FIR19-00306
| INSP-Sprinkler Rough-in | 7/3/2019 | 7/3/2019 | 7/3/2019 2:27:55 PM | P | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping in area of work complete, notated city approved drawings areas approved for cover.
Parcel cover job is broke up in phases. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00214
| INSP-Final Inspection | 7/2/2019 | 7/3/2019 | 7/3/2019 2:26:41 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Plans are in Marks office Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD18-04518
| FIRE-Final Inspection | 7/2/2019 | 7/3/2019 | 7/3/2019 1:47:34 PM | A | FAIL |
|
|
Need FIR permits for fire sprinkler and fire alarm finaled before life fire safety inspection can be performed.
Ron Phone #: ###-####
|
FIR19-00232
| INSP-Final Inspection | 7/1/2019 | 7/3/2019 | 7/3/2019 1:19:01 PM | P | FAIL |
|
|
Relocate horn/strobe in mens restroom on level 1 to correct coverage, relocate horn strobe in womans restroom basement level. Provide coverage at west en of basement level corridor. Lower horn strobe in southeast level 1 room. Provide monitoring for PIV. Provide coverage for room off of southeast basement classroom, area is marked storage, room is not a storage room. No device testing was done, need corrections made before sounding alarms.
Final inspection with Shilo Sprinklers ; Crane Alarm Please call Eric ###-#### with Crane Alarm to confirm actual time. Requesting for 11:00 am inspection. Phone #: ###-#### Inspection requested via web by Heather Stier
|
FIR18-00180
| INSP-Final Inspection | 7/2/2019 | 7/3/2019 | 7/3/2019 1:12:40 PM | A | FAIL |
|
|
Notated city approved drawings areas that need to be corrected. Submit plan modification to have sway bracing removed from city approved drawings.
Please call Dillion Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR19-00126
| INSP-Sprinkler Rough-in/Hydro | 7/2/2019 | 7/3/2019 | 7/3/2019 1:08:22 PM | A | DONE |
|
|
Hydrostatic test for basement level witnessed, no pressure loss observed.
Contact Noemi Carrero ###-#### 30 min prior to Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00094
| INSP-Sprinkler Rough-in/Hydro | 7/2/2019 | 7/3/2019 | 7/3/2019 1:07:44 PM | A | FAIL |
|
|
Underground supply lost 10PSI during hydro test.
Contact Noemi Carrero - ###-#### 30 min prior to Hydro insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00258
| INSP-Sprinkler Rough-in/Hydro | 7/2/2019 | 7/3/2019 | 7/3/2019 11:59:43 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, np pressure loss observed.
Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
|
FIR18-00834
| INSP-Sprinkler Rough-in | 7/3/2019 | 7/3/2019 | 7/3/2019 9:29:54 AM | P | PASS |
|
|
Rough to cover inspection for remaining underground supply complete, approved for cover.
Bryan Collins is the contact. He has already been in contact with Jim Page who has agreed to have this done today, he just needed the paper trail. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00404
| INSP-Sprinkler Rough-in | 7/3/2019 | 7/3/2019 | 7/3/2019 9:14:46 AM | A | PASS |
|
|
Rough to cover ispection for overhead fire sprinkler piping complete, all tenting in place at time of insulation, approved for cover.
|
FIR19-00404
| INSP-Sprinkler Rough-in/Hydro | 7/2/2019 | 7/3/2019 | 7/3/2019 9:13:20 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed at 150PSI, above what is required by 13D, no pressure loss observed.
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-02797
| FIRE-Conference | 7/2/2019 | 7/3/2019 | 7/3/2019 8:25:34 AM | A | DONE |
|
|
Fire conference is complete, items that are not associated with construction are not to be stored in the warehouse. As of this entry the racking permit has not been inspected, the fire alarms cannot be completed due to the fire alarm permit being under review and no life fire safety inspection has been performed. I spoke with Ron Johnson with Boise Fire Department and he agrees with my decision.
call ahead // Mike Phone #: ###-####
|
FIR19-00112
| INSP-Final Inspection | 6/26/2019 | 7/3/2019 | 7/3/2019 8:04:51 AM | A | CANC |
|
|
Inspection request will be rescheduled per conversation with point of contact, the 7AM inspection time was not cooodinated, need a minimum of a 24 hour notice with my approval as well as my supervisors approval for inspections outside of my normal working hours. Next inspection needs to be coordinated or it will result in a fail, this request is cancelled.
Requesting inspection at 7AM - John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
|