Inspections for the day of: Monday, June 24, 2019.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00473 INSP-Final Inspection6/24/20196/24/20196/24/2019 4:08:32 PMPPASS
Final fire sprinkler inspection for area of work complete.

Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00473 INSP-Sprinkler Rough-in6/24/20196/24/20196/24/2019 4:07:40 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
BLD19-00792 FIRE-Final Inspection6/24/20196/24/20196/24/2019 2:56:25 PMPPASS
No fire sprinklers, smoke detectors are stand alone and not monitored, fire extinguisher is placed and will be inspected and tagged with a current inspection tag. Final life fire safety inspection for area of work complete.

Mike Phone #: ###-####
BLD19-00682 FIRE-Final Inspection6/24/20196/24/20196/24/2019 2:13:59 PMPFAIL
Emergency lights by east side entry and west side office space did not operate when A/C power was isolated. FIR permit for fire sprinklers needs to be finaled before fire life safety inspection can be completed. Provide suite number for tenant space.

John Phone #: ###-####
FIR19-00391 INSP-Final Inspection6/20/20196/24/20196/24/2019 2:11:33 PMPPASS
Final fire alarm inspection for area of work complete.

Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR19-00327 INSP-Sprinkler Rough-in/Hydro6/24/20196/24/20196/24/2019 1:15:27 PMPDONE
Hydrostatic test witnessed at city pressure (No FDC connection, static city pressure is required for a minimum), no pressure loss observed.
FIR19-00327 INSP-Sprinkler Rough-in6/24/20196/24/20196/24/2019 1:13:55 PMPPART
Rough in inspection for overhead fire sprinkler piping complete. Tenting was installed on the sprinkler heads only, all other piping still exposed to attice space. Remaining tenting will need to be installed, cover is no approved until all tenting is installed, inspected and passed.

Colton Cox is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00394 INSP-Sprinkler Rough-in6/24/20196/24/20196/24/2019 12:31:30 PMPPART
Rough to cover inspection for underground supply stub-up and first change of direction from under the footing complete, area inspected approved for cover, remaining underground to be inspected at a later date.

underground Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR19-00278 INSP-Sprinkler Rough-in6/24/20196/24/20196/24/2019 12:00:15 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Adam Phone #: ###-####
FIR18-00964 INSP-Sprinkler Rough-in6/24/20196/24/20196/24/2019 11:36:26 AMPPASS
Rough in and rough to cover inspections for overhead fire sprinkler piping in new addition complete, demo work, where required, for fire sprinkler piping in existing building to be completed at a later date. Awaiting final inspection request from the fire alarm vendor to final fire sprinkler systems.

Please call Lonnie with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
FIR19-00256 INSP-Final Inspection6/21/20196/24/20196/24/2019 11:23:46 AMAPART
Final inspection for life fire safety substantially complete. Fire alarm inspection is complete, no fire sprinklers, fire extinuishers are placed with current inspection tags. TCO is authorized for 30 days contingent on knox box being installed. Will need to verify if building has seperate address for tenant spaces or if each space has an address, will verify with knox box install.

Please call 30 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by Kristin Dolan
BLD19-00488 FIRE-Final Inspection6/21/20196/24/20196/24/2019 11:20:23 AMAPASS
Final fire alarm inspection complete.

Clint Phone #: ###-####
FIR19-00374 INSP-Sprinkler Rough-in/Hydro6/20/20196/24/20196/24/2019 10:20:45 AMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00699 INSP-Sprinkler Rough-in/Hydro6/21/20196/24/20196/24/2019 10:20:07 AMADONE
Underground hydrostatic test witnessed, no pressure loss observed.

Gabe Garduno is the contact. Stacey is aware of this flush/hydro inspection, he will be there. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00699 INSP-Supply line flush6/21/20196/24/20196/24/2019 10:19:11 AMADONE
Underground main line flush complete.

Gabe Garduno is the contact. Stacey is aware of this flush/hydro inspection, he will be there. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00119 INSP-Final Inspection6/24/20196/24/20196/24/2019 10:17:44 AMPFAIL
Relocate head in master closet as discussed. Pressure relief hose kept coming loose during flow test, still need to accomplish flow test. Raise head in closet next to mech room as discussed.

Contact Ken Orahood ###-#### Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF19-00019 INSP-Sprinkler Rough-in6/21/20196/24/20196/24/2019 10:15:23 AMAPASS
Previously noted items have been corrected.

Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Bryan
FIR19-00111 INSP-Final Inspection6/20/20196/24/20196/24/2019 9:19:44 AMACANC
Contact Ken Orahood ###-#### 30 min prior to Final Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
BLD19-01444 FIRE-Final Inspection6/22/20196/24/20196/24/2019 8:56:26 AMAFAIL
Provide addressing for tenant space. Provide fire extinguisher with a current inspection tag, cuurent inspection on extinguisher was completed in 2009. Exit sign/emergency lighting needs serviced, all exit/emergency lighting did not operate when A/C power was isolated. Provide sign at front door reading "Door to remain unlocked while building is occupied", signage currently reads "Door to remain unlocked during business hours". Rear exit is partially blocked by mattress storage.

Fire, Life and Safety inspection to be completed at the same time as fire sprinkler if possible-please call chad for access 208.994.2805 Phone #: ###-#### Inspection requested via web by Chad Aland
FIR19-00457 INSP-Final Inspection6/24/20196/24/20196/24/2019 8:52:26 AMAPASS
Final fire sprinkler ispection for area of work complete.
FIR19-00457 INSP-Sprinkler Rough-in6/21/20196/24/20196/24/2019 8:50:55 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello