FIR19-00252
| INSP-Sprinkler Rough-in | 6/18/2019 | 6/18/2019 | 6/18/2019 3:23:49 PM | P | PASS |
|
|
Rough in inspection for new overhead fire sprinkler piping below new hardlid in area of work complete. Insulation has been moved to above sprinkler piping in attic space.
chris Phone #: ###-####
|
BLD18-04579
| FIRE-Final Inspection | 6/18/2019 | 6/18/2019 | 6/18/2019 2:02:07 PM | P | PART |
|
|
No fire sprinkler, no fire alarms, fire extinguishers in the 1509 addressed area are placed with current inspection tags. Partial final for life fire safety inspection complete for the 1509 address side of the core and shell project, restrooms on the 1511 address side are part of the core and shell remodel, restrooms on mentioned side will still need to be completed for core and shell sign off for life fire safety. Per conversation with Ron Johnson with Boise Fire a 90 day TCO is authorized contingent on the restrooms being completed on the 1511 address side.
Dale Phone #: ###-####
|
BLD19-00722
| FIRE-Final Inspection | 6/18/2019 | 6/18/2019 | 6/18/2019 2:00:25 PM | P | PART |
|
|
Partial final for life fire safety inspection complete. No fire sprinklers, no fire alarms, fire exitnguishers are placed with a current inspection tags. A 90 day TCO is auhtorized for life fire safety inspection per conversation with Ron Johnson with Boise Fire contingent on the core and shell permit being finaled (BLD18-04579).
|
FIR18-00943
| INSP-Final Inspection | 6/17/2019 | 6/18/2019 | 6/18/2019 1:54:04 PM | P | PASS |
|
|
Previously noted items have been corrected, final fire sprinkler inspection complete.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00078
| INSP-Final Inspection | 6/17/2019 | 6/18/2019 | 6/18/2019 10:33:07 AM | A | PASS |
|
|
Previously noted items have been completed, final life fire safety inspection comlpete.
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
BLD19-01309
| FIRE-Final Inspection | 6/11/2019 | 6/18/2019 | 6/18/2019 9:53:42 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire exitnguishers will be mounted in discussed locations. Final life fire safety inspection complete.
Tracy Phone #: ###-####
|
FIR19-00263
| INSP-Sprinkler Rough-in/Hydro | 6/14/2019 | 6/18/2019 | 6/18/2019 9:38:18 AM | A | PART |
|
|
Rough to cover ispection for remaining piping above hardlids on level 1 complete, hardlids on level 1 approved for cover.
Robert Chambers is the contact for this RTC/ Hydro inspection on the 1st Floor. He is hoping for an appointment around 9AM. We appreciate your help. Have a nice day Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00112
| INSP-Final Inspection | 6/17/2019 | 6/18/2019 | 6/18/2019 9:19:41 AM | A | FAIL |
|
|
Audio visual device in basement next to print room is blocked by duct work. Sound requirements were no met for basement level restrooms. Adjust/add notification that is blocked on level 2, city approved drawings are notated for areas that require attention.
John Howard Technician, Phone #: ###-#### Inspection requested via web by John Siewert
|