FIR11-00561
| FIR-Aging Inspection | 7/26/2018 | 7/26/2018 | 8/1/2018 1:39:51 PM | | PEND |
|
|
Need site inspection request for permit final
|
FIR17-00694
| INSP-Sprinkler Rough-in | 7/26/2018 | 7/26/2018 | 7/26/2018 2:46:26 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
|
FIR17-00694
| INSP-Sprinkler Rough-in/Hydro | 7/26/2018 | 7/26/2018 | 7/26/2018 2:45:18 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauges.
Richard Clark is the contact for this overhead hydro inspection. We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00543
| INSP-Sprinkler Rough-in | 7/26/2018 | 7/26/2018 | 7/26/2018 1:29:38 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
|
FIR18-00278
| INSP-Sprinkler Rough-in | 7/26/2018 | 7/26/2018 | 7/26/2018 1:27:03 PM | P | PASS |
|
|
ROugh to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Tom Phone #: ###-####
|
FIR17-00330
| INSP-Final Inspection | 7/26/2018 | 7/26/2018 | 7/26/2018 1:26:15 PM | P | PASS |
|
|
Final inspection completed on 7/20/2017, wrong inspection request was assigned at final inspection, request was for a rough in inspection.
|
BLD18-02259
| FIRE-Final Inspection | 7/26/2018 | 7/26/2018 | 7/26/2018 1:24:21 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.
Anegla #1 Phone #: ###-####
|
BLD18-02492
| FIRE-Final Inspection | 7/25/2018 | 7/26/2018 | 7/26/2018 12:06:15 PM | A | FAIL |
|
|
Provide sticker on entry reading door to remain unlocked while building is occupied. Remove thumbturn deadbolts and provide 1 double keyed deadbolt on selected door. Provide single action door hardware as notated on city approved drawings.
Laura Phone #: ###-####
|
FIR18-00420
| INSP-Conference | 7/25/2018 | 7/26/2018 | 7/26/2018 11:55:29 AM | A | DONE |
|
|
Fire conference for standpipe location complete.
for existing standpipe. Please call Randy ###-#### first and if no answer call Steven Vaughn at ###-#### Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00464
| INSP-Sprinkler Rough-in | 7/25/2018 | 7/26/2018 | 7/26/2018 10:14:52 AM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR17-00633
| INSP-Final Inspection | 7/26/2018 | 7/26/2018 | 7/26/2018 10:13:47 AM | A | PART |
|
|
Audilble/visual notification tested, sync issue between school and addition will need to be repaired. All tamper and flow switches have been tested as well as portable buildings.
Zak Anderson - Technician Phone #: ###-#### Inspection requested via web by John Siewert
|
BLD18-00968
| FIRE-Final Inspection | 7/26/2018 | 7/26/2018 | 7/26/2018 7:25:34 AM | A | PART |
|
|
Partial final inspection for life fire safety TCO complete, fire sprinkler inspection is complete, fire extinguishers are in place with current inspection tags, fire alarm permit is still in under review status due to changes to the existing fire alarm system (FIR18-00588, fire alarms are active, if city approved drawings do not match install then corrections will be required to match city approved drawings). When fire alarm permit is finaled then life fire safety can be finaled as well. 30 day TCO authorized for life fire safety.
|