BLD18-03442
| FIRE-Conference | 8/27/2019 | 8/27/2019 | 8/27/2019 4:13:54 PM | P | DONE |
|
|
Fire conference complete, discussed exit sign locations that would work for the low ceiling. Discussed needed items for life fire safety.
|
BLD18-03442
| FIRE-Final Inspection | 8/27/2019 | 8/27/2019 | 8/27/2019 4:12:52 PM | P | CANC |
|
|
Request was for a conference, not a final inspection. This request is cancelled.
Kelly Phone #: ###-####
|
BLD19-00703
| FIRE-Final Inspection | 8/26/2019 | 8/27/2019 | 8/27/2019 2:47:56 PM | P | CANC |
|
|
FIR permit for fire alarm \s needs to be finaled before life fire safety inspection can be completed, last fire alarm inspection resulted in a fail, this request is cancelled.
Mike Phone #: ###-####
|
BLD17-02261
| FIRE-Conference | 8/27/2019 | 8/27/2019 | 8/27/2019 2:45:19 PM | P | DONE |
|
|
Fire conference complete, discussed options for roof top access ladder arrangement.
Per Dave H Phone #: ###-####
|
FIR19-00004
| INSP-Final Inspection | 8/27/2019 | 8/27/2019 | 8/27/2019 1:30:53 PM | P | PASS |
|
|
Final fire sprinkler inspection complete, irrigation isolation not required on flow switch activation, irrigation on seperate non-potable water line and not part of the treated domestic water system.
Call before heading out, thank you Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-01651
| FIRE-Final Inspection | 8/27/2019 | 8/27/2019 | 8/27/2019 11:25:17 AM | P | PASS |
|
|
Compliant door hardware has been installed on pocket doors, final life fire safety inspection is complete.
Jim,
The pulls are on the pocket doors. I will text you and Tony a picture.
Thanks,
Todd Phone #: ###-#### Inspection requested via web by Todd Kurns
|
BLD19-01546
| FIRE-Final Inspection | 8/26/2019 | 8/27/2019 | 8/27/2019 11:22:48 AM | A | PASS |
|
|
Previously noted item has been corrected, final life fire safety inspection for scope of work complete.
call rob Phone #: ###-#### Inspection requested via web by J.C. Murray
|
FIR18-00601
| INSP-Supply line flush | 8/26/2019 | 8/27/2019 | 8/27/2019 10:36:48 AM | A | DONE |
|
|
Underground main line flush after pipe break complete.
Jon Beazer is the contact. Stacey with Suez has been contacted and is planning on this flush being around 9:30 AM. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00740
| FIRE-Final Inspection | 8/26/2019 | 8/27/2019 | 8/27/2019 10:17:51 AM | A | PASS |
|
|
Previously noted items have been corrected, fire sprinkler ispections are complete, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
TOM Phone #: ###-####
|
FIR18-00601
| INSP-Final Inspection | 8/27/2019 | 8/27/2019 | 8/27/2019 9:28:00 AM | P | CANC |
|
|
Jon Beazer is the contact. The final was done this morning, this is just the paper trail. Call Jon Beazer to answer any questions. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR19-00555
| INSP-Final Inspection | 8/26/2019 | 8/27/2019 | 8/27/2019 8:44:37 AM | A | FAIL |
|
|
Network interface between 8th street fire panel and Chase fire panel does not communicate on intial fire alarm, only time panels communicate on general fire is during a second fire alarm while 8th street fire panel is in alarm. Priority 2 alarm reports to chase panel but only have audio notification, no visual notification, troublshoot and repair to be code compliant.
firre alarmBrian Phone #: ###-####
|
FIR19-00237
| INSP-Final Inspection | 8/23/2019 | 8/27/2019 | 8/27/2019 8:14:31 AM | A | CANC |
|
|
Contact Tyler Loomis ###-#### 30 min prior to Final Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|