Inspections for the day of: Monday, August 5, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00263 INSP-Sprinkler Rough-in/Hydro8/5/20198/5/20198/5/2019 4:46:54 PMPPART
Hydrostatic test for FDC piping witnessed, no pressure loss observed.

Robert Chambers is the contact. He would like to do an FDC Hydro at the same time. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00263 INSP-Sprinkler Rough-in8/5/20198/5/20198/5/2019 2:32:28 PMPPART
Rough to cover inspection for overhead fire sprinkler piping in corridor soffits, level 2B complete, corridor soffits on level 2B approved for cover.
BLD19-02918 FIRE-Final Inspection8/2/20198/5/20198/5/2019 2:12:23 PMPFAIL
Provide door hardware on the designated exit doors that does not require twisting of the wrist as specified on the city approved documents.

Cammra-please call so she can meet Phone #: ###-####
BLD17-01950 FIRE-Final Inspection8/1/20198/5/20198/5/2019 1:16:51 PMAFAIL
Provide city approved drawings as well as small documents from building permit fire code review.

Dillon Phone #: ###-####
FIR19-00426 INSP-Sprinkler Rough-in/Hydro8/2/20198/5/20198/5/2019 10:06:10 AMPFAIL
Upright head in Meeting Room C is overspaced, needs corrected. Correct head blockage in mechanical room, mech room has a duct over 48 inches that needs a head installed under, numerous heads are blocked by ductwork in mechanical room. Provide fire sprinkler protection under stairs per 8.15.3.2 of the 2016 NFPA13.

Verfiy that the sidewall heads in the "Quiet Room" meet the requirements of 8.7.4.1 of the 2016 NFPA 13 .

Contact Keith Orahood ###-#### 30 Min prior to RTC/Hydro Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-02553 FIRE-Final Inspection8/2/20198/5/20198/5/2019 9:13:12 AMAFAIL
Racking permit is required if storage racks stay the same height, current top shelf exceeds 8 feet and storage exceeds 12 feet, racking cannot exceed 8 feet without a racking permit. Provide sticker at main entrance reading "Door to remian unlocked while building is occupied".

Jason Phone #: ###-####
FIR19-00417 INSP-Final Inspection8/5/20198/5/20198/5/2019 8:31:44 AMPPASS
Final fire sprinkler inspection for area of work complete.

Please call Adam for inspection. Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR19-00536 INSP-Supply line flush7/30/20198/5/20198/5/2019 8:31:01 AMADONE
Flush has been completed.

Flush with Suez at 10 am Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR19-00237 INSP-Sprinkler Rough-in8/1/20198/5/20198/5/2019 8:30:30 AMAFAIL
Called point of contact 3 times over a 30 minute time span, all calls went straight to voicemail, mailbox was not set up so message could not be left, inspection will need to be rescheduled.

Contact Tyler Loomis - ###-#### 30 Min Prior to RTC nsp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank