Inspections for the day of: Monday, September 16, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-03034 FIRE-Final Inspection9/13/20199/16/20199/16/2019 8:55:46 AMAFAIL
FIR permit for fire alarm modifications needs to be completed before life fire safety inspection will be performed.

Ask for Jeff Roelke at the front door (he''ll have to let you in). Phone #: ###-#### Inspection requested via web by Todd Weltner
BLD19-02723 FIRE-Final Inspection9/13/20199/16/20199/16/2019 7:07:14 AMAPASS
Fire sprinklker inspection is complete, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on sign off card.

Tom Phone #: ###-####
BLD19-02722 FIRE-Final Inspection9/13/20199/16/20199/16/2019 7:05:59 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on signature card.

Tom Phone #: ###-####
FIR19-00608 INSP-Final Inspection9/12/20199/16/20199/16/2019 7:04:20 AMAPASS
Final fire alarm inspection for area of work complete.

This will need to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00550 INSP-Final Inspection9/12/20199/16/20199/16/2019 7:03:46 AMAPASS
Final fire sprinkler inspection for area of work complete.

This will need to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00672 INSP-Conference9/13/20199/16/20199/16/2019 12:00:00 AMAFAIL
** Failed. Plan Mod needed for piping changes. Head at entryway needs moved for proper coverage. Piping on 2nd floor in unheated concealed space needs rerouted out of concealed space to allow for proper freeze protection. GC to build wall in storage area under stair so head is no more than 10' away. Discussed insulation options, and requirements with GC.*MAS**
Gabe Garduno is the contact for this consultation. Thank you for your help. Have a great day. Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR18-00444 INSP-Alarm Testing9/15/20199/16/20199/16/2019 12:00:00 AMAPART
Tested smoke detectors with sounders in dwelling units for floors 2 and 3. (units are complete and GC wants to lock them up to prevent damage). Accessible unit 211 has a strobe in the laundry room that failed. No other areas were tested and the system is not complete so at least partial retest is advised.

As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR19-00673 INSP-Sprinkler Rough-in9/16/20199/16/20199/16/2019 12:00:00 AMPPASS
**Passed Above Ceiling. As built drawings needed before final inspection*MAS**
Todd Phone #: ###-####
FIR19-00673 INSP-Sprinkler Rough-in9/13/20199/16/20199/16/2019 12:00:00 AMPCANC
**Inspection done on 9/16/2019*MAS**
Todd Phone #: ###-####