Inspections for the day of: Friday, August 30, 2019.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00633 INSP-Final Inspection8/29/20198/30/20198/30/2019 1:52:01 PMACANC
Could not test fire alarm associated devices, fire alarms not ready, this requst is cancelled per conversation with point of contact.

Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00360 INSP-Final Inspection8/30/20198/30/20198/30/2019 1:51:18 PMPCANC
Cancelled per conversation with point of contact, will be rescheduled for a later date.

Tre Phone #: ###-####
BLD17-02262 FIRE-Final Inspection8/29/20198/30/20198/30/2019 12:22:23 PMAFAIL
Project not ready for life fire safety inspection, no items inspected.

Tony Phone #: ###-####
BLD17-02261 FIRE-Final Inspection8/29/20198/30/20198/30/2019 12:22:03 PMAFAIL
Project not ready for life fire safety inspection, no items inspected.

Tony Phone #: ###-####
BLD19-03133 FIRE-Final Inspection8/26/20198/30/20198/30/2019 11:59:08 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with a current inspection tag, noted that the space has round type door harware thoughout, did not test exit signs.



Call half hour before to meet // Chris Phone #: ###-####
FIR19-00006 INSP-Final Inspection8/29/20198/30/20198/30/2019 11:57:05 AMAFAIL
Head in lower bedroom is 10ft 6 off of wall, needs to be 10 foot or less. Basement pantry is not a pantry, discussed room with Mark Stumbaugh, fire sprinkler plan reviewer and he agrees that room needs a sprinkler head. Irrigation needs to be active to test irrigation shutdown when flow switch activates, no flow test performed.



Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00593 INSP-Sprinkler Rough-in/Hydro8/30/20198/30/20198/30/2019 10:08:20 AMAPART
Rough in inspection complete, no tenting in place at time of inspection, cover is approved for piping between conditioned spaces, piping in attic spaces that requires tenting is not approved for cover.
FIR19-00593 INSP-Sprinkler Rough-in/Hydro8/29/20198/30/20198/30/2019 10:06:33 AMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00554 INSP-Sprinkler Rough-in8/30/20198/30/20198/30/2019 9:50:36 AMAFAIL
Cover is not approved, tenting not installed correctly.
FIR19-00554 INSP-Sprinkler Rough-in/Hydro8/29/20198/30/20198/30/2019 9:46:59 AMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00578 INSP-Sprinkler Rough-in8/30/20198/30/20198/30/2019 9:12:46 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
FIR19-00578 INSP-Sprinkler Rough-in8/29/20198/30/20198/30/2019 9:00:24 AMAFAIL
Area of work is locked with no access, called point of contact, was informed that someone should be at space in ten minutes, waited for 15 minutes, still no access, proceeded to next inspection.

After 8:00am Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-02469 FIRE-Final Inspection8/30/20198/30/20198/30/2019 8:51:10 AMAPASS
Previously noted items have been corrected, fire sprinkler ispection is complete, fire alarm inspection is complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, card has been signed for fire sprinkler, fire alarm and life safety.

Inspection requested via web by Elliott Sheffield
FIR19-00629 INSP-Final Inspection8/30/20198/30/20198/30/2019 8:48:45 AMAPASS
Final fire alarm inspection for area of work complete.
FIR19-00614 INSP-Sprinkler Rough-in8/29/20198/30/20198/30/2019 8:12:18 AMAPART
Rough to cover inspection for underground stub in (approximately 15 feet of pipe)and riser pipe complete, area inspected approved for cover, remaining underground to be installed at a later date.

Contact Keith Orahood ###-#### 30 min prior to UG rough in insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-02029 FIRE-Final Inspection8/30/20198/30/20198/30/2019 7:34:08 AMAPASS
No fire sprinklers, no fire alarms, final life fire safety inspection for area of work complete, card has been signed.
BLD19-00703 FIRE-Final Inspection8/29/20198/30/20198/30/2019 7:32:14 AMAPASS
Previously noted items have been corrected except for the round type door hardware that is still on 3 doors, the mech room door, janitors closet and large room southside basement, round type door hardware needs to be replaced with code compliant door hardware before BLD final, hardware change will be verified during BLD final per conversation with Dave Hannah. Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags, final life fire safety inspection is complete, card has been signed for fire alarm, fire sprinkler and life safety.

Mike Phone #: ###-####
FIR19-00555 INSP-Final Inspection8/29/20198/30/20198/30/2019 7:28:07 AMAPASS
Final fire alarm inspection for area of work complete, other items noted are to be completed under FIR19-00642, this permit is finaled.

Per Ron Johnson this one will be given a TCO once permit FIR19-00642 was applied for. Phone #: ###-#### Inspection requested via web by Kristin Dolan
FIR19-00620 INSP-Final Inspection8/30/20198/30/20198/30/2019 7:26:53 AMAFAIL
Inspection request was for after hours, fees were not paid for after hours inspection. Tenant owner was not available, could not access tenant space.