Inspections for the day of: Friday, August 2, 2019.
Number of inspections: 27
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-00914 FIRE-Final Inspection8/2/20198/2/20198/2/2019 3:35:12 PMPPASS
No fire alarms, no fire sprinklers, hood suppression system inspection complete, fire exitnguishers are placed with current inspection tags, restroom door configuration is existing with no changes. Final life fire safety inspection for area of work complete.
FIR19-00532 INSP-Final Inspection8/1/20198/2/20198/2/2019 3:33:23 PMPPASS
Final hood suppression system inspection complete.

Final inspection for a new buckeye fire suppression system. Superintendant says that 2pm would be preferable. let me know what works best for you! Thank you! Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR18-00834 INSP-Supply line flush8/2/20198/2/20198/2/2019 3:32:54 PMPDONE
Underground main line flush complete.

Todd Ketterling is the contact. Stacey with Suez is aware of this inspection, he and Todd are working out a specific time to meet there. Please contact them for that time. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-01548 FIRE-Final Inspection7/31/20198/2/20198/2/2019 1:54:37 PMPPASS
No fire sprinklers, no fire alarms, fire exitinguisher will be placed in discussed location and will be tagged with a current inspection tag. Final life fire safety inspection for area of work complete.

Elise (parcel owner and sife to Sean)-please call 30 minutes prior for access Phone #: ###-####
FIR19-00530 INSP-Final Inspection8/2/20198/2/20198/2/2019 12:28:50 PMAPASS
Final fire alarm inspection for scope of work complete.
BLD19-02216 FIRE-Final Inspection8/2/20198/2/20198/2/2019 12:26:43 PMPPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, outlets for VR units shunt during fire alarm activation, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
FIR19-00567 INSP-Final Inspection8/2/20198/2/20198/2/2019 12:24:43 PMPPASS
Previously noted items have been corrected, final fire alarm inspection for scope of work complete.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD19-00936 FIRE-Final Inspection8/2/20198/2/20198/2/2019 11:43:03 AMPPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags, slide bolts on main entry were removed at time of inspection. Final life fire safety inspection for scope of work complete.

Ted Phone #: ###-####
BLD19-00165 FIRE-Final Inspection8/2/20198/2/20198/2/2019 11:41:52 AMPPASS
Final life fire safety inspection for scope of work complete.

Joel Phone #: ###-####
FIR19-00563 INSP-Final Inspection8/1/20198/2/20198/2/2019 11:38:52 AMAPASS
Final fire sprinkler inspection for scope of work complete.

Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
BLD19-02865 FIRE-Final Inspection8/1/20198/2/20198/2/2019 10:34:18 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.

Laura Phone #: ###-####
FIR19-00555 INSP-Final Inspection8/2/20198/2/20198/2/2019 10:14:17 AMAFAIL
Fire alarm sounded for approximately half a second then went silent, this happened to the whole building, could not reset panel even after fire alarm was acknowledged.
FIR19-00536 INSP-Supply line flush8/2/20198/2/20198/2/2019 10:03:42 AMADONE
Underground main line flush complete.
BLD19-02376 FIRE-Final Inspection8/1/20198/2/20198/2/2019 9:23:36 AMAFAIL

Fire alarms did not pass inspection, life fire safety inspection was stopped at fire alarm failure, as of this entry the whole building did not have fire alarm notification.

Please call me to schedule inspection. i need to let my subcontractor know when you will be on site. Thank you Phone #: ###-#### Inspection requested via web by Greg Hedin
FIR19-00548 INSP-Final Inspection8/1/20198/2/20198/2/2019 9:21:50 AMAPASS
Final fire sprinkler inspection for area of work complete.

Adam Phone #: ###-####
FIR19-00548 INSP-Sprinkler Rough-in8/1/20198/2/20198/2/2019 9:21:09 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Adam Phone #: ###-####
BLD19-00278 FIRE-Final Inspection7/30/20198/2/20198/2/2019 9:20:27 AMADONE
East side battered wall filled with insulation, this is the last battered wall for inspection, approved for cover, as-builts for fire sprinklers needs to show the deleted fire sprinklers where insualtion was placed in the battered walls.

Battered wall insulation for east stairwell and building entrance B117. Phone #: ###-#### Inspection requested via web by Corey Hockersmith
BLD19-02376 FIRE-Sprinkler Rough-in8/1/20198/2/20198/2/2019 7:56:49 AMACANC

Fire sprinkler inspections need to happen under FIR permit associated with the fire sprinklers, this request is cancelled.

Please call me to schedule inspection. i need to let my subcontractor know when you will be on site. Thank you Phone #: ###-#### Inspection requested via web by Greg Hedin
BLD19-00416 FIRE-Final Inspection8/2/20198/2/20198/2/2019 7:55:33 AMAPART
Fire sprinkler inspection is complete, fire alarm is partially complete (see notes entered under FIR19-00529), fire extinguishers are placed with current inspection tags. Partial final for life fire safety complete, TCO authorized for life fire safety for 90 days contingent on main fire alarm head unti replacement inspections being finaled.
FIR19-00278 INSP-Final Inspection8/2/20198/2/20198/2/2019 7:52:31 AMAPASS
Final fire sprinkler inspection for area of work complete.
FIR19-00242 INSP-Final Inspection7/29/20198/2/20198/2/2019 7:46:37 AMPCANC
Cnacelled per conversation with point of contact, not ready for final inspection, will be rescheduled for a later date.

Please make last of day inspection, we can''t set off anything until 4:00 on. Phone #: ###-#### Inspection requested via web by Kristin Dolan
BLD19-02376 FIRE-Alarm Testing8/1/20198/2/20198/2/2019 7:36:47 AMACANC
Fire alarm testing needs to be done under FIR permit for fire alarms, this request is cancelled.


Please call me to schedule inspection. i need to let my subcontractor know when you will be on site. Thank you Phone #: ###-#### Inspection requested via web by Greg Hedin
FIR19-00529 INSP-Final Inspection8/1/20198/2/20198/2/2019 7:36:10 AMAPART
Partial final inspwection for fire alarms complete, main head unit fire panel replacement permit is still active, this permit will have to remain in issued status until head unit permit is comlpeted and finaled.

Please Contact Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
FIR19-00426 INSP-Sprinkler Rough-in/Hydro8/1/20198/2/20198/2/2019 7:03:57 AMACANC
Contact Keith Orahood ###-#### 30 Min prior to RTC/Hydro start please

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
BLD19-02771 FIRE-Final Inspection7/30/20198/2/20198/2/2019 12:00:00 AMACANC
Martha Phone #: ###-####
FIR19-00555 INSP-Final Inspection8/1/20198/2/20198/2/2019 12:00:00 AMACANC
Damin Phone #: ###-####
BLD19-00142 FIRE-Final Inspection7/29/20198/2/20198/2/2019 12:00:00 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Doug Storey