FIR17-00303
| INSP-Sprinkler Rough-in | 7/17/2017 | 7/17/2017 | 7/17/2017 3:18:11 PM | P | PART |
|
|
Partial rough to cover inspection complete for the underground, in building riser for building stub up approved for cover, remaining underground to be installed at a later date.
|
FIR17-00162
| INSP-Final Inspection | 7/17/2017 | 7/17/2017 | 7/17/2017 2:49:18 PM | P | CANC |
|
|
Inspection for this permit to be completed at a later date.
|
FIR17-00080
| INSP-Final Inspection | 7/14/2017 | 7/17/2017 | 7/17/2017 2:47:19 PM | P | PASS |
|
|
Final fire sprinkler inspection for this area of work passed/complete.
|
FIR17-00118
| INSP-Final Inspection | 7/15/2017 | 7/17/2017 | 7/17/2017 2:45:25 PM | P | PASS |
|
|
Final fire alarm nispection for this area of work passed/complete.
|
BLD17-00230
| FIRE-Final Inspection | 7/17/2017 | 7/17/2017 | 7/17/2017 1:33:33 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags, final racking permit inspection for life safety complete. Final life fire safety inspection passed/complete.
|
BLD17-01790
| FIRE-Final Inspection | 7/17/2017 | 7/17/2017 | 7/17/2017 1:32:20 PM | P | PASS |
|
|
Final life fire safety inspection for racking permit passed/complete
|
BLD17-01128
| FIRE-Final Inspection | 7/17/2017 | 7/17/2017 | 7/17/2017 1:05:54 PM | P | PASS |
|
|
Fire sprinkler inspection complete, final life fire safety inspection passed/complete
|
FIR17-00114
| INSP-Final Inspection | 7/14/2017 | 7/17/2017 | 7/17/2017 12:01:40 PM | P | CANC |
|
|
Inspection of signals to neighboring buildings. Phone #: ###-#### >> Inspection requested via web by Chris Siewert Inspection cancelled from web by: Chris Siewert
|
FIR17-00017
| INSP-Sprinkler Rough-in | 7/17/2017 | 7/17/2017 | 7/17/2017 11:17:02 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads complete, approved for cover.
|
NAF17-00023
| INSP-Sprinkler Rough-in/Hydro | 7/17/2017 | 7/17/2017 | 7/17/2017 11:15:19 AM | A | PART |
|
|
Hydrostatic test for overhead fire sprinkler piping complete. Sway bracing installation does not match what is on the city approved drawings, sway bracing will need to be repaired, numerous retaining straps throughout space are not installed correctly (straps found need to be bent around truss to retain beam clamp) As-builts will need to be completed and submitted for pipe that was installed around HVAC penetrations through deck.
|
FIR17-00304
| INSP-Sprinkler Rough-in | 7/14/2017 | 7/17/2017 | 7/17/2017 10:23:38 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in area of work complete, approved for cover.
|
FIR17-00292
| INSP-Final Inspection | 7/16/2017 | 7/17/2017 | 7/17/2017 10:23:24 AM | A | PASS |
|
|
|
BLD17-00612
| FIRE-Final Inspection | 7/16/2017 | 7/17/2017 | 7/17/2017 9:59:30 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR17-00106
| INSP-Final Inspection | 7/14/2017 | 7/17/2017 | 7/17/2017 9:13:08 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR17-00281
| INSP-Final Inspection | 7/14/2017 | 7/17/2017 | 7/17/2017 9:12:51 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD17-01335
| FIRE-Final Inspection | 7/16/2017 | 7/17/2017 | 7/17/2017 8:43:20 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, commercial hood fire suppression system inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
BLD17-00215
| FIRE-Final Inspection | 7/14/2017 | 7/17/2017 | 7/17/2017 8:26:57 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers will be mounted in discussed locations. Final life fire safety inspection passed/complete.
|
FIR16-00285
| INSP-Sprinkler Rough-in | 7/14/2017 | 7/17/2017 | 7/14/2017 2:01:05 PM | A | CANC |
|
|
Contact will be Leroy Anderson please contact him 30 min prior to Inspection start... RTC - On 1st floor Prkg Garage drive thru area.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|