Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00232 INSP-Final Inspection7/10/20207/14/20207/14/2020 3:07:25 PMPFAIL
Provide weather proof enclosures for A/V devices in restrooms with showers (Boxes were being installed at time of inspection). Provide document cabinet as well as map showing initiating devices, map to be placed by fire alarm panel.

screened // Michael Phone #: ###-####
FIR19-00779 INSP-Final Inspection7/14/20207/14/20207/14/2020 12:22:23 PMACANC
Cancelled per conversation with point of contact, could not final due too fire alarm inspection not being scheduled, inspection request will be rescheduled too conicide with fire alarm inspection.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00375 INSP-Sprinkler Rough-in/Hydro7/14/20207/14/20207/14/2020 11:06:27 AMADONE
Hydrostatic test witnessed, no pressure loss observed at riser provided gauge.

Call James before heading out, rough/hydro/tenting. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00375 INSP-Sprinkler Rough-in7/14/20207/14/20207/14/2020 11:02:43 AMAPASS
Previously noted items have been corrected, cover is approved. All tenting in place at time of inspection.

FIR20-00168 INSP-Sprinkler Rough-in7/13/20207/14/20207/14/2020 10:30:09 AMAPART
Rough to cover inspection from grid line 8 west is approved for cover, excluding main corridor located south side of building, grid is not installed.

Richard Clark is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus