BLD19-02553
| FIRE-Final Inspection | 8/22/2019 | 8/22/2019 | 8/22/2019 3:29:29 PM | P | PASS |
|
|
Previously noted items have been corrected, storage has been lowered and is now code compliant. No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
Jason Phone #: ###-####
|
FIR19-00507
| INSP-Sprinkler Rough-in | 8/22/2019 | 8/22/2019 | 8/22/2019 3:27:06 PM | P | PASS |
|
|
Previously noted item for insulation on sprinkler head has been corrected, approved for cover.
Charles Lamb is the contact. This inspection has already happened once, it just didn''t pass because of insulation hanging on the heads. The contact is not planning on being there, but please call him if you need him there. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00582
| INSP-Sprinkler Rough-in | 8/22/2019 | 8/22/2019 | 8/22/2019 3:25:46 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
FIR18-00633
| INSP-Conference | 8/22/2019 | 8/22/2019 | 8/22/2019 1:41:49 PM | P | DONE |
|
|
Fire sprinkler conference complete, discussed possible issue before TCO, items noted are already on the job site foreman list, no major issues noted.
|
FIR18-00633
| INSP-Final Inspection | 8/20/2019 | 8/22/2019 | 8/22/2019 1:38:59 PM | P | CANC |
|
|
Request was for a conference to discuss final inspection items, this request is cancelled.
Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-04283
| FIRE-Final Inspection | 8/21/2019 | 8/22/2019 | 8/22/2019 12:22:56 PM | A | FAIL |
|
|
FIR permit for fire alarm needs to be finaled before life fire safety can be completed.
as late as possible // Phone #: 2082588303 >> Inspection requested via mobile web by Marvin Bergloff
|
FIR19-00261
| INSP-Sprinkler Rough-in/Hydro | 8/21/2019 | 8/22/2019 | 8/22/2019 10:41:12 AM | A | PART |
|
|
Most of the previously noteditems have been corrected, all arras except for the main entry approved for cover, main entry has CPVC encapsulated with foam spray in insulation, gap needs to be clear between pipe and sheetrock for freeze protection. Insulators need to provide documentation showing that the spray in foam is compatible with contacting CPVC pipe. Main entry is not approved for cover.
Ron Phone #: ###-####
|
FIR19-00558
| INSP-Sprinkler Rough-in | 8/21/2019 | 8/22/2019 | 8/22/2019 10:07:13 AM | A | PART |
|
|
Rough to cover ispection for overhead fire sprinkler piping located above hardlids in area of work complete, hardlids approved for cover.
John Phone #: ###-####
|
BLD19-00871
| FIRE-Final Inspection | 8/19/2019 | 8/22/2019 | 8/22/2019 7:39:18 AM | A | PART |
|
|
Fire alarm inspection for phase 1 complete, fire sprinkler inspection for phase 1 is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for phase 1 complete.
Tom Phone #: ###-####
|
FIR19-00441
| INSP-Final Inspection | 8/22/2019 | 8/22/2019 | 8/22/2019 7:36:57 AM | A | PART |
|
|
Final inspection for area of work complete. Project is being worked in phases, coverage is complete for phases but annunciator by main entry is inoperable, annunciator will need to be operational before permit can be finaled.
|
FIR19-00441
| INSP-Alarm Testing | 8/20/2019 | 8/22/2019 | 8/22/2019 7:35:09 AM | A | DONE |
|
|
Fire alarm testing for area of work is complete.
7 am inspection Phone #: ###-#### Inspection requested via web by Brian Richard
|
MIS19-00259
| FIR-Conference | 8/22/2019 | 8/22/2019 | 8/22/2019 12:00:00 AM | P | CANC |
|
|
working without permit Phone #: ###-#### CANCEL INSPECTION PER BRANDON THE INSPECTOR
|