Inspections for the day of: Friday, August 24, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02737 FIRE-Final Inspection8/24/20188/24/20188/24/2018 1:44:17 PMPFAIL
Phone number provided for point of contact is not an active phone number, message says number is disconnected, inspection request will need to rescheduled.

Sean-Mcalvain subed Sean to do work Phone #: ###-####
FIR18-00159 INSP-Sprinkler Rough-in8/23/20188/24/20188/24/2018 1:16:33 PMPPART
Rough to cover inspection for overhead fire sprinkler piping located on north wing level 1 complete excluding corridor heads, approved for cover, corridor cover is not approved until finish pendant heads are installed and inspected.

All Rooms on North Wing. First floor I believe.
Leon Taylor should be on site. Phone #: ###-#### Inspection requested via web by Randy Knutson
BLD18-01600 FIRE-Final Inspection8/24/20188/24/20188/24/2018 1:15:13 PMPPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection complete.

Matt Phone #: ###-####
FIR18-00651 INSP-Final Inspection8/24/20188/24/20188/24/2018 1:14:02 PMPPASS
Final fire sprinkler inspection complete.

John Phone #: ###-####
FIR18-00546 INSP-Sprinkler Rough-in/Hydro8/23/20188/24/20188/24/2018 11:34:27 AMPDONE
Hydrostatic test for newly installed CPVC overhead fire sprinkler piping witnessed, no pressure loss observed at contractor provided gauge.

Phone #: ###-#### Inspection requested via web by Connie Danes
FIR18-00320 INSP-Final Inspection8/24/20188/24/20188/24/2018 10:43:40 AMPCANC
Cancelled per conversation with point of contact, inspection will be rescheduled for a later date.

Dave Phone #: ###-####Dave Phone #: ###-####
FIR18-00666 INSP-Final Inspection8/24/20188/24/20188/24/2018 10:43:19 AMPCANC
Cancelled per conversation with point of contact, inspection will be rescheduled for a later date.

Dave Phone #: ###-####
FIR18-00364 INSP-Sprinkler Rough-in8/23/20188/24/20188/24/2018 9:08:11 AMAPASS
Rough to cover inspection formoverhead fire sprinkler piping in area of work complete, approved for cover.

Don Phone #: ###-####