Inspections for the day of: Wednesday, June 19, 2019.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-02161 FIRE-Final Inspection6/17/20196/19/20196/19/2019 4:19:51 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Larren Phone #: ###-####
BLD19-02154 FIRE-Final Inspection6/17/20196/19/20196/19/2019 4:19:00 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Larren Phone #: ###-####
BLD19-02162 FIRE-Final Inspection6/17/20196/19/20196/19/2019 4:18:38 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Larren Phone #: ###-####
BLD19-02160 FIRE-Final Inspection6/17/20196/19/20196/19/2019 4:17:54 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Larren Phone #: ###-####
FIR19-00126 INSP-Sprinkler Rough-in6/19/20196/19/20196/19/2019 3:11:35 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in basement level complete, approved for cover, notated city approved drawings 3 areas that has exposed combustibles above ceiling grid, sprinkler protection will be required for mentioned areas, will verify coverage is in place during a follow up inspection. Level 1 sprinkler rough in complete.

Contact Ken Orahood ###-#### 30 min prior to RTC Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD17-01000 FIRE-Final Inspection6/19/20196/19/20196/19/2019 2:30:27 PMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. 2015 IFC was approved per official request to Ron Johnson with Boise Fire to be used for the access control system due to the changes made in the code cycle between 2012 IFC and 2015 IFC, code segment 1010.1.9.8 is allowed from the 2015 IFC instead of the requirements of the 2012 IFC section 1008.1.9.8.

Final life fire safety inspection is complete.

Bruce Phone #: ###-####
BLD19-01162 FIRE-Final Inspection6/19/20196/19/20196/19/2019 1:31:03 PMPFAIL
Fire sprinkler pendant head that provided sprinkler coverage in room that was removed is still in place, upright protection is adequate but pendant head needs to be removed, a permit is required for any fire sprinkler modifications.

Tim Phone #: ###-####
BLD19-00904 FIRE-Final Inspection6/19/20196/19/20196/19/2019 1:09:25 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.

Joseph Phone #: ###-####
FIR18-00302 INSP-Final Inspection6/18/20196/19/20196/19/2019 12:13:47 PMACANC
Inspection request cancelled per conversation with point of contact, city approved drawings/small documents could not be located, city approved drawings and small documents are required for inspection.

Dillion Phone #: ###-####
FIR18-00301 INSP-Final Inspection6/18/20196/19/20196/19/2019 12:13:28 PMACANC
Inspection request cancelled per conversation with point of contact, city approved drawings/small documents could not be located, city approved drawings and small documents are required for inspection.

Dillion Phone #: ###-####
FIR18-00300 INSP-Final Inspection6/18/20196/19/20196/19/2019 12:10:44 PMACANC
Inspection request cancelled per conversation with point of contact, city approved drawings/small documents could not be located, city approved drawings and small documents are required for inspection.

Dillion Phone #: ###-####
FIR18-00180 INSP-Final Inspection6/18/20196/19/20196/19/2019 12:09:24 PMACANC
Inspection request cancelled per conversation with point of contact, city approved drawings/small documents could not be located, city approved drawings and small documents are required for inspection.

Dillion Phone #: ###-####
FIR18-00001 INSP-Final Inspection6/18/20196/19/20196/19/2019 12:08:52 PMACANC
Inspection request cancelled per conversation with point of contact, city approved drawings/small documents could not be located, city approved drawings and small documents are required for inspection.

Dillion Phone #: ###-####
BLD18-02821 FIRE-Supply Line Cover6/19/20196/19/20196/19/2019 11:27:09 AMACANC
Tenting inspection needs to be requested by the fire sprinkler contractor, this request is cancelled and future fire sprinkler related inspection must be done under associated FIR permit.

Insulation or tent over fire sprinkler piping that is in attic area of project. Not sure if we ordered the correct inspection? Phone #: ###-#### Inspection requested via web by James Larkin
FIR19-00418 INSP-Sprinkler Rough-in6/18/20196/19/20196/19/2019 11:25:53 AMPFAIL
Tenting had not been started at time of inspection, request will need to be rescheduled.

Tenting Inspection, should be ready by afternoon. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00207 INSP-Sprinkler Rough-in6/19/20196/19/20196/19/2019 11:24:50 AMPFAIL
Piping exposed in north part of attic space. Tenting is not installed correctly in numerous areas at time of inspection, areas of concern will allow blow-in type insulation to get under pipe and filling pocket that is required between piping and sheetrock.

Tenting Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-02139 FIRE-Final Inspection6/18/20196/19/20196/19/2019 10:41:51 AMAFAIL
Service/replace non-operational emergrncy lighting and exit signs or have them removed as they are not required. Fire extinguishers need to inspected/serviced and tagged accordingly. Provide code compliant size numbering for address.

Please call for access- Andrew ###-####
FIR17-00508 INSP-Final Inspection6/19/20196/19/20196/19/2019 10:27:27 AMPPASS
Final fire alarm inspection complete. Project was reviewed under the 2012 IBC and IFC which required releasing of the access control per section 1008.1.9.8, Ron Johnson allowed the code section 1010.1.9.8 of the 2015 IFC to be applied due to the change in code requirements and application for this project.

Kristin Phone #: ###-####
FIR19-00322 INSP-Final Inspection6/18/20196/19/20196/19/2019 9:34:50 AMAPASS

Previously noted items have been corrected, final fire alarm inspection complete.

Phone #: ###-#### Inspection requested via web by Matt Casey
FIR17-00474 INSP-Final Inspection6/18/20196/19/20196/19/2019 9:29:38 AMAPASS
Final fire sprinkler inspection is complete.

Mark Jensen is the contact. This inspection has already been done, they just wanted a paper trail. Call the contact with further questions. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00784 INSP-Final Inspection6/18/20196/19/20196/19/2019 9:28:54 AMAPASS
Previously noted items have been corrected, final inspection complete. Noted that the fire department has been informed of the grease build up behind the placed aluminum foil to cover mentioned grease.

nate Phone #: ###-####