NAF19-00063
| INSP-Final | 9/12/2019 | 9/12/2019 | 9/13/2019 8:57:07 AM | P | CANC |
|
|
Wrong permit was requested by a different permit holder, this request is cancelled.
Call prior to going Phone #: 2088509308 >> Inspection requested via mobile web by Bill Tonkin
|
BLD18-00632
| FIRE-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 5:12:14 PM | P | FAIL |
|
|
FIR permits for hood suppression and fire alarm need to be finaled before life fire safety can be signed as complete. Provice internally illuminated exit signage and emergency lighting on exterior gates. Fire caulk condensate drain hole in riser room, riser room is a 1 hour rated assembly. Escutcheon in level 1 common restroom does not cover the entire sprinkler hole, escutcheon must cover entire hole. Remove masking from sprinkler heads in level 2 janitors closet and mech room.
Jim Phone #: ###-####
|
BLD17-04447
| FIRE-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 5:11:26 PM | P | FAIL |
|
|
FIR permits for hood suppression and fire alarm need to be finaled before life fire safety can be signed as complete. Provice internally illuminated exit signage and emergency lighting on exterior gates. Fire caulk condensate drain hole in riser room, riser room is a 1 hour rated assembly. Escutcheon in level 1 common restroom does not cover the entire sprinkler hole, escutcheon must cover entire hole. Remove masking from sprinkler heads in level 2 janitors closet and mech room.
Jim Phone #: ###-####
|
FIR19-00657
| INSP-Final Inspection | 9/12/2019 | 9/12/2019 | 9/12/2019 5:07:22 PM | P | CANC |
|
|
Cancelled per conversation with point of contact, missing nozzle in exhaust duct, will be rescheduled for a later date.
Inspection for Ansul r102 suppression system Phone #: ###-#### Inspection requested via web by Don Kartchner
|
FIR19-00540
| INSP-Sprinkler Rough-in/Hydro | 9/12/2019 | 9/12/2019 | 9/12/2019 5:06:01 PM | P | CANC |
|
|
Rescheduled for 13SEPT2019 per conversation with point of contact, this request is cancelled.
Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00934
| INSP-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 5:05:08 PM | P | FAIL |
|
|
All audio visual devices have been inspected, all fire sprinkler related items have been inspected with no deficiencies. 6 Smoke detectors in daycare area are within 36 inches of HVAC registers, smoke detectors have to be a minimum of 36 inches away from HVAC registers.
Fire Alarm Final Phone #: ###-#### Inspection requested via web by Ken Webster
|
FIR18-00525
| INSP-Final Inspection | 9/10/2019 | 9/12/2019 | 9/12/2019 5:02:30 PM | P | PASS |
|
|
Final fire sprinkler inspection is complete.
Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-01812
| FIRE-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 2:44:58 PM | P | FAIL |
|
|
Provide city approved drawings, blue prints on site are not the stamped city approved set of drawings.
documentsPhone #: ###-#### Inspection requested via web by Scott Asin
|
NAF19-00095
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:24:58 PM | P | CANC |
|
|
Rescheduled for 13SEPT2019 per conversation with point of contact due to manpower for sprinkler inspections, this request is cancelled.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00096
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:24:41 PM | P | CANC |
|
|
Rescheduled for 13SEPT2019 per conversation with point of contact due to manpower for sprinkler inspections, this request is cancelled.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00333
| INSP-Sprinkler Rough-in/Hydro | 9/12/2019 | 9/12/2019 | 9/12/2019 2:20:45 PM | P | DONE |
|
|
Hydrostatic test for underground supply witnessed, no pressure loss observed.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
NAF19-00094
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:08:49 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00093
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:08:20 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00092
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:07:51 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00091
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:07:21 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00090
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:06:51 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-00975
| FIRE-Conference | 9/12/2019 | 9/12/2019 | 9/12/2019 2:06:24 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Darius Saxton
|
NAF19-00089
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:05:59 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00088
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:05:30 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00087
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:04:55 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00086
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:04:19 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
NAF19-00085
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 2:03:48 PM | P | FAIL |
|
|
Sprinkler head/heads at top of stairs do not extend past wall as shown on approved drawings.
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-02544
| FIRE-Final Inspection | 9/12/2019 | 9/12/2019 | 9/12/2019 1:25:57 PM | P | FAIL |
|
|
Provide emergency lighting for exterior landing discharge per IFC 1008.3.2. Provide fire exitnguisher with a current inspection tag.
John Phone #: ###-####
|
BLD19-00975
| FIRE-Final Inspection | 9/12/2019 | 9/12/2019 | 9/12/2019 1:11:49 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Darius Saxton
|
FIR19-00470
| INSP-Final Inspection | 9/12/2019 | 9/12/2019 | 9/12/2019 1:06:53 PM | P | PASS |
|
|
Final fire sprinkler ispection for area of work complete.
Darius Phone #: ###-####
|
BLD19-00727
| FIRE-Final Inspection | 9/12/2019 | 9/12/2019 | 9/12/2019 12:29:55 PM | P | FAIL |
|
|
Plans inside space did not have city approved stamp. Existing exit sign still in place that is not lined up with any door, another exit sign has been added a short disatnce away from existing that is in the correct location, need exisitng exit sign removed. Ceiling tile not in place next to fire sprinkler head. Main entry has access control mag locks, per IFC chapter 10 of IFC, mag locks need to release under general fire alarm when associated with an egress door.
Please call 30min prior to arrival to insure onsite. Phone #: ###-#### Inspection requested via web by Travis Knutson
|
FIR18-00444
| INSP-Alarm Testing | 9/11/2019 | 9/12/2019 | 9/12/2019 11:56:11 AM | P | CANC |
|
|
Rescheduled per conversation with point of contact, this request is cancelled.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
BLD17-03345
| FIRE-Final Inspection | 9/10/2019 | 9/12/2019 | 9/12/2019 11:55:44 AM | P | CANC |
|
|
Rescheduled per conversation with point of contact, this request is cancelled.
Jason- inspection for Levels #2 and #3 Phone #: ###-####
|
FIR18-00510
| INSP-Final Inspection | 9/12/2019 | 9/12/2019 | 9/12/2019 11:55:09 AM | P | CANC |
|
|
Rescheduled per conversation with point of contact, this request is cancelled.
We want to final off second and third floors and the condos Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00360
| INSP-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 11:51:17 AM | P | FAIL |
|
|
Panel shows ground fault trouble, needs to be corrected. FDC bell only rings with level 1 stair 2 riser, no other flow switches are hooked to bell, FDC bell needs to ring during all water flow events.
Trey Phone #: ###-####
|
FIR18-00633
| INSP-Final Inspection | 9/10/2019 | 9/12/2019 | 9/12/2019 11:48:02 AM | A | PART |
|
|
Fire alarm associated devices have been tested, still need to perform walk through.
Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-03429
| FIRE-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 10:25:19 AM | A | FAIL |
|
|
Provide annual inspection on fire extinguisher, inspection tag shows 2014 as last inspection.
Alison Phone #: ###-####
|
BLD19-03073
| FIRE-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 10:09:49 AM | A | FAIL |
|
|
Exit sign did not operate with loss of AC power.
Alicia Phone #: ###-####
|
FIR19-00621
| INSP-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 10:03:12 AM | A | CANC |
|
|
Cancelled per conversation with Charles, city approved draiwngs not on site.
Chris Lamb is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00280
| INSP-Supply line flush | 9/11/2019 | 9/12/2019 | 9/12/2019 9:44:39 AM | A | DONE |
|
|
Underground main line flush complete.
Troy will coordinate with Suez. Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR19-00506
| INSP-Sprinkler Rough-in | 9/12/2019 | 9/12/2019 | 9/12/2019 9:43:50 AM | A | PASS |
|
|
Previously noted items have been corrected, all tenting in place at time of inspection, rough to cover inspection complete, cover is approved, approval sticker placed by sprinkler riser.
|
FIR19-00506
| INSP-Sprinkler Rough-in/Hydro | 9/11/2019 | 9/12/2019 | 9/12/2019 9:41:52 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed at city pressure, no pressure l;oss observed.
Call Anthony before heading out, thanks! Also Tenting inspection Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00006
| INSP-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 9:18:24 AM | A | PASS |
|
|
Previously noted items have been corrected, downstairs room labeled as pantry will stay as a pantry. Final fire sprinkler inspection is complete.
Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-03231
| FIRE-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 8:39:50 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags, city approved drawings shows doors in office area are existing with no changes, doors have round type door hardware installed. Final life fire safety inspection for area of work complete. Signature provided on permit card.
Jerome Phone #: ###-####
|
FIR19-00370
| INSP-Sprinkler Rough-in | 9/11/2019 | 9/12/2019 | 9/12/2019 8:11:19 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00371
| INSP-Sprinkler Rough-in | 9/11/2019 | 9/12/2019 | 9/12/2019 8:10:38 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00657
| INSP-Final Inspection | 9/10/2019 | 9/12/2019 | 9/12/2019 8:04:01 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Don Kartchner Inspection cancelled from web by: Don Kartchner
|