Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00505 INSP-Sprinkler Rough-in8/8/20198/8/20198/8/2019 4:17:28 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Tom Phone #: ###-####
FIR19-00263 INSP-Sprinkler Rough-in/Hydro8/7/20198/8/20198/8/2019 4:16:48 PMPPART
Hydrostatic test for level 2 overhead fire sprinkler piping witnessed, no pressure loss observed.

Robert Chambers is the contact. This Hydro is for the 1st and 2nd floors. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00254 INSP-Sprinkler Rough-in8/8/20198/8/20198/8/2019 4:14:07 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
FIR19-00254 INSP-Sprinkler Rough-in/Hydro8/8/20198/8/20198/8/2019 4:13:26 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed at 200PSI, above the static city pressure requirement, no pressure loss observed.

Overhead rough/hydro and tenting. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-00142 FIRE-Final Inspection8/8/20198/8/20198/8/2019 3:50:40 PMPPART
Partial final inspection for life fire safety inspection complete, final sign off is contingent upon FIR19-00588 being completed for the out of sync correction for fire alarm system. Scope of work for JCI on the fire alarms is complete, no fire sprinklers, fire extinguishers are placed with current inspection tags. 30 day TCO authorized per conversation with Romeo Gervais with Boise Fire for life fire safety.

Rescheduled by Doug for PM inspection when JCI can have a technician on site. 208.860.1445
FIR19-00242 INSP-Final Inspection8/7/20198/8/20198/8/2019 3:46:45 PMPPASS
Previously noted except for the sync issue have been corrected, sync repair is being addressed under a seperate permit, FIR19-00588. Final inspection for this scope of work complete.

DEMIAN Phone #: ###-####
FIR19-00552 INSP-Sprinkler Rough-in8/8/20198/8/20198/8/2019 2:29:56 PMPPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Jonathan LaFond
FIR19-00552 INSP-Final Inspection8/8/20198/8/20198/8/2019 2:29:23 PMPPASS
Rough in inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Jonathan LaFond
BLD14-02415 FIRE-Final Inspection8/8/20198/8/20198/8/2019 1:56:47 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers will be placed in discussed locations. Final life fire safety inspection complete.

Tony- Call for access (need key) Phone #: ###-####
FIR19-00190 INSP-Final Inspection8/7/20198/8/20198/8/2019 11:49:42 AMAPASS
Final fire sprinkler inspection complete.

Josh Eaton is the contact. He was already arranged a time with Jim Page. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-00560 FIRE-Final Inspection8/2/20198/8/20198/8/2019 11:49:17 AMAFAIL
Corrections have not been made to the fire sprinkler modifications, FIR permit for area of work is still in issued status, FIR19-00459, reference notes entered by Troy Cobbley on 02AUG2019.

Ann Phone #: ###-####
FIR19-00426 INSP-Sprinkler Rough-in8/7/20198/8/20198/8/2019 11:00:50 AMAFAIL
Upright heads in meeting room C are still overspaced. No corrections were made to Quiet Room sidewalls or mech room blocked heads. Added head under stairs needs a hanger, almost 3 foot of unsupported pipe.

Contact Keith Orahood ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00261 INSP-Sprinkler Rough-in8/7/20198/8/20198/8/2019 10:36:56 AMAFAIL
Tenting needs to be corrected in numerous areas.

Ron-insulation Phone #: ###-####
BLD18-01246 FIRE-Final Inspection8/7/20198/8/20198/8/2019 10:08:23 AMPPASS
Remaining item for radio coverage complete, final life fire safety inspection complete.

Phone #: ###-#### Inspection requested via web by Sam Reading
FIR19-00402 INSP-Final Inspection8/7/20198/8/20198/8/2019 10:04:59 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR19-00237 INSP-Sprinkler Rough-in8/7/20198/8/20198/8/2019 9:25:04 AMAPASS
Previously noted items have been repaired for rough to cover in basement area, basement area approved for cover.

Contact Tyler Loomis ###-#### 30 min prior to RTC Insp Start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-00425 FIRE-Final Inspection8/7/20198/8/20198/8/2019 9:23:42 AMAFAIL
Need exhaust fan on paint booth to shut down when fire alarm activates. Repair emergency lighting that did not work on the exterior whip emergency light and fix the inop light on the interior middle door egress lighting.

JAKE- Phone #: ###-####
FIR19-00576 INSP-Final Inspection8/8/20198/8/20198/8/2019 9:23:42 AMPPART
Partial final for fire alarm inspection complete, riser monitoring has been completed, need to have exhaust fan on paint booth needs to shut down during general fire alarm.

Phone #: ###-#### Inspection requested via web by Robert Gobler
FIR19-00358 INSP-Final Inspection8/7/20198/8/20198/8/2019 9:23:41 AMAPASS
Final fire sprinkler inspection for area of work complete.

Mike O Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR19-00533 INSP-Final Inspection8/7/20198/8/20198/8/2019 12:00:00 AMAPASS
9/10 am please-Zach Phone #: ###-####
All systems tested. No faults found.