FIR18-00180
| INSP-Final Inspection | 7/29/2019 | 7/29/2019 | 7/29/2019 2:33:00 PM | P | PASS |
|
|
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.
Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR19-00233
| INSP-Sprinkler Rough-in/Hydro | 7/29/2019 | 7/29/2019 | 7/29/2019 2:30:59 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR17-00708
| INSP-Final Inspection | 7/26/2019 | 7/29/2019 | 7/29/2019 1:01:07 PM | P | FAIL |
|
|
Fire sprinkler head needs to be added corridor next to glass doors.
Cleve Phone #: ###-####
|
FIR18-00891
| INSP-Sprinkler Rough-in/Hydro | 7/26/2019 | 7/29/2019 | 7/29/2019 11:17:25 AM | A | FAIL |
|
|
Underground lost 6 psi during hydro
Reashard Howard is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00889
| INSP-Sprinkler Rough-in/Hydro | 7/26/2019 | 7/29/2019 | 7/29/2019 11:16:48 AM | A | FAIL |
|
|
Underground lost 5 psi during hydro.
Reashard Howard is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00006
| INSP-Final Inspection | 7/29/2019 | 7/29/2019 | 7/29/2019 10:52:32 AM | P | CANC |
|
|
Wrong permit was entered for inspection request, this inspection is cancelled, was not requested by this permit holder.
Matt Phone #: ###-####
|
FIR19-00518
| INSP-Sprinkler Rough-in | 7/29/2019 | 7/29/2019 | 7/29/2019 10:16:40 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
Lockbox at back of space at gas meter. Lockbox code is 0912. Phone #: ###-#### Inspection requested via web by Jonathan LaFond
|