FIR19-00378
| INSP-Final Inspection | 8/9/2019 | 8/9/2019 | 8/9/2019 1:45:52 PM | P | FAIL |
|
|
Noted defecincies in multi purpose room located by the kitchen and in the kitchen area on city approved drawings, stopped inspection at kitchen due too the number of defecincies, notated issues that were inspected on the city approved drawing.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00882
| INSP-Final Inspection | 8/9/2019 | 8/9/2019 | 8/9/2019 1:41:49 PM | P | CANC |
|
|
Cancelled per conversation with point of contact, fire alarm not ready.
please call jeff with time frame Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00436
| INSP-Final Inspection | 8/9/2019 | 8/9/2019 | 8/9/2019 12:51:12 PM | P | CANC |
|
|
Cancelled per conversation with Clint at JCI, fire alarm inspection will be rescheduled to coincide with fire sprinkler inspection.
Damnian Phone #: ###-####
|
FIR19-00101
| INSP-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 12:46:59 PM | A | PASS |
|
|
Previously noted items have been corrected, final fire sprinkler inspection complete.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00168
| INSP-Sprinkler Rough-in | 8/8/2019 | 8/9/2019 | 8/9/2019 11:22:55 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping in area of work complete, notated the city approved drawings with red ink areas approved for cover.
Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
|
BLD18-03533
| FIRE-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 11:04:44 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Mark Phone #: ###-####
|
BLD19-02784
| FIRE-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 10:41:58 AM | A | CANC |
|
|
Cancelled per conversation with point of contact, city approved paperwork is not on site, inspection will be rescheduled when city approved documents are on site and available.
ALE Phone #: ###-####
|
BLD19-01808
| FIRE-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 10:15:15 AM | A | PART |
|
|
Partial final inspection for life fire safety inspection complete. Last remaining items include sway bracing mod fire sprinkler permit, (per conversation with Romeo Gervais with Boise Fire, a temp can be given for 30 days, contingent on the fire sprinkler being re-issued and finaled) and door hardware is the existing round type, plans show lever type hardware that is on back order, will be installed when recieved. Fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. TCO for life fire safety authorized for 30 days.
Phone #: ###-#### Inspection requested via web by Mike Walling
|
FIR19-00290
| INSP-Sprinkler Rough-in | 8/8/2019 | 8/9/2019 | 8/9/2019 9:14:39 AM | A | PART |
|
|
Inspection for preset hangers complete, verified back nuts are in place with sammy attachments, preset hangers approved for cover.
Todd Ketterling is the contact. He would like a hanger inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00425
| FIRE-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 9:13:51 AM | A | PASS |
|
|
Previously noted items have been corrected, sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags, paint booth fan shut down tested with fire alarm interface. Final life fire safety inspection for area of work complete.
Jake Phone #: ###-####
|
FIR19-00576
| INSP-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 9:12:33 AM | A | PASS |
|
|
Previously noted item has been corrected, as-builts will be sent to fire alarm plan reviewer. Final fire alarm inspection complete.
Paint Booth Shut-Down. Phone #: ###-#### Inspection requested via web by Robert Gobler
|
BLD19-02896
| FIRE-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 7:44:37 AM | A | CANC |
|
|
No sign off required for life safety, this request is cancelled.
Final roofing Phone #: ###-#### Inspection requested via web by Frank Roman
|
BLD19-01273
| FIRE-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 7:40:35 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher is placed with a current inspection tag (extinguisher annual inspection due by end August). Final life fire safety inspection for area of work complete.
ZIT Phone #: ###-####
|
FIR19-00481
| INSP-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 7:39:12 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
John Phone #: ###-####
|
FIR19-00575
| INSP-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 7:38:41 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
FIR18-00844
| INSP-Final Inspection | 8/5/2019 | 8/9/2019 | 8/9/2019 7:05:27 AM | A | CANC |
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|