FIR16-00222
| INSP-Alarm Testing | 6/15/2017 | 6/15/2017 | 6/15/2017 3:38:58 PM | P | PART |
|
|
Alarm testing performed on all fire sprinkler devices (all tamper switches excluding south standpipe control valve, this valve still needs to be wired to panel, will be locked in the open position until wiring is complete, fire pump power loss, all flow switches, high low air sensors and dry system pressure switches) Smoke/CO2 detectors were tested in units 601 and 602, devices were not going into alarm, alarm testing stopped until troubleshooting can be performed and issues corrected.
|
FIR16-00088
| INSP-Final Inspection | 6/13/2017 | 6/15/2017 | 6/15/2017 3:34:06 PM | A | PART |
|
|
Partial final inspection for fire sprinklers complete. Main building as well as parking garages complete, town homes will have final inspection requested at a later date (General contractor is requesting TCO for main building untis and parking garage levels including lobbies on both 1st and 2nd, town homes to be completed at a later date)
|
FIR17-00113
| INSP-Final Inspection | 6/14/2017 | 6/15/2017 | 6/15/2017 3:30:15 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD17-00241
| FIRE-Final Inspection | 6/14/2017 | 6/15/2017 | 6/15/2017 1:08:30 PM | P | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR16-00703
| INSP-Sprinkler Rough-in/Hydro | 6/14/2017 | 6/15/2017 | 6/15/2017 12:23:49 PM | A | PASS |
|
|
Rough to cover inspection complete for overhead fire sprinkler piping, approved for cover. Hydrostatic test complete for overhead fire sprinklers/piping associated with this system.
|
FIR16-00804
| INSP-Sprinkler Rough-in/Hydro | 6/14/2017 | 6/15/2017 | 6/15/2017 12:22:54 PM | A | PASS |
|
|
Rough to cover inspection complete for overhead fire sprinkler piping, approved for cover. Hydrostatic test complete for overhead fire sprinklers/piping associated with this system.
|
FIR16-00808
| INSP-Sprinkler Rough-in/Hydro | 6/14/2017 | 6/15/2017 | 6/15/2017 12:21:04 PM | A | CANC |
|
|
Inspection request cancelled per conversation with Chris, request will be rescheduled for a later date.
|
FIR17-00279
| INSP-Final Inspection | 6/14/2017 | 6/15/2017 | 6/15/2017 12:19:17 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD17-00395
| FIRE-Final Inspection | 6/12/2017 | 6/15/2017 | 6/15/2017 7:16:14 AM | A | FAIL |
|
|
No pre-test was performed on fire alarm system for area of work prior to life fire safey inspection, fire alarm failed inspection for area of work. Life fire safety inspection will need to be reschedule when fire alarm issues are resolved.
|
BLD16-02221
| FIRE-Final Inspection | 6/12/2017 | 6/15/2017 | 6/15/2017 7:15:54 AM | A | FAIL |
|
|
No pre-test was performed on fire alarm system for area of work prior to life fire safey inspection, fire alarm failed inspection for area of work. Life fire safety inspection will need to be reschedule when fire alarm issues are resolved.
|
BLD16-02185
| FIRE-Final Inspection | 6/12/2017 | 6/15/2017 | 6/15/2017 7:15:32 AM | A | FAIL |
|
|
No pre-test was performed on fire alarm system for area of work prior to life fire safey inspection, fire alarm failed inspection for area of work. Life fire safety inspection will need to be reschedule when fire alarm issues are resolved.
|
FIR17-00151
| INSP-Final Inspection | 6/14/2017 | 6/15/2017 | 6/15/2017 7:13:15 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR17-00150
| INSP-Final Inspection | 6/14/2017 | 6/15/2017 | 6/15/2017 7:12:55 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR17-00152
| INSP-Final Inspection | 6/14/2017 | 6/15/2017 | 6/15/2017 7:12:26 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR17-00201
| INSP-Final Inspection | 6/15/2017 | 6/15/2017 | 6/15/2017 7:11:41 AM | A | FAIL |
|
|
Area of work has audible notification but visual notification was not operable.
|
FIR17-00200
| INSP-Final Inspection | 6/15/2017 | 6/15/2017 | 6/15/2017 7:11:18 AM | A | FAIL |
|
|
Area of work has audible notification but visual notification was not operable.
|
FIR17-00202
| INSP-Final Inspection | 6/15/2017 | 6/15/2017 | 6/15/2017 7:10:53 AM | A | FAIL |
|
|
Area of work has audible notification but visual notification was not operable.
|
FIR15-00838
| INSP-Final Inspection | 6/15/2017 | 6/15/2017 | 6/15/2017 6:06:08 AM | A | PASS |
|
|
Final inspection for underground supply passed/complete
|
FIR16-00040
| INSP-Supply line flush | 6/14/2017 | 6/15/2017 | 6/15/2017 5:49:32 AM | A | DONE |
|
|
Undergournd flush for south main completed after underground repair was made.
|