in/Hydro | 6/11/2019 | 6/12/2019 | 6/12/2019 2:14:07 PM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Gabe Garduno is the contact. This inspection is to be done in connection with an underground flush/hydro for 11783 W. Fairview at 10:00 AM, as well as an underground flush/hydro for this building. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00637
| FIRE-Final Inspection | 6/12/2019 | 6/12/2019 | 6/12/2019 11:48:18 AM | P | CANC |
|
|
Inspection request will be rescheduled to coincide with fire sprinkler inspection. This request is cancelled per conversation with point of contact.
Joe Phone #: ###-####
|
FIR18-00435
| INSP-Conference | 6/11/2019 | 6/12/2019 | 6/12/2019 11:45:28 AM | P | DONE |
|
|
Per conversation with Ron Johnson, the material that Petra wants to move in needs to be non-combustible material, due to fire sprinklers not being monitored/active then material cannot be combustible. Moving in combustibles that are not associated with cunstruction is fuel loading and per Ron Johnson with Boise Fire this is not acceptable until active fire protection is in place.
Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00414
| INSP-Sprinkler Rough-in | 6/12/2019 | 6/12/2019 | 6/12/2019 11:22:26 AM | P | FAIL |
|
|
Rough in inspection for new sprinkler piping complete, cover is not approved due to insulation/insulation foil is resting on some of the uprights, insualtion and foil must be secure and not resting/blocking fire sprinkler heads.
Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00309
| INSP-Sprinkler Rough-in/Hydro | 6/11/2019 | 6/12/2019 | 6/12/2019 11:17:34 AM | A | CANC |
|
|
Cancelled per conversation with point of contact, leak was found, hydrostatic test to be rescheduled for a later date.
Gabe Garduno is the contact. This inspection is to be done in connection with an underground flush/hydro for 11792 W. Fairview at 10:00 AM, as well as an underground flush/hydro for this building. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00698
| INSP-Supply line flush | 6/11/2019 | 6/12/2019 | 6/12/2019 10:40:55 AM | A | DONE |
|
|
Underground main line flush complete.
Gabe Garduno is the contact. Stacey with Suez will be at this building as well as 11783 at 10:00 AM to do this underground flush. This inspection is to be at the same time as above ground hydros for both buildings as well. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00697
| INSP-Supply line flush | 6/11/2019 | 6/12/2019 | 6/12/2019 10:40:25 AM | A | DONE |
|
|
Underground main line flush complete.
Gabe Garduno is the contact. Stacey with Suez will be at this building as well as 11792 at 10:00 AM to do this underground flush. This inspection is to be at the same time as above ground hydros for both buildings as well. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-03484
| FIRE-Final Inspection | 6/12/2019 | 6/12/2019 | 6/12/2019 10:25:36 AM | P | FAIL |
|
|
Self closing door hinges on east level 1 units are not operable, doors will not close on their own. Provide signage for fire sprinkler riser room and FACP for fire alarm control panel. Provide apartment unit number for each apartment, signage not in place at time of inspection. Install knox box for fire department. Bill Phone #: ###-####
|
FIR19-00263
| INSP-Sprinkler Rough-in | 6/11/2019 | 6/12/2019 | 6/12/2019 9:40:32 AM | A | PART |
|
|
Partial rough to cover inspection for attic dry system complete, notated city approved drawings with yellow highlighter areas approved for cover on the dry system.
Daniel Arce is the contact for this RTC inspection. He is requesting it to be done on the dry system. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00168
| INSP-Sprinkler Rough-in | 6/11/2019 | 6/12/2019 | 6/12/2019 9:00:09 AM | A | PART |
|
|
Rough to cover inspection for sprinkler piping above hardlids in locker rooms complete, approved for cover.
Lonnie Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
|
FIR18-00824
| INSP-Final Inspection | 6/11/2019 | 6/12/2019 | 6/12/2019 8:35:07 AM | A | PASS |
|
|
Final fire sprinkler ispection complete.
Call James to coordinate, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|