FIR19-00215
| INSP-Final Inspection | 6/28/2019 | 6/28/2019 | 6/28/2019 1:43:33 PM | P | CANC |
|
|
Inspection request needs to be coordinated with fire alarm vendor, alarm contractor has inspection scheduled for 01JULY2019, this request is cancelled.
Gabe Garduno is the contact for this final. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00221
| INSP-Sprinkler Rough-in/Hydro | 6/28/2019 | 6/28/2019 | 6/28/2019 1:42:15 PM | P | DONE |
|
|
24 hour air test for dry system on level 1 witnessed, no pressure loss observed.
|
FIR19-00221
| INSP-Sprinkler Rough-in | 6/28/2019 | 6/28/2019 | 6/28/2019 1:40:59 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping in level 1 apartment units and storage area complete, notated city approved drawings areas approved for cover, also notated sprinkler head in east corridor next to storage area that will require some type of freeze protection.
Tom Phone #: ###-####
|
BLD19-01483
| FIRE-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 11:35:49 AM | A | PASS |
|
|
No fire sprinkler modifications for this space (fire sprinklers modifications are under the 300 address), no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
were underShawn Phone #: ###-####- please call 30 min prior for access
|
BLD19-01482
| FIRE-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 11:31:46 AM | A | PASS |
|
|
Fire sprinkler inspection complete, no fire alam modifications, fire extinguishers are mounted with current inspection tags. Final life fire safety inspection for area of work complete.
Shawn Phone #: ###-#### please call 30 min prior for access
|
BLD19-00560
| FIRE-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 10:49:31 AM | A | CANC |
|
|
Due to the history of this permit, the point of contact is going to reschedule for when Troy Cobbley is back in the office, this request is cancelled per conversation with point of contact.
Ann Phone #: ###-####
|
BLD17-02434
| FIRE-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 10:49:15 AM | A | CANC |
|
|
Due to the history of this permit, the point of contact is going to reschedule for when Troy Cobbley is back in the office, this request is cancelled per conversation with point of contact.
Ann Phone #: ###-####
|
BLD17-02437
| FIRE-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 10:47:59 AM | A | CANC |
|
|
Due to the history of this permit, the point of contact is going to reschedule for when Troy Cobbley is back in the office, this request is cancelled per conversation with point of contact.
Call for access- Ann Phone #: ###-####
|
BLD17-02439
| FIRE-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 10:47:41 AM | A | CANC |
|
|
Due to the history of this permit, the point of contact is going to reschedule for when Troy Cobbley is back in the office, this request is cancelled per conversation with point of contact.
Ann Phone #: ###-####
|
BLD17-02436
| FIRE-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 10:47:31 AM | A | CANC |
|
|
Due to the history of this permit, the point of contact is going to reschedule for when Troy Cobbley is back in the office, this request is cancelled per conversation with point of contact.
Ann Phone #: ###-####
|
BLD19-00630
| FIRE-Final Inspection | 6/28/2019 | 6/28/2019 | 6/28/2019 10:46:23 AM | P | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire exitnguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
|
FIR18-00633
| INSP-Sprinkler Rough-in/Hydro | 6/26/2019 | 6/28/2019 | 6/28/2019 10:17:12 AM | A | PART |
|
|
Hydrostatic test for levels 2, 3, 4 and standpipe witnessed, no pressure loss observed, level 1 is the last hydro requirement.
Kenny Caldwell is the contact for this full building hydro. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00633
| INSP-Sprinkler Rough-in | 6/26/2019 | 6/28/2019 | 6/28/2019 10:16:03 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping in remaining apartments on level 1 complete, approved for cover.
Kenny Caldwell is the contact for this partial rough-in for the 1st floor. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00447
| INSP-Final Inspection | 6/26/2019 | 6/28/2019 | 6/28/2019 10:14:06 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00340
| INSP-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 10:13:51 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-01272
| FIRE-Final Inspection | 6/28/2019 | 6/28/2019 | 6/28/2019 8:55:18 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag, suite number will be installed before final BLD inspection. Final life fire safety inspection for area of work complete.
|
BLD19-01372
| FIRE-Final Inspection | 6/26/2019 | 6/28/2019 | 6/28/2019 8:53:28 AM | A | CANC |
|
|
Wrong permit requested for inspection, this request is cancelled.
John Phone #: ###-####
|
FIR19-00324
| INSP-Final Inspection | 6/28/2019 | 6/28/2019 | 6/28/2019 8:12:01 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Adam Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD19-01162
| FIRE-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 8:07:41 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety for area of work complete.
Tim Phone #: ###-####
|
FIR19-00472
| INSP-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 8:04:39 AM | A | PASS |
|
|
Final fire sprinkler inspection for scope of work complete.
Chris Lamb is the contact for this final inspection. Thank you for your help.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00215
| INSP-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 7:57:22 AM | A | CANC |
|
|
Could not final, fire alarms not ready, this request is cancelled.
Gabe Garduno is the contact. Thank you for all that you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00698
| INSP-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 7:56:55 AM | A | CANC |
|
|
Could not final, fire alarms not ready, this request is cancelled.
Gabe Garduno is the contact. Thank you for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00202
| INSP-Final Inspection | 6/26/2019 | 6/28/2019 | 6/28/2019 7:56:15 AM | A | FAIL |
|
|
Fire alarm system not ready for inspection.
I would like an 8:00am fire alarm final Inspection Phone #: ###-#### Inspection requested via web by Heather Stier
|
FIR19-00250
| INSP-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 12:00:00 AM | A | PART |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
6-28-19 All smoke detectors and pull stations tested. Most heat detectors tested. All functioned properly. 1 sounder base failed in a room that is accessible from the outside only. 3 existing notification devices that do not work and no longer required need to be removed. 1 abandonded notification power supply has had the equipment removed but abandonded wiring still exists. Abandonded wire is to be removed per NEC requirements. Reinspection required once corrections have been made.
|
BLD19-02139
| Extend Permit 90/180 days | 6/27/2019 | 6/28/2019 | 6/27/2019 3:49:07 PM | A | CANC |
|
|
Cooridnated for 10AM with point of contact. Please call for access- Linda Phone #: ###-####
|