BLD17-02261
| FIRE-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 3:07:47 PM | A | PART |
|
|
Partial final inspection for life fire safety complete, fire sprinkler inspection is complete, fire alarm system drawings need to be updated and resubmitted before final sign off due to the number of changes required to make it code compliant, fire extinguishers have been placed with current inspection tags. Remaining items to inspect for final sign off are:
1. Install permanent signage on stairwells/fire sprinkler riser room and FACP.
2. Provide inspection report for elevator inspection recall and shunt.
3. Update fire alarm drawings an resubmit for approval.
4. Change thumbturn deadbolts on sliding glass doors, level 2, to single action door hardware.
5. Provide a barrier for fall protection on roof top access ladder, stair 3. 6. Provide opening or gates in metal surround by HVAC units on roof for fireman access as discussed. 7. Hose valves on levels 1 through 4 project into the path of egress more than 4 inches, per IFC 1003.3.3, if a horizontal projection sticks out into the path of egress more than 4 inches then gaurds have to be provided if the projection doesn't impede the minimum width for the path of egress. If valves do in fact project into the path of egress, then hose valves will be required to be installed in a recessed cabinet.
45 day TCO authorized per conversation with Ron Johnson with Boise Fire Department.
David Phone #: ###-####
|
BLD17-02262
| FIRE-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 3:07:27 PM | A | PART |
|
|
Partial final inspection for life fire safety complete, fire sprinkler inspection is complete, fire alarm system drawings need to be updated and resubmitted before final sign off due to the number of changes required to make it code compliant, fire extinguishers have been placed with current inspection tags. Remaining items to inspect for final sign off are:
1. Install permanent signage on stairwells/fire sprinkler riser room and FACP.
2. Provide inspection report for elevator inspection recall and shunt.
3. Update fire alarm drawings an resubmit for approval.
4. Change thumbturn deadbolts on sliding glass doors, level 2, to single action door hardware.
5. Provide a barrier for fall protection on roof top access ladder, stair 3. 6. Provide opening or gates in metal surround by HVAC units on roof for fireman access as discussed. 7. Hose valves on levels 1 through 4 project into the path of egress more than 4 inches, per IFC 1003.3.3, if a horizontal projection sticks out into the path of egress more than 4 inches then gaurds have to be provided if the projection doesn't impede the minimum width for the path of egress. If valves do in fact project into the path of egress, then hose valves will be required to be installed in a recessed cabinet.
45 day TCO authorized per conversation with Ron Johnson with Boise Fire Department.
|
BLD17-02261
| FIRE-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 2:33:40 PM | P | CANC |
|
|
Duplicate inspection request, this request is cancelled.
Curtis Phone #: ###-####
|
BLD17-02262
| FIRE-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 2:33:24 PM | P | CANC |
|
|
Duplicate inspection request, this request is cancelled.
Curtis Phone #: ###-####
|
BLD19-00142
| FIRE-Final Inspection | 9/18/2019 | 9/18/2019 | 9/18/2019 2:32:51 PM | P | PASS |
|
|
Fire alarm issues have been resolved under FIR19-00588, final life fire safety inspwection for areas of work complete.
|
FIR19-00540
| INSP-Sprinkler Rough-in/Hydro | 9/18/2019 | 9/18/2019 | 9/18/2019 2:31:42 PM | P | DONE |
|
|
Hydrostatic test for levels 1 and 2 witnessed, no pressure loss observed.
Robert Chambers is the contact. He would prefer this in the later afternoon/evening if possible. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00418
| INSP-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 10:56:48 AM | P | FAIL |
|
|
Sprinkler escutcheon does not cover entire hole in 3 areas, master closet, master bedroom and sidewall under stairs. Sprinkler timer is sitting on garage floor, sprinkler timer must be in place and permanent wiring installed before final inspection.
Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00672
| INSP-Sprinkler Rough-in | 9/17/2019 | 9/18/2019 | 9/18/2019 10:21:28 AM | A | PART |
|
|
Previously noted items have been corrected, rough in inspection for overhead fire sprinkler piping is complete, plan mod still needs to be submitted as of this entry, cover is not approved until plan mod has been reviewed and accepted.
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00286
| FIRE-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 10:03:05 AM | A | PASS |
|
|
Previously noted items have been corrected, no fire sprinklers, no fire alarm modificaitons, fire extinguisher is placed with a current inspection tag, round type door hardware on breakroom door to be changed to lever type before building final, will be verified during final inspection. Final life fire safety inspection for area of work complete, signature card not provided, no signatures given.
Kaleb Phone #: ###-####
|
BLD19-02470
| FIRE-Final Inspection | 9/18/2019 | 9/18/2019 | 9/18/2019 9:55:42 AM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection is complete, fire extinguisher was placed in discussed location and has a current inspection tag. Final life fire safety inspection for area of work is complete, signatures provided for associated trades on sign off card.
|
BLD19-03034
| FIRE-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 9:47:46 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided for associated trades on sign off card.
Ask for Jeff Roelke at the front door (he''ll have to let you in). Phone #: ###-#### Inspection requested via web by Todd Weltner
|
FIR19-00506
| INSP-Sprinkler Rough-in/Hydro | 9/17/2019 | 9/18/2019 | 9/18/2019 9:34:03 AM | A | DONE |
|
|
Re-hydro witnessed after pipe relocation, no pressure loss observed.
Re-Hydro. We had to cut out a line of pipe due to conflict with another trade, and reinstalled it under the stairs. Call Anthony before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-01127
| FIRE-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 8:56:49 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature card not provided at time of inspection, no signatures given.
Zach Phone #: ###-####
|
FIR19-00635
| INSP-Sprinkler Rough-in | 9/17/2019 | 9/18/2019 | 9/18/2019 7:23:48 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00633
| INSP-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 7:05:23 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Needs to be done at 7:00 am Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00649
| INSP-Final Inspection | 9/17/2019 | 9/18/2019 | 9/18/2019 7:04:44 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|