Inspections for the day of: Tuesday, August 6, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00834 INSP-Sprinkler Rough-in/Hydro8/5/20198/6/20198/6/2019 4:34:23 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00362 INSP-Final Inspection8/5/20198/6/20198/6/2019 2:56:17 PMPCANC
Inspection request is cancelled, addressing needs to be corrected by the GC for the BLD permit assigned to this space, cannot final permit until addressing is corrected and project related permits have the correct address for tenant space, 509 McGregor is already used by COI in the same building and no suite number has been assigned to this tenant space.

Plans on site Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-01802 FIRE-Final Inspection8/5/20198/6/20198/6/2019 2:53:04 PMPFAIL
509 address is already assigned to the COI tenant space, need to have addressing corrected for this tenant space before life fire safety can be finaled.

Please call 30 min ahead Phone #: ###-#### Inspection requested via web by Chase Cheverton
FIR19-00398 INSP-Final Inspection8/2/20198/6/20198/6/2019 12:50:58 PMAPART
Fire sprinklers in area or work have been removed from service leaving areas of work with no active fire sprinklers. Permit will remain in issued status until sprinklers are made active or a permit is issued for new work to be completed, as of this entry no permit for sprinkler modifications exist.

Contact is Nate Meikle with Okland Construction Phone #: ###-#### Inspection requested via web by Paul Marcolina
FIR18-00834 INSP-Sprinkler Rough-in8/6/20198/6/20198/6/2019 12:13:41 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
FIR19-00237 INSP-Sprinkler Rough-in/Hydro8/6/20198/6/20198/6/2019 11:40:22 AMPFAIL
Fire sprinkler upright in mech room is 8 foot off of the wall, correct overspace issue. Install correct type hanger where grid wire is holding up the pipe. Correct areas where sammy type hangers are not installed correctly, refer to manufactures documents for listed install for sammy type hanger attatchment. Relocate sidewall head that is blocked when door is open.

Contact Tyler Loomis ###-#### 30 min prior to RTC/Hydro Insp start please..Tyler has a Dr Appt. and would like to do this around 1:30 pm if at all possible please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00549 INSP-Final Inspection8/5/20198/6/20198/6/2019 9:55:02 AMAPASS
Final fire sprinkler inspection for area of work complete.

Plans are on site Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00549 INSP-Sprinkler Rough-in8/6/20198/6/20198/6/2019 9:54:35 AMAPASS
Rough to cover inspection for fire sprinkler piping in area of work complete, approevd for cover.

BLD19-02918 FIRE-Final Inspection8/5/20198/6/20198/6/2019 9:31:35 AMAPASS
Previously noted items have been corrected, no fire sprinklers, no fire alarm modifications, fire exitnguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.

Cammra Phone #: ###-####
BLD19-02376 FIRE-Final Inspection8/6/20198/6/20198/6/2019 9:18:32 AMAPART
Partial final inspection for life fire safety complete, fire sprinkler inspection is complete, fire alarm inspection for space is complete but fire alarm system has items that need to be resloved before fire alarm permit will be finaled, fire exitnguisher will be placed in discussed location and has a current inspection tag. TCO authorized for 30 days contingent on the fire alarm issues being resloved.
FIR19-00555 INSP-Final Inspection8/5/20198/6/20198/6/2019 9:15:16 AMAPART
Partial final fire alarm inspection complete, TCO authorized for 30 days contingent on noted items being repaired. Notification works in tenant space, fire panel has ground fault that is being resloved and the network interface between fire panels needs to be resloved.

Clint Phone #: ###-####
FIR19-00237 INSP-Sprinkler Rough-in/Hydro8/6/20198/6/20198/6/2019 8:19:37 AMPCANC
Contact Tyler Loomis 208-859--6589 30 min prior to RTC/Hydro Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
FIR19-00555 INSP-Alarm Testing8/5/20198/6/20198/5/2019 12:00:00 AMACANC
Damion Phone #: ###-####