Inspections for the day of: Tuesday, July 2, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00263 INSP-Sprinkler Rough-in7/1/20197/2/20197/2/2019 3:00:31 PMPPART
Rough to cover inspection for overhead fire sprinkler piping/tenting above northwest stairs complete, area inspected approved for cover.

Robert Chambers is the contact. This rough-in inspection is for the 2nd floor area A. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-02371 FIRE-Final Inspection7/2/20197/2/20197/2/2019 2:43:28 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, no hood suppression system modifications, inspection tag is current for hood suppression, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

call for access- KO ###-####
FIR19-00126 INSP-Sprinkler Rough-in/Hydro7/1/20197/2/20197/2/2019 1:23:16 PMPPART
Hydrostatic test for level 1 witnessed, no pressure loss observed.

Contact Noemi Carrero ###-#### 30 min Prior to OH Hydro Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00126 INSP-Sprinkler Rough-in/Hydro7/2/20197/2/20197/2/2019 1:22:44 PMPFAIL
Basement level lost 4PSI during hydro, visible leak in corridor.
FIR19-00094 INSP-Sprinkler Rough-in/Hydro7/1/20197/2/20197/2/2019 1:20:45 PMPFAIL
Underground lost 50PSI during 2 hour hydrostatic test.

Contact Noemi Carrero ###-#### 30 Min prior to UG Hydro Insp Start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-00939 FIRE-Final Inspection7/2/20197/2/20197/2/2019 12:23:10 PMPPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Dustin Keyes
FIR19-00442 INSP-Final Inspection7/2/20197/2/20197/2/2019 12:20:54 PMPPASS
Final fire sprinkler inspection for area of work complete.
BLD17-04623 FIRE-Final Inspection7/2/20197/2/20197/2/2019 12:07:35 PMPPASS
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags, final life fire safety inspection complete.

fire/ life ; safety final Phone #: ###-#### Inspection requested via web by J.C. Murray
FIR18-00720 INSP-Final Inspection7/1/20197/2/20197/2/2019 11:27:03 AMAPASS
Final inspection for scope of work complete.

Call prior to going Phone #: 2089853303 >> Inspection requested via mobile web by Mike Kroll
FIR19-00259 INSP-Final Inspection7/1/20197/2/20197/2/2019 11:04:37 AMAPASS
Final fire alarm inspection for area of work complete.

John Phone #: ###-####
FIR19-00094 INSP-Supply line flush7/1/20197/2/20197/2/2019 10:55:53 AMADONE
Main line flush complete.

Contact Noemi Carrero ###-#### 30min prior to UG Flush insp start please Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD18-03233 FIRE-Conference7/2/20197/2/20197/2/2019 8:34:45 AMADONE
During my fire sprinkler inspection it was noticed that equipment was running, asked warehouse personnel if they were setting up equipment or if they were producing. I was informed that they were in fact producing. The fire sprinkler inspection has not been finaled for extra work, the electrical permit is in issued status as of this entry and no life fire safety inspection has been performed. I spoke with Gareth over the phone and informed him that production should not be happening until all inspections are complete and finaled for all permits associated with area of work.
FIR19-00443 INSP-Sprinkler Rough-in7/1/20197/2/20197/2/2019 8:29:29 AMAPASS
Rough in inspection for overhead fire sprinkler piping in area of work complete.

Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00232 INSP-Final Inspection6/29/20197/2/20197/1/2019 11:13:05 AMACANC
I would like an 8:00am inspection to final the fire alarm system Phone #: ###-#### >> Inspection requested via web by Heather Stier Inspection cancelled from web by: Heather Stier