Inspections for the day of: Friday, September 13, 2019.
Number of inspections: 39
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00360 INSP-Final Inspection9/12/20199/13/20199/13/2019 4:52:09 PMPPART
Initiating devices in common areas tested. Audio visual notification has been tested. Fire sprinkler initiating devices has been tested. Notification to be added in trash rooms on each floor, will verify before final C of O. Monitoring has been verified.

David Phone #: ###-####
FIR18-00633 INSP-Final Inspection9/13/20199/13/20199/13/2019 4:49:29 PMPPASS
Final fire sprinkler inspection complete.

Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-03329 FIRE-Final Inspection9/12/20199/13/20199/13/2019 4:48:59 PMPCANC
Rescheduled for 16SEPT2019 for the AM per conversation with point of contact, this request is cancelled.

Call ahead // Tony Phone #: ###-####
BLD19-00722 FIRE-Final Inspection9/13/20199/13/20199/13/2019 3:22:44 PMPPASS
Scope of work has been completed, no fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Tod Phone #: ###-####
BLD19-00727 FIRE-Final Inspection9/13/20199/13/20199/13/2019 3:03:18 PMPPART
Previously noted items have been corrected, partial final inspection for life fire safety complete. Fire sprinkler inspection is complete, scope of work for fire alarm has been completed but mag locks have been installed and will be programmed by the tenant, per IFC chapter 10, access controled doors in the path of egress must release during general fire alarm, fire extinguisher will be placed in discussed location. 45 day TCO authorized by Ron Johnson with Boise Fire contingent upon mag lock release on fire alarm, a permit will be required for fire alarm modifications. Signature has been provided on sign off card for associated trades.

Phone #: ###-#### Inspection requested via web by Travis Knutson
FIR19-00359 INSP-Sprinkler Rough-in9/13/20199/13/20199/13/2019 2:41:04 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Contact Noemi Carrero - ###-#### 30min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD17-02182 FIRE-Final Inspection9/13/20199/13/20199/13/2019 1:55:03 PMPFAIL
Reference notes entered by Troy Cobbley on 17AUG2017, tenant space is showing 2 suite numbers, 125 and 150, sent point of contact a text message as well as phone call with no answer, proceeded to next inspection.

Please call 30 mins ahead of time so I can meet you out there. Phone #: ###-#### Inspection requested via web by Gerome Fries
BLD19-01272 FIRE-Final Inspection9/13/20199/13/20199/13/2019 1:38:27 PMPDONE
Life fire safety inspection for area of work completed on 28JUNE2019.

John Phone #: ###-####
BLD19-01372 FIRE-Final Inspection9/13/20199/13/20199/13/2019 1:36:34 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas and not in vanilla space, next tenant will be required to have additional fire extinguishers due to current extinguisher spacing. Final life fire safety inspection for vanilla space is complete, signatures provided on sign off card for associated trades, no occupancy allowed under this permit.

John Phone #: ###-####
BLD19-02544 FIRE-Final Inspection9/13/20199/13/20199/13/2019 1:33:09 PMPPASS
Previously noted items have been corrected. No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signature provided on sign off card for associated trades.

John Phone #: ###-####
NAF19-00095 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:17:02 PMPPART
Previously noted items have been corrected. Rough to cover inspection for overhead fire sprinkler piping/tenting is complete, approved for cover. Hydro not ready at time of inspection.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00096 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:15:46 PMPPASS
Previously noted items have been corrected. Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover. Hydrostatic test has been witnessed, no pressure loss observed.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00093 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:12:47 PMPPASS
Previously noted items have been corrected. Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover. Hydrostatic test witnessed, no pressure loss observed.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00090 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:11:03 PMPPART
Previously noted items have been corrected. Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover, hydro was not ready.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00092 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:09:42 PMPFAIL
Level 1 T was dry fit, no hydro performed, cover is not approved.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00094 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:08:27 PMPPART
Previously noted items have been corrected. Rough in inspection for overhead fire sprinkler piping complete, sprinkler piping between conditioned spaces approved for cover, not all tenting in place at time of inspection, piping requiring tenting not approved for cover. Hydrostatic test has been witnessed, no pressure loss observed.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00091 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:07:39 PMPPART
Previously noted items have been corrected. Rough in inspection for overhead fire sprinkler piping complete, sprinkler piping between conditioned spaces approved for cover, not all tenting in place at time of inspection, piping requiring tenting not approved for cover. Hydrostatic test has been witnessed, no pressure loss observed.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00089 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:05:09 PMPPART
Previously noted items have been corrected. Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover, no hydro at this time.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00088 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:04:28 PMPPART
Previously noted items have been corrected. Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover, no hydro at this time.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00087 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:03:47 PMPPART
Previously noted items have been corrected. Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approevd for cover, no hydro at this time.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00086 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 1:01:35 PMPPART
Hydro was not ready, rough in inspection complete, piping between conditioned spaces approved for cover, not all tenting in place at time of inspection, cover is not approved where tenting is required.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
NAF19-00085 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 12:59:24 PMPPART
Hydro was not ready, rough in inspection complete, piping between conditioned spaces approved for cover, not all tenting in place at time of inspection, cover is not approved where tenting is required.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-03073 FIRE-Final Inspection9/12/20199/13/20199/13/2019 11:59:54 AMAPASS
Exit light has been removed, final life fire safety inspection for area of work complete.

ALICIA Phone #: ###-####
FIR19-00540 INSP-Supply line flush9/13/20199/13/20199/13/2019 11:46:15 AMAPART
Rough to cover inspection is complete, city approved drawings will need to show the additional head on level 3. Levels 1 and 2 are approved for cover, level 3 is not approved for cover until freeze protection is in place, inspected and approved for cover. Spray foam insulation is being used, the pocket between sheetrock and piping must be maintained, a letter of compatability needs to be submitted to Mark Stumbaugh, Fire Sprinkler Plan Reviewer, if spray foam is not compatable with CPVC piping then any and all piping that has spray foam on piping will be required to be replaced. As shown on city approved drawings, a minimum of R38 is required over the top of the piping.
FIR19-00540 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/13/2019 11:39:29 AMAFAIL
Level 3 hydro complete with no loss at gauge, levels 1 and 2 both lost pressure.

Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00579 INSP-Final Inspection9/12/20199/13/20199/13/2019 11:38:07 AMAPASS
Final fire sprinkler inspection for area of work complete.

Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
BLD17-04630 FIRE-Final Inspection9/12/20199/13/20199/13/2019 10:46:45 AMAPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, heat trace inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, signatures provided on sign off card for associated trades.

call me when on site Phone #: ###-#### Inspection requested via web by J.C. Murray
BLD17-00634 FIRE-Final Inspection9/13/20199/13/20199/13/2019 10:04:00 AMPDONE
Life fire safety inspection for this permit scope of work was completed on 18OCT2018.

Ed Phone #: ###-####
BLD19-03345 FIRE-Final Inspection9/12/20199/13/20199/13/2019 10:00:45 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on sign off card.

Mandy Phone #: ###-####-please call ten minutes prior to meet for access
BLD19-03396 FIRE-Final Inspection9/12/20199/13/20199/13/2019 9:59:42 AMAFAIL
Provide fire alarm notification in break room area as discussed, all fire alarm modifications require a permit for the work to be completed and inspected.

Mandy Phone #: ###-####-please call ten minutes prior to meet for access
FIR19-00660 INSP-Sprinkler Rough-in/Hydro9/13/20199/13/20199/13/2019 9:29:08 AMPCANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Friday, September 13, 2019.
FIR19-00582 INSP-Final Inspection9/12/20199/13/20199/13/2019 9:25:29 AMAPASS
Final fire sprinkler inspection for area of work complete.

Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
BLD18-02566 FIRE-Final Inspection9/12/20199/13/20199/13/2019 9:24:30 AMACANC
Previous permit for area of work has not been finaled, BLD17-00634, this permit needs to finaled before any life safety items can be addressed for this permit. Spoke with point of contact, he is going to work on getting BLD17-00634 finaled so we can proceed with this permit. This request is cancelled per conversation with point of contact.

Ed Phone #: ###-####
NAF19-00005 INSP-Final9/12/20199/13/20199/13/2019 9:06:34 AMADONE
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags, noted that east side exit door has thumturn deadbolt on door, this door is outside of the scope of work. Final life fire safety inspection for area of work complete.

Call prior to going Phone #: 2088509308 >> Inspection requested via mobile web by Bill Tonkin
NAF18-00115 INSP-Final9/10/20199/13/20199/13/2019 8:49:26 AMADONE
Previously noted items have been corrected, no fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tags. Final life fire safety inspection for area of work passed and complete.

As early as possible Phone #: 2089015831 >> Inspection requested via mobile web by Jinny Gerry
BLD19-03434 FIRE-Final Inspection9/11/20199/13/20199/13/2019 8:27:52 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags, some interior doors have existing round type door hardware. Final life fire safety inspection for atrea of work complete.

call to meet // rex Phone #: ###-####
BLD19-01812 FIRE-Final Inspection9/12/20199/13/20199/13/2019 7:59:41 AMAPASS
Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Scott Asin
NAF19-00096 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/12/2019 9:59:14 PMACANC
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
NAF19-00095 INSP-Sprinkler Rough-in/Hydro9/12/20199/13/20199/12/2019 9:59:12 PMACANC
Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello