Inspections for the day of: Thursday, June 27, 2019.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-02139 FIRE-Final Inspection6/27/20196/27/20196/27/2019 3:50:37 PMACANC
Cooridnated for 10AM with point of contact. Please call for access- Linda Phone #: ###-####
NAF18-00085 INSP-Sprinkler Rough-in/Hydro6/26/20196/27/20196/27/2019 3:41:04 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00083 INSP-Sprinkler Rough-in/Hydro6/26/20196/27/20196/27/2019 3:41:03 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00084 INSP-Sprinkler Rough-in/Hydro6/26/20196/27/20196/27/2019 3:41:03 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00086 INSP-Sprinkler Rough-in/Hydro6/26/20196/27/20196/27/2019 3:41:02 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00086 INSP-Sprinkler Rough-in6/26/20196/27/20196/27/2019 3:41:02 PMPFAIL
Tenting is still not correct on level 4, refer to diagram on city approved drawings for correct install of tenting. Exposed CPVC under stairs on level 1. Head is blocked in garage be garage door bracing, obstruction was mentioned on last inspection. Remote area on level 4 does not match city approved drawings, remote area needs to match or a plan mod needs to be completed showing changes in remote calc area.

Contact Andrew Larson ###-#### 30 min prior to RTC Insp Start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00394 INSP-Sprinkler Rough-in/Hydro6/27/20196/27/20196/27/2019 1:58:31 PMPDONE
Hydrostatic test for underground supply witnessed, no pressure loss observed.

underground Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR19-00263 INSP-Sprinkler Rough-in6/26/20196/27/20196/27/2019 1:33:52 PMPPART
Rough to cover inspection for overhead fire sprinkler piping above lowered hardlids in kitchen/dining/living room complete, area inspected approved for cover. Exterior battered wall on southwest corner of Area A is filled with non-combustible insulation, area inspected approved for cover. As-builts need to show deleted heads that will no longer be in the area filled with insulation.

Robert Chambers is the contact for this inspection. This rough-in is for the 1st floor area A section 2. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-00278 FIRE-Conference6/26/20196/27/20196/27/2019 1:31:30 PMPDONE
Fire conference complete, exterior battered wall on southwest corner of Area A is filled with non-combustible insulation, area inspected approved for cover.

Phone #: ###-#### Inspection requested via web by Corey Hockersmith
BLD19-01981 FIRE-Final Inspection6/27/20196/27/20196/27/2019 12:39:44 PMPPASS
No fire sprinklers, no fire alarms, fire extinuisher will be placed in discussed location and had a current inspection tag. Final life fire safety inspection for area of work complete.

Ariel Phone #: ###-####
FIR19-00233 INSP-Conference6/27/20196/27/20196/27/2019 12:17:09 PMPDONE
Gas meter is set in the wrong location, city approved drawings show gas meter by north door, currently meter is set under PIV for fire sprinklers, needs to be relocated to give the required 36 inch clearance around PIV.
BLD18-04470 FIRE-Conference6/27/20196/27/20196/27/2019 12:10:31 PMPCANC
BLD18-04470 FIRE-Conference6/27/20196/27/20196/27/2019 12:10:10 PMPDONE
Gas meter is set in the wrong location, city approved drawings show gas meter by north door, currently meter is set under PIV for fire sprinklers, needs to be relocated to give the required 36 inch clearance around PIV.
FIR19-00327 INSP-Sprinkler Rough-in6/26/20196/27/20196/27/2019 10:53:59 AMAPASS
Tenting has been corrected, all tenting in place at time of inspection. Overhead fire sprinkler piping/tenting approved for cover.

Colton Cox is the contact. This rough-in is for the tinting inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-01444 FIRE-Final Inspection6/26/20196/27/20196/27/2019 10:37:25 AMPPASS
Previously noted items have been corrected. Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work comlpete.

Access is through a lock box located in the mailbox beside the door. Code is 2805 Phone #: ###-#### Inspection requested via web by Chad Aland
FIR19-00372 INSP-Sprinkler Rough-in6/27/20196/27/20196/27/2019 10:18:55 AMAFAIL
Sprinkler head in foyer is overspaced, head is more than 9 feet off of wall, spacing for this area is 16 X 16 so head needs to be a maximum of 8 feet off of wall. A wall has been added in the office, need to verify if the 20 X 20 spacing will work in this room with the new wall splitting the 2 heads shown on the city approved drawings. As-builts will be required for heads added for beam in entry hallway and changes to floor plan. No tenting installed at time of inspection.
FIR19-00372 INSP-Sprinkler Rough-in/Hydro6/27/20196/27/20196/27/2019 10:15:17 AMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed at 150PSI instead of the city static pressure, no pressure loss observed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00117 INSP-Final Inspection6/27/20196/27/20196/27/2019 9:40:21 AMPPASS
Previously noted items have been completed, final fire sprinkler inspection complete. Fire sprinkler system is a shared system with the domestic, the lawn sprinklers is pressurized irrigation, not domestic treated water, irrigation shut-down on flow switch not required for this application.

all fixes are done thank you. Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00462 INSP-Final Inspection6/26/20196/27/20196/27/2019 8:34:53 AMAPASS
Final fire sprinkler inspection for area of work complete.

Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00462 INSP-Sprinkler Rough-in6/26/20196/27/20196/27/2019 8:34:21 AMAPASS
Rough in inspection for area of work complete.

Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
BLD19-02139 FIRE-Final Inspection6/26/20196/27/20196/27/2019 8:27:34 AMACANC
Inspection request is rescheduled for 28JUNE2019 per conversation with point of contact due to scheduling issues on meet up time. Inspection is rescheduled and this request is cancelled.

Please call for access- Linda Phone #: ###-####
FIR19-00250 INSP-Final Inspection6/26/20196/27/20196/27/2019 8:25:49 AMPCANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 27, 2019.
FIR19-00389 INSP-Final Inspection6/26/20196/27/20196/27/2019 7:17:37 AMACANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 27, 2019.
FIR19-00250 INSP-Final Inspection6/26/20196/27/20196/26/2019 11:01:29 AMACANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Wednesday, June 26, 2019.