Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00303 INSP-Sprinkler Rough-in7/17/20177/17/20177/17/2017 3:18:11 PMPPART
Partial rough to cover inspection complete for the underground, in building riser for building stub up approved for cover, remaining underground to be installed at a later date.
FIR17-00162 INSP-Final Inspection7/17/20177/17/20177/17/2017 2:49:18 PMPCANC
Inspection for this permit to be completed at a later date.
FIR17-00080 INSP-Final Inspection7/14/20177/17/20177/17/2017 2:47:19 PMPPASS
Final fire sprinkler inspection for this area of work passed/complete.
FIR17-00118 INSP-Final Inspection7/15/20177/17/20177/17/2017 2:45:25 PMPPASS
Final fire alarm nispection for this area of work passed/complete.
BLD17-00230 FIRE-Final Inspection7/17/20177/17/20177/17/2017 1:33:33 PMPPASS
Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags, final racking permit inspection for life safety complete. Final life fire safety inspection passed/complete.
BLD17-01790 FIRE-Final Inspection7/17/20177/17/20177/17/2017 1:32:20 PMPPASS
Final life fire safety inspection for racking permit passed/complete
BLD17-01128 FIRE-Final Inspection7/17/20177/17/20177/17/2017 1:05:54 PMPPASS
Fire sprinkler inspection complete, final life fire safety inspection passed/complete
FIR17-00114 INSP-Final Inspection7/14/20177/17/20177/17/2017 12:01:40 PMPCANC
Inspection of signals to neighboring buildings. Phone #: ###-#### >> Inspection requested via web by Chris Siewert Inspection cancelled from web by: Chris Siewert
FIR17-00017 INSP-Sprinkler Rough-in7/17/20177/17/20177/17/2017 11:17:02 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping/pendant heads complete, approved for cover.
NAF17-00023 INSP-Sprinkler Rough-in/Hydro7/17/20177/17/20177/17/2017 11:15:19 AMAPART
Hydrostatic test for overhead fire sprinkler piping complete. Sway bracing installation does not match what is on the city approved drawings, sway bracing will need to be repaired, numerous retaining straps throughout space are not installed correctly (straps found need to be bent around truss to retain beam clamp) As-builts will need to be completed and submitted for pipe that was installed around HVAC penetrations through deck.
FIR17-00304 INSP-Sprinkler Rough-in7/14/20177/17/20177/17/2017 10:23:38 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in area of work complete, approved for cover.
FIR17-00292 INSP-Final Inspection7/16/20177/17/20177/17/2017 10:23:24 AMAPASS
BLD17-00612 FIRE-Final Inspection7/16/20177/17/20177/17/2017 9:59:30 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR17-00106 INSP-Final Inspection7/14/20177/17/20177/17/2017 9:13:08 AMAPASS
Final fire alarm inspection passed/complete
FIR17-00281 INSP-Final Inspection7/14/20177/17/20177/17/2017 9:12:51 AMAPASS
Final fire alarm inspection passed/complete
BLD17-01335 FIRE-Final Inspection7/16/20177/17/20177/17/2017 8:43:20 AMAPASS
No fire sprinklers, no fire alarms, commercial hood fire suppression system inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD17-00215 FIRE-Final Inspection7/14/20177/17/20177/17/2017 8:26:57 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers will be mounted in discussed locations. Final life fire safety inspection passed/complete.
FIR16-00285 INSP-Sprinkler Rough-in7/14/20177/17/20177/14/2017 2:01:05 PMACANC
Contact will be Leroy Anderson please contact him 30 min prior to Inspection start...