BLD19-02490
| FIRE-Final Inspection | 7/9/2019 | 7/9/2019 | 7/9/2019 2:20:58 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
Monica Phone #: ###-####
|
BLD19-00475
| FIRE-Final Inspection | 7/9/2019 | 7/9/2019 | 7/9/2019 1:00:49 PM | P | CANC |
|
|
As of these notes the permit status is under review for floor plan modifications, floor plan needs to match city approved drawings for life fire safety inspection, need permit to be in issued status for life fire safety inspection to be completed, this request is cancelled and a new inspection will need to be requested when permit is back in issued status.
Armodo Phone #: ###-####
|
FIR19-00233
| INSP-Sprinkler Rough-in | 7/8/2019 | 7/9/2019 | 7/9/2019 11:18:04 AM | A | PASS |
|
|
Rough in inspection for interior sprinkler piping complete, no cover for interior piping, scope of work is for core and shell protection only. Rough to cover inspection for overhead fire sprinkler piping in exterior canopies complete, exterior canopies approved for cover.
Adam Phone #: ###-####
|
FIR19-00465
| INSP-Sprinkler Rough-in | 7/8/2019 | 7/9/2019 | 7/9/2019 8:24:35 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piiping complete, approved for cover. Notated city approved drawings in two areas, one has a head that needs relocated to the next tile to cover shadow area and an area that has 2 heads less than 6 foot apart. Will verify corrections at final inspection.
Phone #: ###-#### Inspection requested via web by Sam Ball
|