Inspections for the day of: Thursday, July 30, 2020.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00458 INSP-Sprinkler Rough-in7/30/20207/30/20207/30/2020 4:15:00 PMPPASS
Rough to cover inspection for area of work is complete, cover is approved. Plywood install above suspended ceiling is fire treated per product stamp, upright coverage not required.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00453 INSP-Sprinkler Rough-in7/29/20207/30/20207/30/2020 12:49:20 PMPFAIL
2 90's have been added on the 2 inch piping supplying branchlines in the rooms (2 per line, a total of 10 nhave been added), 90's need to be shown on plans and calcs checked to make sure 90's can remain in place. Provide hangers in areas where hangers on branch lines are overspaced. Provided branch line restraints as shown on city approved drawings cover for area of work is not approved..

Contact Andrew Larson ###-#### 30 min prior to RTC Insp start please. Andrew is requesting a 12PM inspection time if at all possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD20-01384 FIRE-Final Inspection7/29/20207/30/20207/30/2020 12:14:21 PMAPASS
No fire sprinklers, no fire alarm modifications, fire extinguisher is placed with a current ninspection tag. Final life fire safety inspection complete, signature provided on permit sign off card.

Please call me 30 mins ahead of time, so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
BLD20-01322 FIRE-Final Inspection7/29/20207/30/20207/30/2020 11:36:34 AMAFAIL
Need fire alarm inspection to be scheduled and performed before life fire safety can be complete, point of contact for this inspection has been notified.

screened // Mike Phone #: ###-####
BLD20-00356 FIRE-Final Inspection7/29/20207/30/20207/30/2020 11:35:18 AMAPART
Per conversation with Joe Bruce, Fire Section Supervisor, racking permit needs to be finaled before life fire safety for this permit can be signed off, refer to notes entered on 02JULY2020.

Rod- */Screened*/ Phone #: ###-####
BLD19-03269 FIRE-Final Inspection7/29/20207/30/20207/30/2020 11:32:48 AMACANC
Life safety signed off on 02JULY2020 for this permit, this request is cancelled.

Rod- */Screened*/ Phone #: ###-####
FIR20-00421 INSP-Final Inspection7/29/20207/30/20207/30/2020 10:01:33 AMAPASS
Final fire sprinkler inspection for scope of work is complete.

Phone #: ###-#### Inspection requested via web by Brian Carlisle
FIR20-00421 INSP-Sprinkler Rough-in7/29/20207/30/20207/30/2020 10:01:00 AMAPASS
Rough in inspection for scope of work is complete.

Phone #: ###-#### Inspection requested via web by Brian Carlisle
FIR20-00139 INSP-Final Inspection7/29/20207/30/20207/30/2020 9:27:22 AMACANC
Inspection ws suppose to be scheduled for 31JULY2020 per conversation with point of contact, this request is cancelled.

Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
BLD20-02507 FIRE-Final Inspection7/29/20207/30/20207/30/2020 9:26:20 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Addressing and signage inside door reading "Door to remain unlocked while building is occupied" to be placed before builidng final. Signature card not available at time of inspection.

Screened- Jill Phone #: ###-####
BLD19-01828 FIRE-Final Inspection7/30/20207/30/20207/30/2020 8:56:27 AMAPART
Fire sprinkler inspection is complete, fire alarm inspection is complete but city approved drawings need updated showing required cahnges, fire extinguishers are placed with current inspection tags, knox box is located by south stairwell entry, fire emergency guide has been reviewed and approved by Joe Bruce, fire section supervisor and emergency guide will be provided too tenants. 14 day TCO authorized for life fire safety, final sign off is contigent upon fire alarm drawings getting updated and the associated permit being finaled. Sigantures provided on permit sign off card.
FIR19-00681 INSP-Final Inspection7/29/20207/30/20207/30/2020 8:50:43 AMAPART
Fire alarm is compliamt with NFPA72, horns needed to be removed due too exceeding 110db. Plans are too be updated showing changes, permit can be finaled after cahnges are approved. 14 day TCO authorized pending fire alarm drawing update.

Coordinated with FA techician for 8AM, Brandon ###-####