Inspections for the day of: Friday, August 23, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00540 INSP-Sprinkler Rough-in8/22/20198/23/20198/23/2019 3:08:33 PMAFAIL
Installation does not match city approved drawings, most changes are on level 2 and remote area 4, no cover is approved.



Reashard Howard is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00276 INSP-Final Inspection8/22/20198/23/20198/23/2019 3:07:51 PMAPASS
Final fire sprinkler inspection for area of work complete.

Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR19-00276 INSP-Sprinkler Rough-in8/23/20198/23/20198/23/2019 3:07:14 PMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
BLD19-00575 FIRE-Final Inspection8/23/20198/23/20198/23/2019 1:06:19 PMPPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Travis Knutson
FIR19-00426 INSP-Final Inspection8/22/20198/23/20198/23/2019 1:02:10 PMPFAIL
Replace 2 heads that were painted. Head next to southeast exit is blocked by communication wires. Remove masking on sprinkler head.

Contact Andrew Larson - ###-#### 30 Min prior to Final Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00260 INSP-Final Inspection8/22/20198/23/20198/23/2019 12:32:38 PMAPASS
Final fire sprinkler inspection for scope of work complete.

Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR19-00260 INSP-Sprinkler Rough-in8/23/20198/23/20198/23/2019 12:32:10 PMAPASS
Rough in inspection for demo work complete.
FIR19-00168 INSP-Sprinkler Rough-in8/22/20198/23/20198/23/2019 10:35:48 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
BLD18-04283 FIRE-Final Inspection8/23/20198/23/20198/23/2019 9:29:40 AMPPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, no hood suppression, fire extinguishers are placed with current inspection tags, access control has free egress, does not need to be interfaced with fire alarm system, knox box will be placed in discussed location. Notated one exit sign was but one was visible within 100 feet. Final life fire safety inspection for area of work complete.

Marvin Phone #: ###-####
FIR19-00476 INSP-Final Inspection8/23/20198/23/20198/23/2019 9:25:58 AMPPASS
Final fire alarm inspection complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD18-04283 FIRE-Alarm Testing8/23/20198/23/20198/23/2019 9:25:28 AMPCANC
Phone #: ###-#### Inspection requested via web by Kevin Honeycutt
FIR19-00237 INSP-Final Inspection8/22/20198/23/20198/23/2019 8:23:54 AMACANC
Contact Tyler Loomis ###-#### 30 Min prior to Final Insp start please

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank