Inspections for the day of: Thursday, June 15, 2017.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00222 INSP-Alarm Testing6/15/20176/15/20176/15/2017 3:38:58 PMPPART
Alarm testing performed on all fire sprinkler devices (all tamper switches excluding south standpipe control valve, this valve still needs to be wired to panel, will be locked in the open position until wiring is complete, fire pump power loss, all flow switches, high low air sensors and dry system pressure switches) Smoke/CO2 detectors were tested in units 601 and 602, devices were not going into alarm, alarm testing stopped until troubleshooting can be performed and issues corrected.
FIR16-00088 INSP-Final Inspection6/13/20176/15/20176/15/2017 3:34:06 PMAPART
Partial final inspection for fire sprinklers complete. Main building as well as parking garages complete, town homes will have final inspection requested at a later date (General contractor is requesting TCO for main building untis and parking garage levels including lobbies on both 1st and 2nd, town homes to be completed at a later date)
FIR17-00113 INSP-Final Inspection6/14/20176/15/20176/15/2017 3:30:15 PMPPASS
Final fire sprinkler inspection passed/complete
BLD17-00241 FIRE-Final Inspection6/14/20176/15/20176/15/2017 1:08:30 PMPPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00703 INSP-Sprinkler Rough-in/Hydro6/14/20176/15/20176/15/2017 12:23:49 PMAPASS
Rough to cover inspection complete for overhead fire sprinkler piping, approved for cover. Hydrostatic test complete for overhead fire sprinklers/piping associated with this system.
FIR16-00804 INSP-Sprinkler Rough-in/Hydro6/14/20176/15/20176/15/2017 12:22:54 PMAPASS
Rough to cover inspection complete for overhead fire sprinkler piping, approved for cover. Hydrostatic test complete for overhead fire sprinklers/piping associated with this system.
FIR16-00808 INSP-Sprinkler Rough-in/Hydro6/14/20176/15/20176/15/2017 12:21:04 PMACANC
Inspection request cancelled per conversation with Chris, request will be rescheduled for a later date.
FIR17-00279 INSP-Final Inspection6/14/20176/15/20176/15/2017 12:19:17 PMPPASS
Final fire sprinkler inspection passed/complete
BLD17-00395 FIRE-Final Inspection6/12/20176/15/20176/15/2017 7:16:14 AMAFAIL
No pre-test was performed on fire alarm system for area of work prior to life fire safey inspection, fire alarm failed inspection for area of work. Life fire safety inspection will need to be reschedule when fire alarm issues are resolved.
BLD16-02221 FIRE-Final Inspection6/12/20176/15/20176/15/2017 7:15:54 AMAFAIL
No pre-test was performed on fire alarm system for area of work prior to life fire safey inspection, fire alarm failed inspection for area of work. Life fire safety inspection will need to be reschedule when fire alarm issues are resolved.
BLD16-02185 FIRE-Final Inspection6/12/20176/15/20176/15/2017 7:15:32 AMAFAIL
No pre-test was performed on fire alarm system for area of work prior to life fire safey inspection, fire alarm failed inspection for area of work. Life fire safety inspection will need to be reschedule when fire alarm issues are resolved.
FIR17-00151 INSP-Final Inspection6/14/20176/15/20176/15/2017 7:13:15 AMAPASS
Final fire sprinkler inspection passed/complete
FIR17-00150 INSP-Final Inspection6/14/20176/15/20176/15/2017 7:12:55 AMAPASS
Final fire sprinkler inspection passed/complete
FIR17-00152 INSP-Final Inspection6/14/20176/15/20176/15/2017 7:12:26 AMAPASS
Final fire sprinkler inspection passed/complete
FIR17-00201 INSP-Final Inspection6/15/20176/15/20176/15/2017 7:11:41 AMAFAIL
Area of work has audible notification but visual notification was not operable.
FIR17-00200 INSP-Final Inspection6/15/20176/15/20176/15/2017 7:11:18 AMAFAIL
Area of work has audible notification but visual notification was not operable.
FIR17-00202 INSP-Final Inspection6/15/20176/15/20176/15/2017 7:10:53 AMAFAIL
Area of work has audible notification but visual notification was not operable.
FIR15-00838 INSP-Final Inspection6/15/20176/15/20176/15/2017 6:06:08 AMAPASS
Final inspection for underground supply passed/complete
FIR16-00040 INSP-Supply line flush6/14/20176/15/20176/15/2017 5:49:32 AMADONE
Undergournd flush for south main completed after underground repair was made.