FIR17-00633
| INSP-Final Inspection | 8/16/2018 | 8/17/2018 | 8/17/2018 2:53:03 PM | A | PASS |
|
|
Final fire alarm inspection complete per Lee Meredith.
Phone #: ###-#### Inspection requested via web by John Siewert
|
BLD18-00943
| FIRE-Final Inspection | 8/14/2018 | 8/17/2018 | 8/17/2018 2:42:29 PM | P | PART |
|
|
Final life fire safety inspection for remodeled parking lot complete.
This is for the parking lot only Phone #: ###-#### Inspection requested via web by Russell Valline
|
FIR18-00511
| INSP-Sprinkler Rough-in | 8/17/2018 | 8/17/2018 | 8/17/2018 2:28:53 PM | P | PART |
|
|
Rough in inspection complete for overhead fire sprinkler piping, sway bracing will need to be adjusted so the 4 ways are not connected together as discussed. Piping for pendant heads to be inspected at a later date.
|
FIR18-00511
| INSP-Sprinkler Rough-in/Hydro | 8/16/2018 | 8/17/2018 | 8/17/2018 2:17:07 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.
Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00544
| INSP-Sprinkler Rough-in | 8/17/2018 | 8/17/2018 | 8/17/2018 1:39:50 PM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00545
| INSP-Sprinkler Rough-in | 8/17/2018 | 8/17/2018 | 8/17/2018 1:39:14 PM | P | CANC |
|
|
Undergound not ready for inspection, this request is cancelled and a new inspection will be rescheduled for when the underground supply is complete.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00621
| INSP-Final Inspection | 8/16/2018 | 8/17/2018 | 8/17/2018 1:37:35 PM | P | PASS |
|
|
Final inspection for demo work complete.
Jason Phone #: ###-####
|
FIR18-00298
| INSP-Sprinkler Rough-in | 8/16/2018 | 8/17/2018 | 8/17/2018 11:21:13 AM | A | FAIL |
|
|
Phone number provided was not the correct point of contact, building is locked and secure with no access, inspection will need to be rescheduled.
Contact Brad Westbrook ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00448
| INSP-Final Inspection | 8/15/2018 | 8/17/2018 | 8/17/2018 11:17:52 AM | A | PASS |
|
|
Previously noted items have been completed, final fire sprinkler inspection complete.
Please call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD17-03128
| FIRE-Final Inspection | 8/16/2018 | 8/17/2018 | 8/17/2018 11:03:47 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are place with current inspection tags, building does have a knox box installed by main entry, addressing on permit needs to be changed to the correct property address before BLD final. Final life fire safety inspection complete.
Daryl Phone #: ###-####
|
FIR18-00478
| INSP-Sprinkler Rough-in | 8/16/2018 | 8/17/2018 | 8/17/2018 10:39:05 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping in area of work complete, notated city approved drawings with green highlighter/red ink areas approved for cover.
Partial cover . Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD18-01771
| FIRE-Final Inspection | 8/16/2018 | 8/17/2018 | 8/17/2018 9:58:47 AM | A | FAIL |
|
|
Fire sprinkler head in lobby og tenant space is to far off of wall, either fire sprinkler head needs relocated or one will need to be added.
Doug Phone #: ###-####
|
FIR18-00119
| INSP-Sprinkler Rough-in | 8/16/2018 | 8/17/2018 | 8/17/2018 9:42:55 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
Contact Brad Westbrook ###-#### - 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00542
| INSP-Final Inspection | 8/16/2018 | 8/17/2018 | 8/17/2018 9:18:31 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Please call ###-####, Thanks, Jim Phone #: ###-#### Inspection requested via web by Jim Shilton
|
FIR18-00430
| INSP-Final Inspection | 8/16/2018 | 8/17/2018 | 8/17/2018 8:30:12 AM | A | PASS |
|
|
Final fire alarm inspection complete.
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00408
| INSP-Sprinkler Rough-in | 8/16/2018 | 8/17/2018 | 8/17/2018 8:29:12 AM | A | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
Bryan Collins is the contact for this Underground RTC Inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|