BLD17-04653
| FIRE-Final Inspection | 6/26/2019 | 6/26/2019 | 6/26/2019 3:26:48 PM | P | PASS |
|
|
Previously noted items have been corrected. Fire sprinkler inspection is complete, fire alarm inspection is complete, hood suppression system inspection are complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
Please call before. Thank you David. Phone #: ###-#### Inspection requested via web by David Sferle
|
FIR18-00886
| INSP-Sprinkler Rough-in | 6/26/2019 | 6/26/2019 | 6/26/2019 3:06:31 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids in rooms 109 and 256 complete, hardlids approved for cover.
Contact Noemi Carrero - ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00117
| INSP-Final Inspection | 6/25/2019 | 6/26/2019 | 6/26/2019 2:41:32 PM | P | FAIL |
|
|
Provide 911 sign for fire bell. Sprinkler head in entry is to close to crown molding, need a minimum of 4 inches to be code compliant. Need to raise head in bedroom that is hanging down below ceiling.
please give a heads up thank you Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR19-00262
| INSP-Final Inspection | 6/24/2019 | 6/26/2019 | 6/26/2019 1:53:41 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Jason Phone #: ###-####
|
BLD17-04623
| FIRE-Final Inspection | 6/25/2019 | 6/26/2019 | 6/26/2019 1:25:50 PM | P | FAIL |
|
|
Called point of contact with no answer, provide street address fopr building. Could not access rooms to verify sprinkler escutcheons were in place. Need fire lane signage installed where required.
Fire/ Life ; Safety Final. Phone #: ###-#### Inspection requested via web by J.C. Murray
|
BLD18-02797
| FIRE-Conference | 6/25/2019 | 6/26/2019 | 6/26/2019 12:46:14 PM | A | DONE |
|
|
Fire conference complete, per international fire code, section 1013.1 requires exit signs to be visible within 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Mike Phone #: ###-####
|
FIR19-00221
| INSP-Sprinkler Rough-in | 6/26/2019 | 6/26/2019 | 6/26/2019 12:39:57 PM | A | PART |
|
|
Rough in inspection complete for levels 2 and 3 suites complete, notated city approved plans with pink highlighter areas that were inspected. Sprinkler piping in areas inspected that is betewwen conditioned spaces approved for cover, areas requiring tenting not approved for cover until tenting has been inspected and passed.
This an rough inspection for the 3rd and 2nd floor of the South side of the building. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR19-00285
| INSP-Final Inspection | 6/25/2019 | 6/26/2019 | 6/26/2019 12:37:34 PM | P | PASS |
|
|
Final fire alarm inspection for area of work complete.
Please call 1 hour prior to ensure that all parties involved will be onsite. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
BLD19-00278
| FIRE-Conference | 6/25/2019 | 6/26/2019 | 6/26/2019 10:22:09 AM | A | DONE |
|
|
Fire conference complete.
Layout for smoke detectors in hallways. Please call and let me know when you''re on site. Phone #: ###-#### Inspection requested via web by Corey Hockersmith
|
FIR19-00456
| INSP-Sprinkler Rough-in | 6/25/2019 | 6/26/2019 | 6/26/2019 9:52:28 AM | P | CANC |
|
|
Duplicate inspection request, this request is cancelled.
John Phone #: ###-####
|
FIR19-00456
| INSP-Sprinkler Rough-in | 6/25/2019 | 6/26/2019 | 6/26/2019 9:51:55 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Payton Phone #: ###-####
|
FIR18-00886
| INSP-Sprinkler Rough-in | 6/26/2019 | 6/26/2019 | 6/26/2019 9:44:43 AM | P | CANC |
|
|
Contact Noemi Carrero ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
FIR19-00327
| INSP-Sprinkler Rough-in | 6/25/2019 | 6/26/2019 | 6/26/2019 9:38:36 AM | A | FAIL |
|
|
Tenting is not installed correctly in numerous areas.
Colton Cox is the contact. He would like this inspection to be for the tenting. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00071
| INSP-Final Inspection | 6/25/2019 | 6/26/2019 | 6/26/2019 8:57:59 AM | A | PASS |
|
|
Final fire alarm ispection for scope of work complete.
Dave Phone #: ###-####
|
FIR19-00442
| INSP-Sprinkler Rough-in | 6/25/2019 | 6/26/2019 | 6/25/2019 4:27:58 PM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, scope of work approved for cover.
Tom Phone #: ###-####
|