BLD19-03034
| FIRE-Final Inspection | 9/13/2019 | 9/16/2019 | 9/16/2019 8:55:46 AM | A | FAIL |
|
|
FIR permit for fire alarm modifications needs to be completed before life fire safety inspection will be performed.
Ask for Jeff Roelke at the front door (he''ll have to let you in). Phone #: ###-#### Inspection requested via web by Todd Weltner
|
BLD19-02723
| FIRE-Final Inspection | 9/13/2019 | 9/16/2019 | 9/16/2019 7:07:14 AM | A | PASS |
|
|
Fire sprinklker inspection is complete, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on sign off card.
Tom Phone #: ###-####
|
BLD19-02722
| FIRE-Final Inspection | 9/13/2019 | 9/16/2019 | 9/16/2019 7:05:59 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on signature card.
Tom Phone #: ###-####
|
FIR19-00608
| INSP-Final Inspection | 9/12/2019 | 9/16/2019 | 9/16/2019 7:04:20 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
This will need to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00550
| INSP-Final Inspection | 9/12/2019 | 9/16/2019 | 9/16/2019 7:03:46 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
This will need to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00672
| INSP-Conference | 9/13/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | A | FAIL |
|
|
** Failed. Plan Mod needed for piping changes. Head at entryway needs moved for proper coverage. Piping on 2nd floor in unheated concealed space needs rerouted out of concealed space to allow for proper freeze protection. GC to build wall in storage area under stair so head is no more than 10' away. Discussed insulation options, and requirements with GC.*MAS**
Gabe Garduno is the contact for this consultation. Thank you for your help. Have a great day. Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
FIR18-00444
| INSP-Alarm Testing | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | A | PART |
|
|
Tested smoke detectors with sounders in dwelling units for floors 2 and 3. (units are complete and GC wants to lock them up to prevent damage). Accessible unit 211 has a strobe in the laundry room that failed. No other areas were tested and the system is not complete so at least partial retest is advised.
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR19-00673
| INSP-Sprinkler Rough-in | 9/16/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
**Passed Above Ceiling. As built drawings needed before final inspection*MAS**
Todd Phone #: ###-####
|
FIR19-00673
| INSP-Sprinkler Rough-in | 9/13/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | CANC |
|
|
**Inspection done on 9/16/2019*MAS**
Todd Phone #: ###-####
|