Inspections for the day of: Thursday, August 22, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-02553 FIRE-Final Inspection8/22/20198/22/20198/22/2019 3:29:29 PMPPASS
Previously noted items have been corrected, storage has been lowered and is now code compliant. No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.

Jason Phone #: ###-####
FIR19-00507 INSP-Sprinkler Rough-in8/22/20198/22/20198/22/2019 3:27:06 PMPPASS
Previously noted item for insulation on sprinkler head has been corrected, approved for cover.

Charles Lamb is the contact. This inspection has already happened once, it just didn''t pass because of insulation hanging on the heads. The contact is not planning on being there, but please call him if you need him there. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00582 INSP-Sprinkler Rough-in8/22/20198/22/20198/22/2019 3:25:46 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
FIR18-00633 INSP-Conference8/22/20198/22/20198/22/2019 1:41:49 PMPDONE
Fire sprinkler conference complete, discussed possible issue before TCO, items noted are already on the job site foreman list, no major issues noted.
FIR18-00633 INSP-Final Inspection8/20/20198/22/20198/22/2019 1:38:59 PMPCANC
Request was for a conference to discuss final inspection items, this request is cancelled.

Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-04283 FIRE-Final Inspection8/21/20198/22/20198/22/2019 12:22:56 PMAFAIL
FIR permit for fire alarm needs to be finaled before life fire safety can be completed.

as late as possible // Phone #: 2082588303 >> Inspection requested via mobile web by Marvin Bergloff
FIR19-00261 INSP-Sprinkler Rough-in/Hydro8/21/20198/22/20198/22/2019 10:41:12 AMAPART
Most of the previously noteditems have been corrected, all arras except for the main entry approved for cover, main entry has CPVC encapsulated with foam spray in insulation, gap needs to be clear between pipe and sheetrock for freeze protection. Insulators need to provide documentation showing that the spray in foam is compatible with contacting CPVC pipe. Main entry is not approved for cover.

Ron Phone #: ###-####
FIR19-00558 INSP-Sprinkler Rough-in8/21/20198/22/20198/22/2019 10:07:13 AMAPART
Rough to cover ispection for overhead fire sprinkler piping located above hardlids in area of work complete, hardlids approved for cover.

John Phone #: ###-####
BLD19-00871 FIRE-Final Inspection8/19/20198/22/20198/22/2019 7:39:18 AMAPART
Fire alarm inspection for phase 1 complete, fire sprinkler inspection for phase 1 is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for phase 1 complete.

Tom Phone #: ###-####
FIR19-00441 INSP-Final Inspection8/22/20198/22/20198/22/2019 7:36:57 AMAPART
Final inspection for area of work complete. Project is being worked in phases, coverage is complete for phases but annunciator by main entry is inoperable, annunciator will need to be operational before permit can be finaled.

FIR19-00441 INSP-Alarm Testing8/20/20198/22/20198/22/2019 7:35:09 AMADONE
Fire alarm testing for area of work is complete.

7 am inspection Phone #: ###-#### Inspection requested via web by Brian Richard
MIS19-00259 FIR-Conference8/22/20198/22/20198/22/2019 12:00:00 AMPCANC
working without permit Phone #: ###-#### CANCEL INSPECTION PER BRANDON THE INSPECTOR